Lennox HSXA15 SERIES Installation Instructions Manual Download Page 13

Page 13

To Open Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex−head extension to

back the stem out counterclockwise as far as pos-
sible.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

Service Valve

(Valve Closed)

Schrader valve open

to line set when valve is

closed (front seated)

service

port

service

port cap

stem cap

insert hex

wrench here

(valve front seated)

to outdoor coil

to indoor coil

Service Valve

(Valve Open)

Schrader

valve

service

port

service port

cap

insert hex

wrench here

to indoor coil

to outdoor coil

stem cap

Figure 12

To Close Service Valve:

 1 − Remove the stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex−head extension to

turn the stem clockwise to seat the valve. Tighten it
firmly.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

Leak Testing

After the line set has been connected to the indoor and
outdoor units, check the line set connections and indoor
unit for leaks. 

WARNING

Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

 

WARNING

Danger of explosion:  Can cause
equipment damage, injury or death.
Never use oxygen to pressurize a re-
frigeration or air conditioning system.
Oxygen will explode on contact with
oil and could cause personal injury.

WARNING

Danger of explosion:  Can cause equipment damage,
injury or death. When using a high pressure gas
such as dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).

Using an Electronic Leak Detector

 1 − Connect the high pressure hose of the manifold gauge

set to the vapor valve service port. 

(Normally, the high

pressure hose is connected to the liquid line port, how-
ever, connecting it to the vapor port helps to protect the
manifold gauge set from damage caused by high pres-
sure.)

 2 − With both manifold valves closed, connect the cylinder

of R410A refrigerant to the center port of the manifold
gauge set. Open the valve on the R410A cylinder (va-
por only).

 3 − Open the high pressure side of the manifold to allow

R410A into the line set and indoor unit. Weigh in a trace
amount of R410A.

 [A trace amount is a maximum of 2

ounces (57 g) refrigerant or 3 pounds (31 kPa) pres-
sure.] 

Close the valve on the R410A cylinder and the

valve on the high pressure side of the manifold gauge
set. Disconnect R410A cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

 5 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open

the valve on the high side of the manifold gauge set in
order to pressurize the line set and the indoor coil.

 6 − After a few minutes, open a refrigerant port to check

that an adequate amount of refrigerant has been add-
ed for detection (refrigerant requirements will vary
with line lengths). Check all joints for leaks. Purge ni-
trogen and R410A mixture. Correct any leaks and re-
check.

Summary of Contents for HSXA15 SERIES

Page 1: ...matched with an indoor coil as specified in Lennox Engineering Handbook Coils previously charged with HCFC 22 must be flushed INSTALLATION INSTRUCTIONS HSXA15 SERIES UNITS CONDENSING UNITS 504 668M 0...

Page 2: ...SXA15 024 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 2 7 8 5 1 2 HSXA15 024 mm 708 657 759 311 570 367 562 73 140 HSXA15 030 HSXA15 036 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8...

Page 3: ...t avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab plat forms or supports Refer to figure 2 for installation clear ances 36 914 mm 36 914 mm 36 914 mm 36 914...

Page 4: ...CEC Refer to the furnace or blower coil installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protectio...

Page 5: ...W Y G C Thermostat Indoor Unit Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is...

Page 6: ...fty feet 15 m For applications longer than fifty feet consult the Lennox Refrig erant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Inst...

Page 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Page 10: ...ls used in this system absorb mois ture quickly Failure to install the filter drier will void the warranty Flushing Existing Line Set Indoor Coil IMPORTANT If this unit is being matched with an approv...

Page 11: ...ice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap proved for use with R410A refrigerant and may pre vent proper flushing Use a field provided f...

Page 12: ...or use with R410A refrigerant in the liquid line at the indoor coil Refrigerant Metering Devices Use HSXA15 units in TXV systems systems See the Len nox Engineering Handbook for approved TXV match ups...

Page 13: ...ning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry ni...

Page 14: ...he manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid deep vacuum operation Do not use com pressors to e...

Page 15: ...he colder months The method of charging is deter mined by the unit s refrigerant metering device and the outdoor ambient temperature Measure the liquid line temperature and the outdoor ambi ent temper...

Page 16: ...quid Line Temp Outdoor Ambient F C HSXA15 024 8 1 4 5 5 HSXA15 030 8 1 4 5 5 HSXA15 036 6 1 3 3 5 HSXA15 042 9 1 5 5 HSXA15 048 8 1 4 5 5 HSXA15 060 12 1 6 7 5 NOTE For best results the same electroni...

Page 17: ...14 385 4 145 572 8 53 150 1 84 250 3 115 390 7 146 579 8 54 152 8 85 254 1 116 396 0 147 586 8 55 155 5 86 258 0 117 401 3 148 593 8 56 158 2 87 262 0 118 406 7 149 601 0 57 161 0 88 266 0 119 412 2 1...

Page 18: ...necessary 2 Check connecting lines and coils for evidence of oil leaks 3 Check condensate line and clean if necessary Indoor Unit 1 Clean or change filters 2 Adjust blower speed for cooling Measure t...

Reviews: