Table 32.
Two Stage Heat Pump Unit In First Stage Heating
(Maximum pressure approximately @525PSI)
Size
2 Tons
3 Tons
4 Tons
5 Tons
Unit In First Stage
1.34 Tons
2.01 Tons
2.68 Tons
3.35 Tons
Minimum CFM @380 CFM
Per Ton
509 CFM
764 CFM
1,018 CFM
1,273 CFM
Recommend CFM @450 CFM Per Ton
603 CFM
904 CFM
1,206 CFM
1,508 CFM
V
ariable
c
OndensinG
u
nit
: m
inimum
c
OOlinG
cFm
Table 33. Variable Condensing Unit: Minimum Cooling CFM
(At minimum blower CFM superheat must be at or above 5˚SH)
Model
EL18XCV-024
EL18XCV-036
EL18XCV-048
EL18XCV-060
System at Minimum Capacity
.8 Tons
.875 Ton
1.49 Ton
1.625 Ton
Minimum CFM @300 CFM Per Ton For
Zoning
250 CFM
262.5 CFM
447 CFM
488 CFM
Model
EL18XPV-024
EL18XPV-036
EL18XPV-048
EL18XPV-060
System at Minimum Capacity
.8 Tons
.87 Tons
1.55 Tons
1.78 Tons
Minimum CFM @300 CFM Per Ton For
Zoning
250 CFM
261 CFM
465 CFM
534 CFM