
Page 19
FIGURE 18
MANUAL MAIN SHUT−OFF VALVE
WILL NOT HOLD TEST PRESSURE
IN EXCESS OF 0.5 PSIG (14"W.C.)
GAS VALVE
CAP
GAS PIPING TEST PROCEDURE
FIELD PROVIDED
LINE PRESSURE TAP
When checking piping connections for gas leaks, use pre-
ferred means. Kitchen detergents can cause harmful corro-
sion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended. It is available
through Lennox under part number 31B2001. See Corp.
8411−L10, for further details.
Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.
D−Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 18. Check gas
line pressure with unit firing at maximum rate. Low pres-
sure may result in erratic operation or underfire. High pres-
sure can result in permanent damage to gas valve or over-
fire. See table 15 for operating pressure at unit gas connec-
tion (line).
On multiple unit installations, each unit should be checked
separately, with and without units operating. Supply pres-
sure must fall within range listed in previous paragraph.
E−Check Manifold Pressure
After line pressure has been checked and adjusted, check
manifold pressure. Move pressure gauge to outlet pres-
sure tap located on unit gas valve (GV1). Checks of man-
ifold pressure are made as verification of proper regulator ad-
justment. Manifold pressure for the G40DF(X) can be mea-
sured at any time the gas valve is open and is supplying gas
to the unit. See table 15 for normal operating manifold pres-
sure.
TABLE 15
All G40DF Units
Natural
LP
Line Pressure WC"
4.5 − 10.5
11.0 − 13.0
Manifold Pressure WC"
3.5
10.0
IMPORTANT
For safety, connect a shut-off valve between the
manometer and the gas tap to permit shut off of
gas pressure to the manometer.
The gas valve is factory set and should not require adjust-
ment. All gas valves are factory regulated. See specifica-
tions section of this manual for High Altitude manifold pres-
sure settings.
Manifold Adjustment Procedure:
1 − Connect a test gauge to outlet pressure tap on gas
valve. See figures 13, 14 and 15. Start unit and allow 5
minutes for unit to reach steady state.
2 − While waiting for the unit to stabilize, notice the flame.
Natural gas should burn blue. L.P. gas should burn
mostly blue with some orange streaks.
3 − After allowing unit to stabilize for 5 minutes, record
manifold pressure.
NOTE−Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to re-
place pressure tap plug.
F− Proper Gas Flow (Approximate)
Furnace should operate at least 5 minutes before check-
ing gas flow. Determine time in seconds for
two
revolu-
tions of gas through the meter. (Two revolutions assures a
more accurate time.)
Divide by two
and compare to time
in table 16 below. Adjust manifold pressure on gas valve to
match time needed. Manifold pressure should not exceed
values listed in table 15. If manifold pressure matches
table 15 and rate is incorrect, check gas orifices for proper
size and restriction.
NOTE− To obtain accurate reading, shut off all other gas
appliances connected to meter.
IMPORTANT
For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.
TABLE 16
GAS METER CLOCKING CHART
Seconds for One Revolution
G40DF
Natural
LP
G40DF
Unit
1 cu ft
Dial
2 cu ft
Dial
1 cu ft
Dial
2 cu ft
DIAL
−45
82
164
205
410
−70
55
110
136
272
−90
41
82
102
204
−110
33
66
82
164
−135
27
54
68
136
G− Proper Combustion
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking com-
bustion. See sections E− and F−. Take combustion sample
beyond the flue outlet and compare to table 17. The maxi-
mum carbon monoxide reading should not exceed 100
ppm.