background image

Page 1

504,669M

*P504669M*

02/04

*2P0204*

2000 Lennox Industries Inc.

Dallas, Texas, USA

HS27 Outdoor Unit

HS27 outdoor units are designed for expansion valve sys-
tems only. They are not designed for RFC systems. Refer to
Lennox engineering handbook for expansion valve kits
which must be ordered separately.

Shipping & Packing List

 1 − Assembled HS27 outdoor unit

 2 − Grommets (for liquid and vapor lines)

 1 − Bushing (for low voltage wiring)

Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.

WARNING

Improper installation, adjustment, alteration, service
or maintenance can cause property damage, person-
al injury or loss of life. Installation and service must
be performed by a qualified installer or service
agency.

IMPORTANT

The Clean Air Act of 1990 bans the intentional vent-
ing of refrigerant (CFC’s and HCFC’s) as of July 1,
1992. Approved methods of recovery, recycling or
reclaiming must be followed. Fines and/or incarcera-
tion may be levied for noncompliance.

INSTALLATION
INSTRUCTIONS

HS27 SERIES UNITS

CONDENSING UNITS

504,669M
02/04
Supersedes 12/02

Table of Contents

HS27 Outdoor Unit

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Shipping & Packing List

1

. . . . . . . . . . . . . . . . . . . . . . . . . 

General Information

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Unit Dimensions

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Parts Arrangement

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Setting the Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Electrical

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Piping

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Metering Device

9

. . . . . . . . . . . . . . . . . . . . . 

Manifold Gauge Set

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Service Valves

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Leak Testing

10

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Evacuation

11

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Charging

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

System Operation

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Maintenance

14

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Optional Accessories

14

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−up & Performance Check List

15

. . . . . . . . . . . . . . . 

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

General Information

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.

WARNING

This product and/or the indoor unit it is matched with
may contain fiberglass wool.

Disturbing the insulation during installation, mainte-
nance, or repair will expose you to fiberglass wool
dust. Breathing this may cause lung cancer. (Fiber-
glass wool is known to the State of California to
cause cancer.)

Fiberglass wool may also cause respiratory, skin,
and eye irritation.

To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.

Lennox Industries Inc.

P.O. Box 799900
Dallas, TX 75379−9900

Litho U.S.A.

Summary of Contents for HS27 Series

Page 1: ...4 669M 02 04 Supersedes 12 02 Table of Contents HS27 Outdoor Unit 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Parts Arrangement 3 Setting the Unit 3 Electrical 3 Refrigerant Pipi...

Page 2: ...View Access View 4 1 2 114 2 3 4 70 4 102 6 1 16 154 1 3 8 35 A 4 7 8 22 4 102 2 9 16 65 18 5 8 473 26 5 8 676 34 1 16 865 2 51 28 1 8 714 7 1 2 191 7 1 2 191 3 7 8 98 3 7 8 98 air inlet air inlet 2 5...

Page 3: ...o avoid accidental contact with sharp edges Refer to unit dimensions for sizing mounting slab platform s or supports Refer to figure 2 for installation clearances 36 914 mm 36 914 mm 36 914 mm 36 914...

Page 4: ...structions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size WARNING Unit must be grounded in accordance with...

Page 5: ...R W Y G C Thermostat Furnace Outdoor Unit Y1 Outdoor Unit C Outdoor Unit power heat cooling indoor blower common NOTE see unit wiring diagram for power supply connections NOTE If the indoor unit is no...

Page 6: ...ing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set contact with the structu...

Page 7: ...id Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve W...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...ne Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 8 Outsid...

Page 10: ...ps If you install an expansion valve with an indoor coil that includes a fixed orifice remove the orifice before instal ling the expansion valve IMPORTANT Failure to remove RFC orifice when installing...

Page 11: ...t hex wrench here valve front seated to outdoor coil to indoor coil Service Valve Valve Open Schrader valve service port service port cap insert hex wrench here to indoor coil to outdoor coil stem cap...

Page 12: ...ollows low pressure gauge to vapor line service valve high pressure gauge to liquid line service valve 2 Connect micron gauge 3 Connect the vacuum pump with vacuum gauge to the center port of the mani...

Page 13: ...or unit should be charged during warm weather However applications arise in which charging must occur in the colder months The method of charging is deter mined by the unit s refrigerant metering devi...

Page 14: ...tdoor ambient temperature to check the liquid line temperature 5 The difference between the ambient and liquid temper atures should match values given in table 4 If the val ues don t agree with the th...

Page 15: ...shed with a water hose Ensure the power is turned off before you clean the coil 2 The outdoor fan motor is prelubricated and sealed No further lubrication is needed 3 Visually inspect connecting lines...

Page 16: ...oor Fan Checked Job No City City Serial No Date State State Service Technician Compressor Outdoor Fan Indoor Filter Clean Electrical Connections Tight Supply Voltage Unit Off Vapor Pressure Thermostat...

Reviews: