eCO2Boost XS 3
7
4.2. Installation place
INSTALLATION CONDITIONS:
Provide space above the equipment to allow it to be opened (access for maintenance / reparation operations).
Provide at least 500 mm of free space on the right-hand side.
Provide at least 500 mm of free space on the left-hand side and the front and back.
4.3. Installation condition
1.
Install the equipment in a dry and well-ventilated location, where air isn't recycled.
2.
Place the equipment in a location sheltered from direct sunlight, heat sources and cold wind.
If exposing the equipment to direct sunlight is unavoidable, protect the device with a canopy.
3.
Choose a location where the noise produced by the refrigerating unit will not disturb any close neighbors.
The noisiest parts are located on sides and at the back of the unit.
4.
The air outlet must not be directed towards house windows or plantations.
5.
Place the equipment on a solid, smooth surface.
6.
Place the equipment in a location where dust and debris do not risk being sucked into the unit cooler fins.
7.
In regions where significant snowfalls occur, always place the equipment under a roof,
a shelter or a snow-proof tarpaulin.
8.
Choose a location that is protected from strong winds.
9.
Avoid locations exposed to oil splashes, salt (within 2km from coast), sulfur gas (nearby hot water springs),
volcanic area.
10.
To avoid any interference, the refrigerating unit must be installed at a minimum distance of 3 m
from any device producing or receiving electromagnetic waves (e.g. radio).
Protect direct sunlight and
then do not disturb fan air flow
CDU :
Distance 500 mm
from wall or barrier
5. Handling
When raising the refrigerating unit, always observe the following
safety precautions:
1.
Protect any parts that are in contact with hoisting ropes,
e.g. using cardboard.
2.
When the refrigerating unit is raised, do not go beneath it.
3.
Weight CDU:
Product weight: 135kg
Total weight including packaging: 145kg
4.
This product's weight is not evenly distributed.
In particular, take care to avoid any shocks and sudden
movements when transporting and raising the equipment.
Installation conditions
•
Provide space on the top of product for the opening of product casing.
•
Provide at least 500 mm of free space on the left and right-hand side and the front and back.