Page 2
SPECIFICATIONS
Gas
Heating
Performance
Model No. EL296DF045XV36BEL296DF070XV48BEL296DF090XV60CEL296DF110XV60C
1
AFUE
96%
96%
96%
96%
High
Fire
Input - Btuh
44,000
66,000
88,000
110,000
Output - Btuh
43,000
64,000
85,000
106,000
Temperature rise range - °F
35-65
35-65
40-70
45-75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
3.5 / 10.0
Low
Fire
Input - Btuh
29,000
43,000
57,000
72,000
Output - Btuh
28,000
42,000
56,000
70,000
Temperature rise range - °F
20 - 50
25 - 55
30 - 60
35 - 65
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
1.7 / 4.5
1.7 / 4.5
1.7 / 4.5
1.7 / 4.5
High static -
in. w.g.
Heating
0.8
0.8
0.8
0.8
Cooling
1.0
1.0
1.0
1.0
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
3/4
3/4
with furnished 90° street elbow 3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d. 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT 3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nom. diameter x width - in.
10 x 9
11 x 10
11 x 11
11 x 11
Motor output - hp
1/2
3/4
1
1
Tons of add-on cooling
2 - 3
2.5 - 4
3 - 5
3 - 5
Air Volume Range - cfm
545 - 1360
575 - 1800
890 - 2130
860 - 2180
Electrical
Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
7.7
10.1
12.8
12.8
Maximum overcurrent protection
15
20
20
20
Shipping Data
lbs. - 1 package
131
136
164
176
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized
furnaces.