13 - LIGHTING INSTRUCTIONS

1. STOP! Read the safety information above. 
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an ignition device 

which automatically lights the pilot. Do 

not

 try to 

light the pilot by hand.

OFF

ON

INLET

GAS CONTROL  KNOB

PILOT ADJUSTMENT

(UNDER CAP SCREW)

PILOT 
OUTLET

OUTLET

WIRING
TERMINALS (2)

INLET

PRESSURE 

TAP

TERMINALS 
(2)

GROUND

PRESSURE
TAP

PRESSURE REGULATOR ADJUSTMENT
(UNDER CAP SCREW) 

OUTLET 

5. Remove lower front panel.

6. Rotate the gas control knob clockwise 

   to 

“OFF”.

7.  Wait 

fi

 ve (5) minutes to clear out any gas. Then  

smell for gas, including near the 

fl

 oor. If you smell  

gas, STOP! Immediately call your gas supplier from a 

neighbor’s phone. Follow the gas supplier’s instructions. 

If you don’t smell gas, go to next step.

8.  Rotate gas control knob counterclockwise 

 to 

“ON”.

9.   Replace lower front panel.
10. Turn on all electric power to the appliance. 
11. Set thermostat to desired setting.
12. If the appliance will not operate, follow the 

instructions “To Turn Off Gas To Appliance” and call 

your service technician or gas supplier.

TO TURN OFF GAS TO APPLIANCE 

1.   Set the thermostat to lowest setting.
2.   Turn off all electric power to the appliance if 

service is to be performed.

3.   Push in gas control knob slightly and turn 

clockwise 

   to “OFF” Do not force.

 WARNING

If you do not follow these instructions 

exactly, a fi re or explosion may result 

causing property damage, personal injury 

or loss of life.

• This appliance is equipped with an ignition device 

which automatically lights burner. 

Do NOT try to 

light this burner by hand.

• Before operating smell all around appliance area 

for gas. Be sure to smell next to 

fl

 oor because 

some gas is heavier than air and will settle to the 

fl

 oor.

• Use only your hand to turn the gas shutoff 

valve

. Never use tools. If valve will not turn 

by hand, do not try to repair it, call a quali

fi

 ed 

service technician. Force or attempted repair may 

result in 

fi

 re or explosion.

• Do not use this appliance if any part has 

been under water.

 Immediately call a quali

fi

 ed 

service technician to inspect appliance and to 

replace any part of control system and any gas 

control which has been under water.

!

  

LIGHTING PROCEDURE FOR BOILER WITH 

INTERMITTENT PILOT SYSTEM

For Your Safety, Read Before Operating!!

A.  This appliance is equipped with an ignition device 

which automatically lights the pilot. Do not try to light 

appliance by hand.

CAUTION

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switches; do not use 

any phone in your building.

• Immediately call your gas supplier from a 

neighbor’s phone. Follow the gas supplier’s 

instructions. 

• If you cannot reach your gas supplier, call the 

fi

 re 

department.

!

!

  

Figure 15 - Automatic Gas Valve

Summary of Contents for GWB8-245E-2

Page 1: ...rds Association for use with Natural and Propane Gases They are constructed and hydrostatically tested for maximum working pressure of 50 psi pounds per square inch in accordance with A S M E American...

Page 2: ...1 DIMENSIONS Table 1 Dimensions BOILER MODEL NUMBER DIMENSIONS INCH FLUE DIAMETER A WIDTH GWB8 245E 2 GWB8 262E 2 7 27 GWB8 280E 2 GWB8 299E 2 7 30 Add 5 to height for vent Damper Figure 1 Dimensions...

Page 3: ...requirements such as intermittent system operation extensive piping systems etc 3 Mbh 1 000 Btuh British Thermal Unit Per Hour Ratings marked Net AHRI Ratings indicate amount of remaining heat input...

Page 4: ...Read this manual and understand all requirements before beginning installation SAFETY SYMBOLS WARNINGS The following defined symbols are used throughout this manual to notify the reader of potential...

Page 5: ...2 Where required by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically fired Boilers ANSI ASME CSD 1 3 Boiler series is...

Page 6: ...cted indoor spaces All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors A Two Permanent Opening Method Provide opening commencing within 12 inches of top and se...

Page 7: ...of the relief valve outlet over the entire length of discharge line have no intervening shutoff valve between safety relief valve and discharge to atmosphere do not plug or place any obstruction in di...

Page 8: ...e 10 Significant condensation may form in boiler and or venting system if boiler is operated for long period of time with return temperatures of less than 120 F Condensate is corrosive and can cause s...

Page 9: ...9 Figure 5 Chilled Water Piping Figure 4 Typical Hot Water Piping 6 CONNECTING SUPPLY AND RETURN PIPING...

Page 10: ...10 Figure 6 BYPASS PIPING CIRCULATOR ON SUPPLY Figure 7 BYPASS PIPING CIRCULATOR ON RETURN Bypass Piping Required For High Mass Large Water Content Systems 6 CONNECTING SUPPLY AND RETURN PIPING...

Page 11: ...ugged by using plug supplied with vent damper 1 Position furnished vent damper on top of flue outlet collar Fasten damper securely to flue outlet collar with sheet metal screws Verify damper blade has...

Page 12: ...fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 7 CHIMNEY AND VENT PIPE CONNECTION 5 Tes...

Page 13: ...r indicator points to open position Turn thermostat or controller down again and check damper position indicator returns to closed position Vent Damper Manual Operation Vent damper may be placed in op...

Page 14: ...ld only be made by licensed propane installer Two stage regulation should be used by propane installer Propane gas piping should be checked out by propane installer CHECKING GAS PIPING DANGER Fire Haz...

Page 15: ...y drafts hot or cold pipes sunlight lighting fixtures televisions a fireplace or a chimney 4 Check thermostat operation by raising and lowering thermostat setting as required to start and stop the bur...

Page 16: ...ntegrated High Limit Electronic Ignition Control 240008781 I Inducer is not an option WARNING Modification substitution or elimination of factory equipped supplied or specified components may result i...

Page 17: ...17 11 WIRING DIAGRAMS Figure 13 Integrated High Limit Electronic Ignition Control 240008781...

Page 18: ...18 11 WIRING DIAGRAMS Figure 14 Integrated High Limit Electronic Ignition Control 240008781...

Page 19: ...repeat this process Repeat until you have covered every radiation units in the system ending up at highest unit in system If your units have automatic vents manual venting is unnecessary but it will...

Page 20: ...rol knob slightly and turn clockwise to OFF Do not force WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life...

Page 21: ...y turning thermostat to lowest setting for one minute then back to normal setting ADJUST PILOT BURNER Pilot flame should surround 3 8 to 1 2 of the pilot sensor See Figure 16 If flame needs adjusting...

Page 22: ...degrees C After setting limit control to limit setting check to see if it shuts off gas supply to burners Turn your thermostat up to call for heat and let boiler run until temperature of water reache...

Page 23: ...T PIPE Venting and piping should be checked at least once a season If vent piping shows any sign of leaking replace immediately WATER SYSTEM If system is to remain out of service during freezing weath...

Page 24: ...inals and wire joints Rollout switch blown Have your service agent check heat exchanged for blockage Replace rollout switch with exact replacement Blocked vent blown Have your service agent check vent...

Page 25: ...nstalled in supply line It will eliminate air from water before it reaches radiators and bleed off this air MAIN AIR VENT FOR DOWN FLOW SYSTEMS OR DIAPHRAGM TYPE EXPANSION TANK Before system is filled...

Page 26: ...ed vent safety switch must be reset manually after switch has cooled off by pushing reset button down Check venting system and chimney for blockage when restoring system to operating condition DO NOT...

Page 27: ...sit Check sensing bulb is fully inserted in well and is not loose Refer to enclosed addendum for wiring instructions when using indirect hot water heater A 3 Adjusting Settings To discourage unauthori...

Page 28: ...retry Flame signal was lost during state 7 or 8 and delay is called before retry 32 second delay 13 Soft lock out Soft lockout duration is one hour may override with manual reset 14 Hard lock out Man...

Page 29: ...and display On retry models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must...

Page 30: ...umber of retries exceeded Soft lockout Soft lockout is reset after one hour if alarm reason disappears 63 Soft lockout maximum number of recycles exceeded Soft lockout 64 Soft Lockout electronics fail...

Page 31: ...nnections are clean and tight Replace damaged wire Check for cracked ceramic insulator which can cause short to ground and replace igniter sensor if necessary At gas valve disconnect main valve wire f...