Lennox HSXA15 SERIES Installation Instructions Manual Download Page 14

Page 14

IMPORTANT

Leak detector must be capable of sensing HFC re-
frigerant.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.

 1 − Connect manifold gauge set to the service valve ports :

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open  both  manifold  valves  and  start  the  vacuum

pump.

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches  of mercu-

ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in 

absolute pressure

.

A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches  of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.

WARNING

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use com-
pressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When the absolute pressure requirement above has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R410A
refrigerant. Open the manifold gauge valves to break
the vacuum from 1 to 2 psig positive pressure in the line
set and indoor unit. Close manifold gauge valves and
shut off the R410A cylinder and remove the manifold
gauge set.

Start−Up

 1 − Rotate fan to check for frozen bearings or binding.

 2 − Inspect all factory− and field−installed wiring for loose

connections.

 3 − After evacuation is complete, open the liquid line and

vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.

 4 − Replace the stem caps and secure finger tight, then

tighten an additional one-sixth (1/6) of a turn.

 5 − Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you
have consulted the power company and the voltage
condition has been corrected.

 6 − Set the thermostat for a cooling demand. Turn on pow-

er to the indoor blower and close the outdoor unit dis-
connect switch to start the unit.

 7 − Recheck voltage while the unit is running. Power must

be within range shown on the nameplate.

Summary of Contents for HSXA15 SERIES

Page 1: ...matched with an indoor coil as specified in Lennox Engineering Handbook Coils previously charged with HCFC 22 must be flushed INSTALLATION INSTRUCTIONS HSXA15 SERIES UNITS CONDENSING UNITS 504 668M 0...

Page 2: ...SXA15 024 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 2 7 8 5 1 2 HSXA15 024 mm 708 657 759 311 570 367 562 73 140 HSXA15 030 HSXA15 036 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8...

Page 3: ...t avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab plat forms or supports Refer to figure 2 for installation clear ances 36 914 mm 36 914 mm 36 914 mm 36 914...

Page 4: ...CEC Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Page 5: ...W Y G C Thermostat Indoor Unit Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is...

Page 6: ...fty feet 15 m For applications longer than fifty feet consult the Lennox Refrig erant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Inst...

Page 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Page 10: ...ls used in this system absorb mois ture quickly Failure to install the filter drier will void the warranty Flushing Existing Line Set Indoor Coil IMPORTANT If this unit is being matched with an approv...

Page 11: ...ice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap proved for use with R410A refrigerant and may pre vent proper flushing Use a field provided f...

Page 12: ...or use with R410A refrigerant in the liquid line at the indoor coil Refrigerant Metering Devices Use HSXA15 units in TXV systems systems See the Len nox Engineering Handbook for approved TXV match ups...

Page 13: ...ning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry ni...

Page 14: ...he manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid deep vacuum operation Do not use com pressors to e...

Page 15: ...he colder months The method of charging is deter mined by the unit s refrigerant metering device and the outdoor ambient temperature Measure the liquid line temperature and the outdoor ambi ent temper...

Page 16: ...quid Line Temp Outdoor Ambient F C HSXA15 024 8 1 4 5 5 HSXA15 030 8 1 4 5 5 HSXA15 036 6 1 3 3 5 HSXA15 042 9 1 5 5 HSXA15 048 8 1 4 5 5 HSXA15 060 12 1 6 7 5 NOTE For best results the same electroni...

Page 17: ...14 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0 57 161 0 88 266 0 119 412 2 1...

Page 18: ...necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check condensate line and clean if necessary Indoor Unit 1 Clean or change filters 2 Adjust blower speed for cooling Measure t...

Reviews: