background image

Page 8

Vent Piping Guidelines

Pipe used for exhaust and intake lines should be sized acĆ
cording to table 4. Note that maximum length of vent pipe is
for one run; either intake or exhaust. Maximum vent length
given is 

not

 the total length of exhaust vents.

Each 90

°

 elbow is equivalent to 5 feet (1.52m) of vent pipe.

Two  45

°

  elbows  are  equivalent  to  one  90

°

  elbow.  One

45

°

elbow is equal to 2.5 feet (.76m) of vent pipe.

If intake and exhaust piping runs are not equal in length and
number of elbows, the larger diameter pipe must be used
for both runs.

TABLE 4

VENT PIPE SIZING TABLE FOR G26 FURNACES

MINIMUM DIAMETER OF INTAKE/EXHAUST PIPE

Vent Pipe 

Equivalent Length 

Max. Feet (Meters)

G26-50

50,000

BTU

G26-75

75,000

BTU

G26-100

100,000

BTU

G26-125

125,000

BTU

15  (4.57m)

1-1/2"

2"

2"

2"

20  (6.10m)

2"

2"

2"

3"

25  (7.62m)

2"

2"

2"

3"

30  (9.14m)

2"

2"

3"

3"

40  (12.19m)

2"

2"

3"

3"

50  (15.24m)

2"

2"

3"

3"

55  (16.76m)

2"

2"

3"

3"

60  (18.29m)

3"

3"

3"

3"

70  (21.34m)

3"

3"

3"

3"

80  (24.38m)

3"

3"

3"

3"

90  (27.43m)

3"

3"

3"

3"

100  (30.48m)

3"

3"

3"

3"

110  (33.53m)

3"

3"

3"

3"

120  (36.58m)

3"

3"

3"

3"

130  (39.62m)

3"

3"

3"

--

NOTE - M inch pipe for G26-50 is 5 feet and 2 elbows of 1.5 inch diameter
pipe.
NOTE - M inch pipe for G26-75 is 5 feet and 2 elbows of 2 inch diameter
pipe.
NOTE - M inch pipe for G26-100 is 5 feet and 2 elbows of 2 inch diameter
pipe.
NOTE - M inch pipe for G26-125 is 5 feet and 2 elbows of 2 inch diameter
pipe.

NOTE - When a WTKX termination kit is installed as part of

the intake and exhaust piping, the two 2 inch diameter 90°

elbows and the 27 inch pipe (in the kit) should be included

in the maximum vent pipe length for each run.

For -50 and -75 kBtuh units, connections are provided for 2
inch diameter venting which should satisfy most venting reĆ
quirements. No transition pieces are provided or needed
for 2 inch venting.
For -100 and -125 kBtuh units, the intake connection is
sized for 3 inch diameter pipe. The exhaust connection has
a 2 inch nipple.

 

A pipe transition piece is shipped with the

unit to connect to 3 inch pipe. See figure 7 for 2 inch and 3
inch venting applications.

Most  venting  applications  will  require  3  inch  venting  for

proper unit operation. 

For no reason should the intake

and exhaust pipe be different diameter pipes. 

RegardĆ

less of the diameter of pipe used, the standard roof and wall

terminations described in section 

Intake and Exhaust PipĆ

ing Terminations

 should be used. Exhaust piping must terĆ

minate with 1-1/2 inch pipe for 1-1/2 inch or 2 inch venting

and 2 inch pipe for 3 inch venting.

FIGURE 7

G26-100 OR -125 WITH 2 IN. VENTING

G26-100 OR -125 WITH 3 IN. VENTING

3 IN.

IN

2 IN

OUT

3 IN. FIELD

PROVIDED

NIPPLE

2 IN. VENT PIPE

3 IN.

IN

2 IN.

OUT

3 IN. VENT PIPE

3 IN. X 2 IN.

REDUCER

2 IN. FIELD

PROVIDED

NIPPLE

3 IN. X 2 IN.

REDUCER

Joint Cementing Procedure

All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.

