eCO2Boost XS 3
19
Error
Error type
Alarm conditions
CDU status
In case of master
controller
Recovery
Conditions
E23
Ambient air
temperature
sensor error
-30°C
≥
TAR
≥
100°C
during 3 seconds
-30°C = 129,3k
Ω
100°C=1,02k
Ω
operate
EEV=(A10paramete)
pls Default
value=480
Alarm activation
CDU operate
Automatic
recovery if :
-30°C
≤
TAR
≤
100°C
E24
Discharge
temperature
sensor error
-15°C
≥
Td
≥
200°C
during 3 seconds
-15°C =
162k
Ω
200°C=892
Ω
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
-15°C
≤
Td
≤
200°C
E26
Heat exchanger
inlet temperature
sensor error
-30°C
≥
Ti
≥
100°C
during 3 seconds
-30°C = k
Ω
100°C=
Ω
operate
Alarm activation
CDU operate
Automatic
recovery if :
-30°C
≤
Ti
≤
100°C
E27
Heat exchanger
outlet temperature
sensor error
-30°C
≥
TU
≥
100°C
during 3 seconds
-30°C = k
Ω
100°C=
Ω
operate
Alarm activation
CDU operate
Automatic
recovery if :
-30°C
≤
TU
≤
100°C
E40
Communications
error with master
controler (if using
an external
communication
system)
No communication
during 10 minutes
operate with local
target value
Alarm activation
CDU operate
Automatic
recovery if :
communication
restart with
master
E42
Inverter
communications
error
No communication
during 30 seconds
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
communication
restart
E50
EEV control error 1
Calculation error
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
calculation is OK
E51
EEV control error 2
Calculation error
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
calculation is OK
E70
Inverter control
error 1
Calculation error
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
calculation is OK
E71
Inverter control
error 2
Calculation error
no operate
Alarm activation
CDU no operate
Automatic
recovery if :
calculation is OK
15. Code error list