Table 24. SL280UHNV
Model
SL280UH060NV36A
SL280UH080NV48B
SL280UH080NV60C
SL280UH100NV60C
Minimum CFM
574 CFM @50˚F TR
Output BTU 31,000
759 CFM @50˚F TR
Output BTU 41,000
759 CFM @50˚F TR
Output BTU 41,000
963 CFM @50˚F TR
Output BTU 52,000
Factory CFM
825 CFM @35˚F TR
Output BTU 31,000
1,060 CFM @36˚F TR
Output BTU 41,000
1,130 CFM @34˚F TR
Output BTU 41,000
1,425 CFM @34˚F TR
Output BTU 52,000
Maximum CFM
1,482 CFM @30˚F TR
Output BTU 48,000
1,975 CFM @30˚F TR
Output BTU 64,000
1,975 CFM @30˚F TR
Output BTU 64,000
2,469 CFM @30˚F TR
Output BTU 80,000
Table 25. SL280DF
Model
SL280DF070V36A
SL280DF090V48B
SL280DF090V60C
SL280DF110V60C
Minimum CFM
589 CFM @55˚F TR
Output BTU 35,000
774 CFM @55˚F TR
Output BTU 46,000
774 CFM @55˚F TR
Output BTU 46,000
993 CFM @55˚F TR
Output BTU 59,000
Factory CFM
860 CFM @38˚F TR
Output BTU 35,000
1,075 CFM @40˚F TR
Output BTU 46,000
1,245 CFM @34˚F TR
Output BTU 46,000
1,325 CFM @41˚F TR
Output BTU 59,000
Maximum CFM
1,375 CFM @35˚F TR
Output BTU 52,000
1,825 CFM @35˚F TR
Output BTU 69,000
1,851 CFM @35˚F TR
Output BTU 70,000
2,302 CFM @35˚F TR
Output BTU 87,000
sl297uHnV
Table 26. SL297UHNV
Model
SL297UH040NV36B
SL297UH060NV36B
SL297UH080NV48C
SL297UH080NV60C
Minimum CFM
463 CFM @50˚F TR
Output BTU 25,000
640 CFM @55˚F TR
Output BTU 38,000
787 CFM @60˚F TR
Output BTU 51,000
859 CFM @55˚F TR
Output BTU 51,000
Factory CFM
704 CFM @33˚F TR
Output BTU 25,000
886 CFM @40˚F TR
Output BTU 38,000
1,219 CFM @39˚F TR
Output BTU 51,000
1,178 CFM @40.˚F TR
Output BTU 51,000
Maximum CFM
772 CFM @30˚F TR
Output BTU 39,000
704 CFM @50˚F TR
Output BTU 58,000
1050 CFM @45˚F TR
Output BTU 78,000
1181 CFM @40˚F TR
Output BTU 78,000
Summary of Contents for Harmony III