WARNING

DANGER OF EXPLOSION! Fumes from pvc glue may

ignite during system check. Remove spark plug wire

from ignition control before 115v power is applied.

Reconnect wire after two minutes.

 1 - Measure and cut vent pipe to desired length.
 2 - Debur and chamfer end of pipe, removing any ridges

or rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.

 3 - Clean and dry surfaces to be joined.
 4 - Test fit joint and mark depth of fitting on outside of pipe.
 5 - Uniformly apply liberal coat of PVC primer for PVC or

ABS cleaner for ABS to inside socket surface of fitting
and male end of pipe to depth of fitting socket.

 6 - Promptly apply solvent cement to end of pipe and in-

side socket surface of fitting. Cement should be ap-
plied lightly but uniformly to inside of socket. Take care
to keep excess cement out of socket. Apply second
coat to end of pipe.

Downloaded from 

ManualsNet.com

 search engine

Summary of Contents for G26 Series

Page 1: ...ting 26 Start Up Performance Check List 31 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WHAT TO DO IF YOU SMELL GAS Do not store or use gasoline or other flammable vapors and liquids in the vi cinit...

Page 2: ...INTAKE 21 3 4 552 7 3 8 187 23 3 4 603 25 635 5 8 16 H G 5 8 16 EXTERNAL SIDE RETURN AIR FILTER KIT Either Side Optional 23 584 D Return Air Knockout Bottom 4 102 Model No A B C D E F G H Model No in...

Page 3: ...ME SIGHT GLASS DuralokPlusTM HEAT EXCHANGER ASSEMBLY CONDENSER COIL CONTROL TRANSFORMER CONTROL BOX COVER DOOR INTERLOCK SWITCH CONTROL VOLTAGE CIRCUIT BREAKER WARM HEADER COLLECTOR BOX COLD HEADER CO...

Page 4: ...e hangar or other building that has a hazardous atmosphere the furnace must be installed according to recommended good practice requirements and current National Fuel Gas Code or CAN CGA B149 1 and B1...

Page 5: ...be installed in areas normally subject to freezing temperatures Return Air Opening Guidelines WARNING Blower door must be securely in place when blower and burners are operating Gas fumes which could...

Page 6: ...AIR OPENING SIDE FILTER CLIPS 2 FURNACE FRONT FURNACE BACK Side Return Air Applications An external filter rack ordered separately is available from Lennox NOTE The filter door may be shipped in the...

Page 7: ...American National Standard Institute and the American Society for Testing and Materials ANSI ASTM standards The solvent shall be free flowing and contain no lumps undissolved particles or any foreign...

Page 8: ...s the intake connection is sized for 3 inch diameter pipe The exhaust connection has a 2 inch nipple A pipe transition piece is shipped with the unit to connect to 3 inch pipe See figure 7 for 2 inch...

Page 9: ...abric softeners for clothes dryers Masonry acid washing materials Intake Piping 1 Cement intake piping in slip connector located at top of unit 2 Route piping to outside of structure Continue with ins...

Page 10: ...intake piping upwind prevailing wind from exhaust piping To avoid re circulation of exhaust gas on roof terminations end of exhaust pipe must be higher than intake pipe Exhaust and intake exits must b...

Page 11: ...all to position above snow accumulation or other ob structions Piping must be supported every 3 feet 91m as shown in figure 15 Refer to figures 13 and 14 for proper piping method WTK wall termination...

Page 12: ...authorities having local jurisdiction At vent termination care must be taken to maintain protective coatings over building materials pro longed exposure to exhaust condensate can destroy protective co...

Page 13: ...AKE VENT Side View OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT INSTALLATION WALL TERMINATION KIT WTK Inches mm FIGURE 18 12 MIN 305 Above Grade COVER EXHAUST VENT WITH 1 2 13 FOAM INSULATION Front Vie...

Page 14: ...UCER BRACKET CONDENSATE TRAP 3 Use the provided adapter 1 2 inch PVC x 1 2 inch MPT and the nipple 1 2 inch PVC to carry drainage outside the cabinet If a field substitute is needed 1 2 inch CPVC x 1...

Page 15: ...combustion air inducer See figure 23 4 The piping should be sloped 1 4 inch 6 4 mm per 15 feet 4 57 m upward toward the meter from the fur nace The piping must be supported at proper inter vals every...

Page 16: ...c feet of gas per hour kilo liters of gas per hour and based on 0 60 specific gravity gas The furnace must be isolated from the gas supply system by closing its individual manual shut off valve during...

Page 17: ...et of the jack See fig ure 27 Any accessory rated up to 4 amps can be con nected to this wire Connect the neutral leg of the acces sory to the neutral white wire in the make up box The ac cessory term...

Page 18: ...IGHT CONTROL DOOR INTERLOCK SWITCH TRANSFORMER DETACHABLE TERMINAL STRIP SURELIGHT INTEGRATED CONTROL BOARD FIGURE 30 TERMINAL DESIGNATIONS ACB COOL ACB HEAT PARK ACB LOW ACC TX HOT HTG ACC NEUTRALS 2...

Page 19: ...Page 19 FIGURE 31 TYPICAL G26 WIRING DIAGRAM OUTDOOR UNIT OUTDOOR UNIT B6 COMBUSTION AIR INDUCER MOTOR Downloaded from ManualsNet com search engine...

Page 20: ...around the appliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor Gas valve may be equipped with either a gas control knob or leve...

Page 21: ...s To Unit and call your service techni cian or gas supplier To Turn Off Gas To Unit 1 Set thermostat to lowest setting 2 Turn off all electrical power to unit if service is to be per formed 3 Remove h...

Page 22: ...te only during nor mal unit operation 6 When test is complete remove obstruction from hose and return hose to gas valve barbed fitting Gas Flow To check for proper gas flow to the combustion chamber d...

Page 23: ...applicable is operating Blower Check the blower wheels for debris and clean if necessary The blower motors are prelubricated for ex tended bearing life No further lubrication is needed Filters 1 Filte...

Page 24: ...he plas tic orifice in the inducer inlet to make sure it has not fallen out See figure 1 Reconnect the 2 pin plug to the wire harness Re install the flue transition in the cabinet and re attach the dr...

Page 25: ...akes a good seal The burners sit on top of the burner box flanges Make certain that the screws from the underneath the box pass through the larger holes in the flange and engage in the smaller holes i...

Page 26: ...SLOW FLASH SLOW FLASH SLOW FLASH FAST FLASH Primary or secondary limit switch open Rollout switch open OR 9 pin connector improperly attached Flame sensed without gas valve energized Pressure switch o...

Page 27: ...D 2 OFF GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY LED 1 OFF LED 2 SLOW FLASH Sequence holds until pressure switch closes or thermostat resets control NO NO YES NO IS THERE...

Page 28: ...ERGIZED YES FLAME STABILIZATION PERIOD GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND IGNITION WATCH...

Page 29: ...MPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 0 SECOND DELAY ACB COOL SPEED TERMINAL IS ENERGIZED ACC TERMINAL IS ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND ACC TERM OFF WITH 0 SECOND...

Page 30: ...G THERMOSTAT OPENS COMBUSTION AIR INDUCER AND HTG ACC TERMINAL ARE DE ENERGIZED INDOOR BLOWER SWITCHES TO ACB COOL SPEED THERMOSTAT OPENS INDOOR BLOWER SWITCHES TO ACB LOW SPEED ACC TERM REMAINS ENERG...

Page 31: ...Pressure Job No City City Serial No Date State Technician Flue Connections Tight HEATING SECTION THERMOSTAT Heat Anticipator Properly Set Level Fuel Type Natural Gas LP Propane Gas Blower Motor H P G...

Reviews: