background image

20

CHECKING AND ADJUSTING

Adjust Steam Pressure Control

•  Steam pressure limit control (pressuretrol) shuts 

off gas to main burners when steam pressure in 

boiler reaches cut-off setpoint (i.e. sum of cut-in and 

differential setpoints). 

•  Burners refire when steam pressure drops to cut-in 

setpoint. 

•  System pressure requirements are based on size and 

condition of pipes, and load.

•  Cut-in setting of pressuretrol should never be less than 

twice system pressure drop for good system operation. 
A.  In typical single family residence with clean one-

pipe heating system and cast iron radiation, cut-in 

is usually set at minimum setting, i.e. 1/2 psi.

•  Steam radiation is sized based on square feet of 

equivalent direct radiation (EDR). This is based on 

steam pressure in the radiator of just less than 2 psi. 

•  Set differential adjustment at 1 psi, i.e. steam pressure 

required in radiators. Results in cut-off setpoint of 1½ 

psi. 

•  Larger systems or other types of systems such as two 

pipe systems, or systems with convectors or fan coil 

units, pressuretrol settings need to be determined on 

system-by-system basis.

•  Cut-in setpoint is determined by system pressure drop 

to furthest radiator or terminal unit. Double system 

pressure drop as safety factor, resulting in the rule 

cut-in setting should never be less than twice system 

pressure drop.

•  Differential setpoint is steam pressure required at 

terminal heating units.

Boiler will now operate in correct pressure range. It 

maintains enough steam pressure to send steam out to 

furthest radiator, and not go over optimum steam pressure 

required at the radiators.

Checking Controls

Low Water Cut-Off

A.  Turn off power to boiler or turn thermostat down to 

lowest setting. 

B.  Drain water to below visible bottom of water gauge 

glass. Turn power on and turn thermostat to call for 

heat. 

C.  Gas valve opens for approximately 10 seconds 

(time delay on probe type LWCO), gas valve will 

close and red indicator illuminates on LWCO. 

D.  When water is restored, it waits 30 seconds before 

reactivating burner circuit.

Boiler Equipped With Optional WF-2U-24

 

Water 

Feeder

 

E.  Continue thermostat call for heat after low water 

cut off recognizes low water condition. 

F.  One minute time delay, water feeder starts feeding 

water to boiler. 

G.  Feeder feeds for one minute, and then goes into 

another one minute waiting period. 

H.  Cycle of alternately waiting and feeding will repeat 

until :

• For Model 67D-1 float type low water cutoffs - as 

the water level raises the float above the burner 

cut off switch level, the burners should ignite. The 

water feeder remains powered until the water 

level raises the float to the water feeder switch 

level, satisfying the water feeder.

• For probe type low water cutoffs - the water level 

will rise until water in the boiler makes contact 

with the probe, satisfying the water feeder, and 

igniting the burners.

I.  In either case, one and two inches of water should 

be visible in glass gauge when both water feeder is 

satisfied, and burners are allowed to ignite.

• Time delays in feed cycles are designed to prevent 

boiler from flooding due to slow return lines.

• To check pressure limit, run boiler until pressure 

reaches system demand. Turn pressure screw and drop 

pressure setting until boiler shuts down. This shows the 

pressure limit is operating properly.

• Refer to control manufacturer’s instructions for more 

information.

Check Thermostat Operation 
Thermostat set above temperature indicated on 

thermometer, boiler should ignite. 
Verify thermostat turns boiler off when room temperature 

reaches selected setting and starts boiler operating when 

room temperature falls few degrees.
Set thermostat for desired temperature. Conditions in your 

home and location of thermostat will govern this setting.

Summary of Contents for GSB8-E

Page 1: ...Canadian Standards Association for use with Natural and Propane Gases They are constructed and hydrostatically tested for a maximum working pressure of 50 psi pounds per square inch in accordance wit...

Page 2: ...imensions Inches Intermittent Ignition w Vent Damper Flue Diameter A Width GSB8 075E 5 11 GSB8 112E 6 14 GSB8 150E 6 17 GSB8 187E 7 21 GSB8 225E 7 24 GSB8 262E 7 27 GSB8 299E 7 30 Add 5 to height for...

Page 3: ...I Rating Sq Ft 1 GSB8 075E 3 Natural Gas 75 62 82 7 47 196 Propane 70 58 82 7 44 183 1 GSB8 112E 4 Natural Gas 112 91 82 0 68 283 Propane 105 85 80 4 64 267 1 GSB8 150E 5 Natural Gas 150 122 82 0 92 3...

Page 4: ...whatsoever Introduction Boiler is designed for use in closed heating systems where all steam is returned as condensate and make up water is minimal Boiler is not designed for or intended for use in o...

Page 5: ...any other gas appliance with improper methods or materials could result in death or serious injury due to fire or to asphyxiation from poisonous gases such as carbon monoxide which is odorless and in...

Page 6: ...conditions of use Boiler location should not interfere with proper circulation of air Introduce outside air if normal infiltration does not provide necessary air Fresh Air for Combustion on page 11 6...

Page 7: ...or place any obstruction in discharge line Terminate freely to atmosphere where any discharge will be clearly visible and at no risk of freezing Allow complete drainage of valve and discharge line Ins...

Page 8: ...from the header one for each main 6 All boilers in gravity return systems must be equipped with a Hartford Loop as shown in Figure 5 7 When piping the vertical risers from the boiler to the header th...

Page 9: ...9 Figure 4 Recommended Near Boiler Piping Using One Supply Tapping SYSTEM PIPING...

Page 10: ...LATION SYSTEM PIPING Figure 6 Chilled Water Piping VALVES A B OPEN FOR HEATING CLOSE FOR COOLING VALVES C D CLOSE FOR HEATING OPEN FOR COOLING Figure 5 Recommended Near Boiler Piping Using Two Supply...

Page 11: ...ter than 0 60 Room volume is greater than 21 cubic feet divided by ACH air changes per hour x Total Input Mbh C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces...

Page 12: ...uld not be longer than 3 4 the chimney height HT Figure 7 page 13 Vent Pipe Fasten sections of vent pipe with 3 sheet metal screws at each joint to make piping rigid Support horizontal portions of ven...

Page 13: ...er gas burning appliance to their previous conditions of use 7 Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code ANSI...

Page 14: ...on and for vent damper troubleshooting guide refer to manual packaged with vent damper Horizontal Installation To Boiler Vent Damper To Chimney NO NO YES YES Flow Install vent damper with actuator to...

Page 15: ...or dampen excessive vibrations and prevent strain on gas connection Gas valve will not support piping weight Use thread joint compound pipe dope suitable for natural and liquefied petroleum gas Insta...

Page 16: ...ut off two wires are black One wire is located on secondary of 24 volt transformer second wire is located on pressure limit control F Boilers with PS 802 probe type low water cut off one wire is green...

Page 17: ...ol knob slightly and turn clockwise to OFF Do not force For Your Safety Read Before Operating WARNING If you do not follow these instructions exactly a fire or explosion may result causing property da...

Page 18: ...wn on left side of boiler Determine water level when boiler is off and cold when all water in the system is inside the boiler and return piping below water line and everything above water line is air...

Page 19: ...inner cones in softer blue outer mantel with no yellow Remain still when observing main burner flames Check main burner orifices burner throat and flame ports for dust and lint obstruction if flame ap...

Page 20: ...ower on and turn thermostat to call for heat C Gas valve opens for approximately 10 seconds time delay on probe type LWCO gas valve will close and red indicator illuminates on LWCO D When water is res...

Page 21: ...ild up Run connection from boiler drain valve to safe discharge point outside Shut off gas burners open drain valve allow all of water in boiler to drain out Close drain valve Allow boiler to cool slo...

Page 22: ...bead of 400 F RTV silicone to four mounting surface flanges of flue collector Mount flue collector on heat exchanger Tighten nuts and bolts 6 Seal front edge and four corners of flue collector to hea...

Page 23: ...e joints Rollout switch blown Have your service technician check heat exchanger for blockage Chimney flue is blocked Spill switch contacts open requiring manual reset of spill switch Have your service...

Page 24: ...s appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 13 Wiring Diagrams For Boilers With PS 802 Probe Type Low Water Cut Off Shown PS802 PS802 C...

Page 25: ...ny of the original wire as supplied with this appliance must be replaced it must be replaced with type 105 C Thermoplastic wire or its equivalent Figure 17 Wiring Diagrams For Boilers With 67D 1 Float...

Page 26: ...l Model WF 2U 24 water feeder maybe used with either of the low water cutoffs listed Water feeder maintains safe minimum water level Keeps boiler running by compensating for minor evaporative steam le...

Page 27: ...27 REPAIR PARTS...

Page 28: ...28 REPAIR PARTS...

Page 29: ...29 REPAIR PARTS...

Page 30: ...30 REPAIR PARTS Safety Relief Valve 14 11 NPT X 4 Nipple PF 033 02...

Page 31: ...31 Date Service Performed Company Name Tech Initials Company Address Phone...

Page 32: ...PRODUCT LITERATURE Lennox Industries Inc Dallas Texas...

Reviews: