Page 28
TYPICAL
EXHAUST AND INTAKE
PIPE CONNECTIONS IN UPFLOW
DIRECT OR NON-DIRECT VENT APPLICATIONS
2”
2”
2”
3”
2”
2”
or
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
TRANSITION
2”
1−1/2”
030/045/070 Only
2”
INTAKE
3”
INTAKE
EXHAUST
Exhaust
Exhaust
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
Exhaust
6” Min
FIGURE 26
SIDE VIEW
2”
2”
2”
or
TYPICAL
EXHAUST AND INTAKE
PIPE CONNECTIONS IN HORIZONTAL DIRECT OR
NON-DIRECT VENT APPLICATIONS
(RIGHT HAND DISCHARGE SHOWN)
3”
2”
45°
MAX
45°
MAX
DO NOT transition
from smaller to larger
pipe in horizontal runs
of exhaust pipe.
EXHAUST
12” max.
*2”
*2”
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE − Exhaust pipe and intake pipe must be the same diameter.
TRANSITION
1−1/2”
2”
3”
*2”
*2”
*2”
*2”
INTAKE
2”
2”
or
2”
2”
EXHAUST
INTAKE
030/045/070 Only
Exhaust
DO NOT transition
from larger to smaller
pipe in horizontal runs
of exhaust pipe.
Exhaust
Exhaust
2”
FIGURE 27