background image

Page 24

V-TYPICAL OPERATING CHARACTERISTICS

A-Blower Operation and Adjustment 

1 - Blower operation is dependent on thermostat control

system.

2 - Generally, blower operation is set at thermostat sub­

base fan switch. With fan switch in ON position, blower
operates continuously. With fan switch in AUTO position,
blower cycles with demand or runs continuously while
heating or cooling circuit cycles.

3 - Depending on the type of indoor thermostat, blower

and entire unit will be off when the system switch is in
OFF position.

B-Temperature Rise (Figure 19)

Temperature rise for EL280DFE units depends on unit in­
put, blower speed, blower horsepower and static pressure
as marked on the unit rating plate. The blower speed must
be set for  unit operation within the range of  “TEMP. RISE

°

F” listed on the unit rating plate.

FIGURE 19

Return

Supply

Temperatures

TEMPERATURE RISE

Supply Duct Temperature

Return Duct Temperature 

_

Temperature Rise  =

C-External Static Pressure

1 - Tap locations shown in figure 20.

2 - Punch a 1/4” diameter hole in supply and return air ple­

nums. Insert manometer hose flush with inside edge of
hole or insulation. Seal around the hose with perma­
gum. Connect the zero end of the manometer to the
discharge (supply) side of the system. On ducted sys­
tems, connect the other end of manometer to the return
duct as above.

3 - With only the blower motor running and the evaporator

coil dry, observe the manometer reading. Adjust blow­
er motor speed to deliver the air desired according to
the job requirements. For heating speed external static
pressure drop must not be more than 0.5” W.C. For
cooling speed external static pressure drop must not
be more than 0.8” W.C.

4 - Seal the hole when the check is complete.

FIGURE 20

EXTERNAL STATIC PRESSURE

Supply Duct Static

Return Duct 

Total Duct Static  = 
(dry coil)

Return

Supply

Summary of Contents for EL280DFE Series

Page 1: ...xcept where noted are recommendations only and do not consti tute code TABLE OF CONTENTS Specifications Page 2 Blower Performance Data Page 3 Parts Identification Page 4 I Unit Components Page 5 II In...

Page 2: ...g 2 3 5 3 4 Air Volume Range cfm 400 1475 780 1700 Electrical Data Voltage 120 volts 60 hertz 1 phase Blower motor full load amps 6 1 8 2 Maximum overcurrent protection 15 15 Shipping Data lbs 1 packa...

Page 3: ...02 0 70 1405 482 1235 365 1075 295 990 259 840 209 0 80 1160 369 1025 308 925 268 780 217 EL280DF070E36A PERFORMANCE Less Filter External Static Pressure in w g Air Volume Watts at Various Blower Spee...

Page 4: ...ION Control Box includes integrated control transformer and door switch Secondary Limit Internal Flue Pipe Assembly Gas Valve Burner Box Assembly Combustion Air Inducer Indoor Blower Heat Exchanger Pr...

Page 5: ...nits are equipped with the SureLight two stage inte grated control The system consists of a ignition blower control figures 4 and 5 with control pin designations in tables 1 and 2 and ignitor The cont...

Page 6: ...he DIP switch to ON for use with a single stage thermostat While in the single stage thermostat mode the burners will always fire on first stage heat The combustion air inducer will operate on low spe...

Page 7: ...T STAGE COOL SIGNAL Y2 THERMOSTAT 2ND STAGE COOL SIGNAL O THERMOSTAT SIGNAL TO HEAT PUMP REVERSING VALVE L NOT USED DH NOT USED HUM UNPOWERED NORMALLY OPEN DRY CONTACTS LI 120 VAC INPUT TO CONTROL ACC...

Page 8: ...ELECTION 1 2 3 4 5 6 ON SureLight W1W2 G Y2 Y1 C C DH L O DS R W1 W2 G Y2 Y1 C C R L DH 7 PROTECTIVE PLASTIC FILM ON DIP SWITCHES MAY BE REMOVED FOR EASE IN SETTING OF DIP SW CUT ON BOARD LINK SOLDER...

Page 9: ...rob bing equipment connected to system May require installation of larger VA transformer to be installed in furnace air handler Clears after fault recovered E 117 Poor ground detected Warning only Pr...

Page 10: ...operation after fault is cleared E 225 High pressure switch failed open Check pressure inches w c of high pressure switch closing on heat call Measure operating pres sure inches w c Inspect vent and...

Page 11: ...ating pressure inches w c Inspect vent and combustion air inducer for correct opera tion and restriction Clears when heat call finishes successfully E 273 Soft lockout Exceeded maximum number of recyc...

Page 12: ...nit is shipped from the factory with a blower off delay of 90 se conds The blower off delay affects comfort and is adjust able to satisfy individual applications Adjust the blower off delay to achieve...

Page 13: ...o provide constant torque at each of the five selectable speed taps Each tap requires 24 volts to en ergize Input Voltage Requirements The circuit is designed to be operated with AC voltage To enable...

Page 14: ...fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to VAC Check for 24 volts acros...

Page 15: ...read approxim ately the same resistance within an ohm 3 Check to see if the blower wheel spins freely FIGURE 11 Motor Test TABLE 8 Scale Measurement range in words ohms 2 M two megohm two million ohms...

Page 16: ...s are located on the valve A regu lator adjustment screw is located on the valve LPG change over kits are available from Lennox Kits include burner orifices 4 Flame Rollout Switches S47 The EL280DFE i...

Page 17: ...Page 17 EL280DFE HEATING COMPONENTS FIGURE 13 Ignitor Burners Sensor Gas Valve Manifold and Gas Orifices Rollout Switch...

Page 18: ...AC volts Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resistance of ignitor at the plug Reading should be between 39 and 70 ohms If the reading...

Page 19: ...thermostat contacts to cycle system 7 When main burners are in operation for two minutes take reading TABLE 9 Flame Signal in Microamps Normal Low Drop Out 2 6 or greater 2 5 or less 06 FIGURE 15 Meas...

Page 20: ...d stage the switch senses that the combustion air inducer is operating It closes a cir cuit to the furnace control when pressure inside the com bustion air inducer decreases to a certain set point Set...

Page 21: ...ails to operate check the following 1 Is the thermostat calling for heat 2 Are access panels securely in place 3 Is the main disconnect switch closed 4 Is there a blown fuse or tripped circuit breaker...

Page 22: ...n on various metals used in gas piping Use of a specialty Gas Leak Detector is strongly recommended It is available through Lennox under part number 31B2001 See Corp 8411 L10 for further details Do no...

Page 23: ...nd pressure switch may require adjustment or replacement to ensure proper operation at higher altitudes See table 14 for manifold pressures and table 15 for pressure switch kits and gas conversion kit...

Page 24: ...E 19 Return Supply Temperatures TEMPERATURE RISE Supply Duct Temperature Return Duct Temperature _ Temperature Rise C External Static Pressure 1 Tap locations shown in figure 20 2 Punch a 1 4 diameter...

Page 25: ...and unobstructed to provide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or blockage Vent system must be free and cl...

Page 26: ...e careful with the collector box gas ket If the gasket is damaged it must be replaced to prevent leakage 6 Disconnect gas supply piping Remove the screw se curing the burner box cover and remove cover...

Page 27: ...bustion air inducer Failure to replace all screws may cause leaks Inspect gaskets for any damage and replace if necessary 15 Reinstall burner box manifold assembly and burner box cover 16 Reconnect al...

Page 28: ...Page 28 VII Wiring and Sequence of Operation EL280DFE Schematic Wiring Diagram...

Page 29: ...zed on low fire first stage and ignition oc curs At the same time the control module sends a sig nal to begin an indoor blower 30 second ON delay When the delay ends the indoor blower motor is ener gi...

Page 30: ...er gized on the low fire heating speed and the HUM con tacts are energized The integrated control also initi ates a second stage on delay factory set at 7 min utes adjustable to 12 minutes 5 If the he...

Page 31: ...T ANY ON BOARD LINKS S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT Not required on all units 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOA...

Page 32: ...E TERM STRIP OUTDOOR UNIT Not required on all units 2 Heat 2 Cool with t stat with humidity control OFF CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM S1 T STAT FURNACE TERM STRIP O...

Page 33: ...ON BOARD LINK W951 HEAT PUMP DEHUM L7724U T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U thermostat w dual fuel capa bilities Capabl...

Page 34: ...AT PUMP CUT ON BOARD LINK W914 DEHUM L7742U T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7742U thermostat w dual fuel capa bilities Capa...

Page 35: ...OR T STAT IS CYCLED OFF ON FOR 3 SEC MINIMUM NO YES FIRST LOW STAGE PRESSURE SWITCH CONTACTS OPEN NO GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF CONTROL REMAINS UNTIL PRESSURE SWITCH I...

Page 36: ...NDS AFTER GAS VALVE OPENS u0 19 microamps GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF STATUS LED HEARTBEAT HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HE...

Page 37: ...ST STAGE HEAT DEMAND SATISFIED GAS VALVE OFF COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE INDOOR BLOWER OFF WITH DELAY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SECOND STAGE HEAT DEMAND REQUIRE...

Page 38: ...ODE DIP SWITCH SET AT SINGLE YES YES FIRST AND SECOND STAGE HEAT DEMAND SATISFIED SIMULTANEOUSLY STATUS LED HEARTBEAT YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF AFTER 5 SECOND LOW SPEED POST PURGE P...

Page 39: ...ZED NO IS THERE PROPER GROUND YES NO INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY FIRST STAGE DEMAND FOR COOL SATISFIED NO THERMOSTAT CALLS FOR SECOND STAGE COOL COMPRESSOR A...

Page 40: ...TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAGE HEAT DE...

Reviews: