Energence
®
Packaged Electric / Electric 26 to 44 kW 50 Hz / Page 27
ELECTRICAL DATA
LCH092H4
LCH102H4
LCH120H4
LCH150H4
1
Voltage - 50hz 3 Phase with neutral
380/420V
380/420V
380/420V
380/420V
Compressor 1
Rated Load Amps
6.1
6.1
7.8
8
Locked Rotor Amps
41
43
51.5
67.1
Compressor 2
Rated Load Amps
6.1
6.1
7.8
10.6
Locked Rotor Amps
41
43
51.5
74
Outdoor Fan
Motors (2)
Full Load Amps
1.3
1.3
1.3
1.5
(total)
(2.6)
(2.6)
(2.6)
(3)
Power Exhaust
(1) 0.19 kW (0.25 HP)
Full Load
Amps
1.3
1.3
1.3
1.3
Indoor Blower
Motor
kW
1.5
2.2
3.7
1.5
2.2
3.7
1.5
2.2
3.7
1.5
2.2
3.7
Full Load Amps
3.4
4.8
7.6
3.5
5
7.8
3.5
5
7.8
3.5
5
7.8
2
Maximum
Overcurrent
Protection
Unit Only
25
25
30
20
25
30
30
30
35
35
40
40
With 0.25 kW (0.33 HP)
Power Exhaust
25
25
30
25
25
30
30
30
35
35
40
40
3
Minimum
Circuit
Ampacity
Unit Only
20
22
26
20
22
26
24
26
28
28
30
33
With 0.25 kW (0.33 HP)
Power Exhaust
22
23
27
22
23
27
25
27
30
30
31
34
ELECTRIC HEAT DATA
Electric Heat Voltage
420
420
420
420
420
420
420
420
420
420
420
420
2
Maximum
Overcurrent
Protection
Unit+
4
Electric Heat
5.7 kW
25
25
30
25
25
30
- - -
- - -
- - -
- - -
- - -
- - -
11.5 kW
25
30
30
25
30
30
30
30
35
35
40
40
17.2 kW
35
40
40
35
40
40
35
40
40
35
40
40
23 kW
45
50
50
45
50
50
45
50
50
45
50
50
34.5 kW
70
70
70
70
70
70
70
70
70
70
70
70
45.9 kW
- - -
- - -
- - -
- - -
- - -
- - -
70
70
80
70
70
80
3
Minimum
Circuit
Ampacity
Unit+
4
Electric Heat
5.7 kW
20
22
26
20
22
26
- - -
- - -
- - -
- - -
- - -
- - -
11.5 kW
25
27
30
25
27
30
25
26
30
28
30
33
17.2 kW
35
37
40
35
37
40
34
36
40
35
37
40
23 kW
44
47
50
44
47
50
44
46
50
44
47
50
34.5 kW
64
66
70
64
66
70
64
66
69
64
66
70
45.9 kW
- - -
- - -
- - -
- - -
- - -
- - -
68
70
73
68
70
74
2
Maximum
Overcurrent
Protection
Unit+
4
Electric Heat
and 0.25 kW
(0.33 HP)
Power Exhaust
5.7 kW
25
25
30
25
25
30
- - -
- - -
- - -
- - -
- - -
- - -
11.5 kW
30
30
35
30
30
35
30
30
35
35
40
40
17.2 kW
40
40
45
40
40
45
40
40
45
40
40
45
23 kW
50
50
60
50
50
60
50
50
60
50
50
60
34.5 kW
70
70
80
70
70
80
70
70
80
70
70
80
45.9 kW
- - -
- - -
- - -
- - -
- - -
- - -
70
80
80
70
80
80
3
Minimum
Circuit
Ampacity
Unit+
4
Electric Heat
and 0.25 kW
(0.33 HP)
Power Exhaust
5.7 kW
22
23
27
22
23
27
- - -
- - -
- - -
- - -
- - -
- - -
11.5 kW
26
28
32
26
28
32
26
28
32
30
31
34
17.2 kW
36
38
42
36
38
42
36
38
41
36
38
42
23 kW
46
48
52
46
48
52
46
48
51
46
48
52
34.5 kW
66
68
72
66
68
72
66
68
71
66
68
72
45.9 kW
- - -
- - -
- - -
- - -
- - -
- - -
70
72
75
70
72
76
1
Extremes of operating range are plus and minus 10% of line voltage.
2
Heating Air Conditioning and Refrigeration (HACR) type breaker or fuse.
3
Refer to local codes to determine wire, fuse and disconnect size requirements.
4
Nominal kW based on 420V-3ph-50hz.
ELECTRIC HEAT CAPACITIES
Volts
Input
5.7 kW
11.5 kW
17.2 kW
23 kW
34.5 kW
45.9 kW
kW
Input
Btuh
Output
No. of
Stages
kW
Input
Btuh
Output
No. of
Stages
kW
Input
Btuh
Output
No. of
Stages
kW
Input
Btuh
Output
No. of
Stages
kW
Input
Btuh
Output
No. of
Stages
kW
Input
Btuh
Output
No. of
Stages
380
4.7 16 000
1
9.4 32 100
1
14.1 48 200
1
18.8 64 200
2
28.2 96 300
2
37.6 128 400
2
400 5.2 17 800
1
10.4 35 500
1
15.6 53 300
1
20.9 71 400
2
31.2 106 600
2
41.6 142 100
2
420 5.7 19 500
1
11.5 39 300
1
17.2 58 700
1
23
78 500
2
34.5 117 500
2
45.9 156 800
2
Summary of Contents for Energence LCH
Page 39: ......