FIGURE 19

MANUAL MAIN SHUT-OFF VALVE

WILL NOT HOLD TEST PRESSURE

IN EXCESS OF 0.5 PSIG (14”W.C.)

GAS VALVE

CAP

GAS PIPING TEST PROCEDURE

FIELD PROVIDED

LINE PRESSURE TAP

When checking piping connections for gas leaks, use pre­
ferred means. Kitchen detergents can cause harmful corro­
sion on various metals used in gas piping. Use of a specialty
Gas Leak Detector is strongly recommended. It is available
through Lennox under part number 31B2001. See Corp.
8411-L10, for further details.

Do not use matches, candles, flame or any other source of
ignition to check for gas leaks.

D- Gas Pressure Adjustment
Gas Flow (Approximate)

TABLE 10

GAS METER CLOCKING CHART

EL180DFE

Unit

Seconds for One Revolution

Natural

LP

1 cu ft

Dial

2 cu ft

Dial

1 cu ft

Dial

2 cu ft

DIAL

-045

80

160

200

400

-070

55

110

136

272

-090

41

82

102

204

-110

33

66

82

164

-135

27

54

68

136

             

Natural-1000 btu/cu ft              LP-2500 btu/cu ft

Furnace should operate at least 5 minutes before check­
ing gas flow. Determine time in seconds for 

two

 revolu­

tions of gas through the meter. (Two revolutions assures a
more accurate time.)  

Divide by two

 and compare to time

in table 10. If manifold pressure matches table 12 and rate
is incorrect, check gas orifices for proper size and restric­
tion. Remove temporary gas meter if installed.

NOTE 

- To obtain accurate reading, shut off all other gas

appliances connected to meter.

E- Supply and Manifold Pressure
Supply Pressure Measurement

 1 - Remove the threaded plug from the inlet side of the

gas valve and install a field-provided barbed fitting.
Connect to a test gauge to measure supply pressure.

 2 - Start unit and allow 5 minutes for unit to reach steady

state.

 3 - After allowing unit to stabilize for 5 minutes, record

supply pressure and compare to value given in table
12.

Manifold Pressure Measurement

 1 - Remove the threaded plug from the outlet side of the

gas valve and install a field-provided barbed fitting.
Connect to a test gauge to measure manifold pres­
sure.

 2 - Start unit and allow 5 minutes for unit to reach steady

state.

 3 - While waiting for the unit to stabilize, observe the

flame. Flame should be stable and should not lift from
burner. Natural gas should burn blue.

 4 - After allowing unit to stabilize for 5 minutes, record

manifold pressure and compare to value given in table
12.

 5 - Shut unit off and remove manometer as soon as an ac­

curate reading has been obtained. Take care to re­
place pressure tap plug

.

 6 - Start unit and perform leak check. Seal leaks if found.

F- Proper Combustion

Furnace should operate a minimum 15 minutes with cor­
rect manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue out­
let and compare to the tables below. The maximum carbon
monoxide reading should not exceed 100 ppm.

TABLE 11

EL180DFE Unit

CO

2

%

 For Nat

CO

2

For LP

045

6.8 - 7.4

7.5 - 9.0

070
090

110

The maximum carbon monoxide reading is 100 ppm.

G- High Altitude

The manifold pressure may require adjustment and com­
bustion air pressure switch may need replacing to ensure
proper combustion at higher altitudes. Refer to table 12 for
manifold pressure and table 13 for pressure switch change
and gas conversion kits.

IMPORTANT

For safety, shut unit off and remove manometer as
soon as an accurate reading has been obtained.
Take care to replace pressure tap plug.

Summary of Contents for EL180DF045E36A

Page 1: ...ute code WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and service must be performed by a licensed professional HVAC in staller or equivalent service agency or the gas sup plier TABLE OF CONTENTS Specifications Page 2 Blower Data Page 3 Parts Identification Page 5 I Unit Components Page 6 II Instal...

Page 2: ...mounting are not furnished and must be field provided 1 Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces OPTIONAL ACCESSORIES MUST BE ORDERED EXTRA A Width Models B Width Models C Width Models CABINET ACCESSORIES Downflow Combustible Flooring Base 11M59 11M60 11M61 FILTERS 1 Down...

Page 3: ...5 170 1225 135 1185 125 1110 105 0 10 1430 290 1275 175 1190 145 1155 135 1005 95 0 20 1400 295 1230 190 1125 160 1110 150 900 100 0 30 1360 310 1205 205 1085 160 1055 155 845 115 0 40 1310 325 1155 210 1050 175 1000 165 790 115 0 50 1280 335 1110 220 985 185 950 180 705 130 0 60 1250 350 1060 235 935 195 865 185 645 135 0 70 1220 355 1000 245 865 205 815 195 590 140 0 80 1165 365 935 250 795 210 ...

Page 4: ... 2095 405 1875 295 1700 225 1635 180 0 10 2385 630 2100 415 1830 310 1610 240 1505 190 0 20 2325 650 2010 440 1760 330 1570 255 1375 195 0 30 2280 675 1940 460 1705 340 1500 260 1320 210 0 40 2235 690 1895 475 1635 365 1440 285 1265 225 0 50 2165 710 1845 490 1595 380 1380 300 1200 235 0 60 2125 735 1800 510 1545 390 1320 310 1170 250 0 70 2090 740 1755 530 1510 405 1285 325 1100 260 0 80 2035 760...

Page 5: ...ustion air inducer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Heat Exchanger Flue Chase Blower Assembly Secondary Limit Access Panel Control Box includes integrated control transformer inter lock switch and circuit breaker ...

Page 6: ...rface ignition control system consisting of an in tegrated control figure 3 with control terminal designa tions in tables 1 2 and 3 flame sensor and ignitor figure 6 The integrated control and ignitor work in combination to ensure furnace ignition and ignitor durability The inte grated control controls all major furnace operations The integrated control also features a RED LED for trouble shooting...

Page 7: ...re Switch In 11 Rollout Switch In 12 Gas Valve Out TABLE 3 1 4 QUICK CONNECT TERMINALS 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality accessory 120VAC NEUTRALS Common 120VAC HUM24 Humidifier 24VAC 3 16 QUICK CONNECT TERMINALS COOL Cooling tap 24VAC HEAT Heating tap 24VAC FAN Continuous blower 24 VAC PARK no power Park terminal for spee...

Page 8: ... etc To clear error codes depress and hold button longer than 5 seconds TABLE 5 03 Integrated Control RED LED Flash Code2 Diagnostic Codes Status of Furnace Off No power to control or board fault detected Heartbeat1 Normal Operation Idle Continuous Fan Cool Continuous Rapid Flash Call For Heat Burner Operation 1 Reverse Line Voltage Polarity 2 Improper Earth Ground 3 Burner failed to light or lost...

Page 9: ...ith a fac tory fan off setting of 90 seconds For customized comfort monitor the supply air temperature once the heat demand is satisfied Note the supply air temperature at the instant the blower is de energized Adjust the fan off delay to achieve a supply air temperature between 90 110 at the instant the blower is de ener gized Longer delay times allow for lower air temperature shorter delay times...

Page 10: ...xchanger the limit will open If the limit is open the integrated control energizes the supply air blower and closes the gas valve The limit auto matically resets when unit temperature returns to normal The switch must reset within three minutes or SureLight control will go into Watchguard for one hour The switch is factory set and cannot be adjusted The switch may have a different setpoint for eac...

Page 11: ...hermostat contacts to cycle system 7 When main burners are in operation for two minutes take reading TABLE 6 Flame Signal in Microamps Normal Low Drop Out 1 5 0 5 1 4 0 4 FIGURE 7 Measuring Flame Signal upflow furnace shown Flame Sensor Flame Sensor Wire Integrated Control Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor...

Page 12: ...the only test needed If the reading on the meter is not correct 0 or infinity then a second test is needed Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resistance of ignitor at the plug Reading should be between 39 and 70 ohms If the reading is correct then the problem is with the wiring between the jack plug and the control If reading is not...

Page 13: ...ressure Switch S18 EL180DFE series units are equipped with a combustion air pressure switch located on the combustion air inducer ori fice bracket The switch is connected to the combustion air inducer housing by means of a flexible silicone hose It mon itors negative air pressure in the combustion air inducer housing The switch is a single pole single throw proving switch elec trically connected t...

Page 14: ...and motor is not operating properly replace motor The motor is not field re pairable If replacing the indoor blower motor or blower wheel is nec essary placement is critical The blower wheel must be cen tered in the blower housing as shown in figure 10 When re placing the indoor blower motor the set screw must be aligned and tightened with the motor shaft as shown in figure 11 13 Secondary Limit C...

Page 15: ...us fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to VAC Check for 24 volts across terminals 24 COM and FAN ter minals on the integrated control If voltage is present prob lem is with the harness If voltage is not present problem may be may be with the integrated control Check ...

Page 16: ...l read approxim ately the same resistance within an ohm 3 Check to see if the blower wheel spins freely FIGURE 16 Motor Test TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 000 200 K two hundred kilo ohm two hundred thousand ohms 0 200 000 20 K twenty kilo ohm twenty thousand ohms 0 20 000 2 K two kilo ohm two thousand ohms 0 2 000 200 two hundred ohms 0 200 M...

Page 17: ...s to be performed 3 Remove the heating compartment access panel 4 Move gas valve switch to OFF position Do not force See figure 18 5 Replace the heating compartment access panel B Safety or Emergency Shutdown Disconnect main power to unit Close manual and main gas valves C Extended Period Shutdown Turn off thermostat or set to UNOCCUPIED mode Close all gas valves both internal and external to unit...

Page 18: ...to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and compare to value given in table 12 Manifold Pressure Measurement 1 Remove the threaded plug from the outlet side of the gas valve and install a field provided barbed fitting Connect to a test gauge to measure manifold...

Page 19: ... 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Altitude Natural Gas Burner Orifice Kit Natural Gas to LP Propane Burner Orifice Kit LP Propane to Natural Gas Burner Orifice Kit 0 4500 ft 4501 7500 ft 7501 10 000 ft 7501 10 000 ft 0 7500 ft 7501 10 000 ft 0 7500 ft 045 No Change No Change 80W51 73W37 11K49 11...

Page 20: ...nergized 0 75 5 Indoor Blower Energized Less than 2 10 CHECK VOLTAGE BETWEEN LINE NEUTRAL AND LOW VOLTAGE C TERMINAL FIGURE 20 CHECK VOLTAGE BETWEEN LINE HOT AND LINE NEUTRAL FIGURE 21 V TYPICAL OPERATING CHARACTERISTICS A Blower Operation and Adjustment NOTE The following is a generalized procedure and does not apply to all thermostat controls 1 Blower operation is dependent on thermostat control...

Page 21: ... trol See figure NO TAG The heating tap is connected to the HEAT terminal and the cooling tap is connected to the COOL terminal The continuous blower tap is connected to the FAN terminal Unused taps must be secured on dummy terminals labeled PARK To change out existing speed tap turn off power and switch out speed tap with tap connected to PARK See blower speed tap table on unit diagram for motor ...

Page 22: ...l system test Turn on the furnace to check operating functions such as the start up and shut off operation 1 Check the operation of the ignition system inspect and clean flame sensor Check microamps before and after Check controls and safety devices gas valve flame sensor temperature limits Consult Service Manual for proper operating range Thermal Limits should be checked by restricting airflow an...

Page 23: ...er Failure to replace all screws may cause leaks Inspect gaskets for any damage and replace if necessary 14 Reinstall burner box manifold assembly and burner box cover 15 Reconnect all wires 16 Reconnect top cap and vent pipe to combustion air in ducer outlet 17 Reconnect gas supply piping 18 Turn on power and gas supply to unit 19 Set thermostat and check for proper operation 20 Check all piping ...

Page 24: ...s are found to be closed Call for heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A92 integrated control energizes R33 ignitor A 20 second warm up period begins 7 GV1 gas valve opens for a 4 second trial for ignition 8 Flame is sensed gas valve remains open for the heat call 9 A...

Page 25: ...LVE ENERGIZED GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until pressure switch opens or thermostat resets control NO NO YES YES IS VOLTAGE ABOVE 70 VOLTS LED FLASHES CODE 13 LOW LINE VOLTAGE CONTROL WILL NOT RESPOND TO A CALL FOR HEATING UNTIL ...

Page 26: ...TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR THERMOSTAT IS CYCLED OFF ON FOR 1 SEC MINIMUM YES THERMOSTAT DEMAND SATISFIED LED SLOW FLASH COMB AIR INDUCER CONTINUES 5 SECOND POST PUR...

Page 27: ...LOSED LED SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR OFF THERMOSTAT OPENS SYSTEM FAN AND EAC TERM OFF WITH 45 SECOND DELAY NO NO LED FLASHES CODE 8 ROLLOUT SWITCH OPEN GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON SEQUENCE HOLDS UNTIL...

Page 28: ...M FAN SWITCHED TO COOL SPEED EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 SECOND DELAY EAC AND HUM TERMINAL REMAIN ON SYSTEM FAN CONTINUES FAN SPEED WITHOUT INTERRUPTION EAC TERMINAL REMAIN ON HUM TERMINAL IS ENERGIZED WITH COMBUSTION AIR BLOWER HU...

Reviews: