background image

Indoor unit 1

Wired controller 2

Wired controller 1

P

Q

E

X1

X2

X1

X2

X1

X2

Figure 6.7

Master wired controller

Slave wired controller

Indoor unit 1

Indoor unit 2

P Q E

X1 X2

P Q E

X1 X2

D1

D2

P Q E

X1 X2

Wired controller 1

X2

X1

D2

D1

Wired controller 2

X2

X1

D2

D1

Figure 6.8

Master wired controller

Slave wired controller

Indoor unit 1

Display board

A

B
C

D

A

B
C

D

Wired controller 1

6.4  Handling the Electrical Wiring Connection Points

The  X1/X2,  D1/D2  ports  on  the  sides  of  the  main  control  board  and  the 

unidirectional communication port (display board side) are for different 

types of wired controllers (see Figure 6.10).
Use the connecting wires (accessories) to connect the D1/D2 terminals.

Once the wiring and connections are done, use tie straps to secure the 

wiring properly so that the connection joint cannot be pulled apart by 

external force. The connection wiring must be straight out so that the cover 

of the electrical box is level and can be closed tightly.
Use professional insulation and sealing materials to seal and protect the 

perforated wires. Poor sealing may lead to condensation, and entry of small 

animals and insects that may cause short circuits in parts of the electrical 

system, causing the system to fail.

2) For a unidirectional communication mode:
  

Use 1 wired controller to control 1 indoor unit (see Figure 6.9).

Figure 6.9

Figure 6.10

9

ENC1

POWER_S

0

2200W

1

2800W

2

3600W

3

4500W

4

5600W

5

7100W

6

8000W

Caution

Caution

•  The capacity DIP switches have been configured before delivery. Only 

a professional maintenance personnel should change these settings.

•  Once the centralized control function for the indoor unit has been 

completed on the outdoor unit, the DIP switch on main control panel of 
the outdoor unit must be set to auto addressing; otherwise, the indoor 
unit in the system are not controlled by the centralized controller.

•  The system can connect up to 64 indoor units (address 0~63) at the same 

time. Each indoor unit can only have one address DIP switch in the system. 
The addresses of any two indoor units in the same system cannot be the 
same. Units that have the same address may malfunction.

7.1  Capacity Settings

7.3  DIP Switch Settings on Main Board

7. 

On-site Configuration

Set up the PCB DIP switch on the indoor electric control box to cater to different 
uses. Once the settings are done, make sure you cut off the main power switch 
again, and then switch the power on. If the power is not cut off and switched on 
again, the settings will not be executed.

ENC1 Settings for Capacity DIP Switch:

DIP Switch Code

Capacity

7.2  Address Settings

When this indoor unit is connected to the outdoor unit, the outdoor unit will 

automatically allocate the address to the indoor unit.

Alternatively, you may use the controller to manually set the address.

w

  The addresses of any two indoor units in the same system cannot be the 

same.

w

  The network address and the indoor unit address are the same, and does 

not have to be configured separately.

w

  Once the address settings are completed, mark the address of each indoor 

unit to facilitate after-sales maintenance.

w

  The centralized control of the indoor unit is completed on the outdoor unit. 

For details, refer to the manual on the outdoor unit.

Indoor unit n(n<=16)

For the specific connection method, refer to the instructions in the 

corresponding wired controller manual to carry out the wiring and 
connections.

Caution

• 

0/1 definition of each dial code switch: 

means 0

means 1

XP4 XS4

P

Q

E

X1

X2

Yellow

Grey

White

Blue

Black

Display board

D2     D1

CN17

CN9

CN15

Main control panel

To wired 

controller 

COMM. BUS

Wired 

controller

A

B
C

D

ENC1

SW1 SW7

SW2

SW3

SW4

SW5

SW6

ON

ON

POWER_S

ON

ON

ON

ON

ON

ON

1 2

ON

1 2

ON

1 2

ON

1 2

ON

1 2

ON

1 2

ON

1 2

To wired 

controller

COMM. BUS

To outdoor/

indoor units 

COMM. BUS

D1

D2

D1

D2

D1

D2

D1

D2

D1

D2

Summary of Contents for e-Lite

Page 1: ...LV FS 2DC IOM 20 04 E e Lite FLOOR STANDING UNIT Installation and Operation Manual...

Page 2: ......

Page 3: ...er installa tion may cause the air conditioner to drop leading to accidents Make sure a standalone circuit is used for the power supply All electrical parts must comply with the local laws and regulat...

Page 4: ...g to suffocation 11 The appliance shall not be installed in the laundry Accessories Verify that the air conditioner includes the following accessories Name Installation Manual Insulation piping two ki...

Page 5: ...onment Square bar material Beam Ceiling Lifting bolt Figure 3 1 Wooden structure Secure the square rod on the beam to set the lifting bolts Figure 2 3 Covered Figure 2 2 Uncovered bottom return air Fi...

Page 6: ...stall 1 Dismantle the panel and follow the instructions described in the following diagram to remove the structure and fix the screws Figure 3 6 B A C Capacity kW 2 2 2 8 3 6 4 5 5 6 8 0 A mm B mm 120...

Page 7: ...5 6 4 12 7 12 7 15 9 C mm 725 925 1225 2 2 2 8 3 6 4 5 5 6 8 0 C Dimensions of unit Capacity kW Table 3 3 Figure 3 11 Figure 3 12 Figure 3 13 Liquid end of refrigerant piping A Gas end of refrigerant...

Page 8: ...ot let air or other gases enter the refrigeration circuit If the refrigerant leaks during installation make sure you fully ventilate the room Use two wrenches when you install or dismantle the piping...

Page 9: ...ject 500 1000 ml of water into the water pan 2 Verify that the water discharge piping outlet discharges water properly and check for water leakages at each joint 5 2 Water Discharge Test 6 When connec...

Page 10: ...nits electrical characteristics Capacity IFM Hz Volts MCA MFA kW FLA 2 8kW 2 2kW 50 50 60 220 240 15 0 49 0 55 0 55 0 55 0 85 1 4 1 4 15 4 5kW 15 5 6kW 15 7 1kW 15 8 0kW 15 15 Power supply 3 6kW 0 1 0...

Page 11: ...system are not controlled by the centralized controller The system can connect up to 64 indoor units address 0 63 at the same time Each indoor unit can only have one address DIP switch in the system...

Page 12: ...is the same as the rated voltage of the air conditioner No obstacles at the air inlet and outlet of the indoor and outdoor units Cut off valves for the gas and liquid ends of the outdoor unit are ope...

Page 13: ...t place vases or other liquid containers on the unit or in places where liquid could drip onto it Water or other liquids that come into contact with the unit can lead to electric shocks or fires Do no...

Page 14: ...ust the air out direction Air Intake Intakes room air Air intake Intake room air here Air out air out louver Adjust the air out direction Feet Lift up the air conditioner 9 Part Names The figure shown...

Page 15: ...Unit state Digital display Standby Shutting down Operation indicator flashes slowly All indicators off Operation indicator on Operation Normal operation Cold draft prevention or outdoor unit defrosti...

Page 16: ...tioner ensure it is powered off Check that the wiring is undamaged and connected Use a dry cloth to wipe the indoor unit and remote controller A wet cloth may be used to clean the indoor unit if it is...

Page 17: ...rom the remote controller Symptom 2 The unit emits white mist White mist is generated and emitted when the unit starts to operate in a very humid environment This phenomenon will stop once the humidit...

Page 18: ...ant leak has occurred Low heating effect Doors or windows are not completelyclosed Close doors and windows Arrange for a professional technician to check the following A refrigerant leak has occurred...

Page 19: ...a certain time No receiving soundfrom the indoor unit whenthe ON OFF button is pressed Check whether the MODE indicated on the display is AUTO Check whether the MODE indicated on the display is DRY A...

Page 20: ...Line loosened or broken w The electronic expansion valve in stuck w Outdoor unit error Ed w Outdoor unit error Water level error EE w Water level float stuck w Water level switch not connected proper...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...and dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause property damage or personal injury Ins...

Reviews: