background image

Page 11

XP25 SERIES

STEP 4 -- LEAK TEST AND EVACUATION (Continued)

A.

Open both manifold valves and start the vacuum pump.

B.

Evacuate the line set and indoor unit to an 

absolute pressure

 of 23,000 microns (29.01 inches of mercury).

NOTE 

— During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a

relatively large leak. If this occurs, 

repeat the leak testing procedure

.

NOTE 

— The term 

absolute pressure

 means the total actual pressure above zero within a given volume or system. Absolute pressure in a

vacuum is equal to atmospheric pressure minus vacuum pressure.

C.

When the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following:

S

Close manifold gauge valves.

S

Close valve on vacuum pump.

S

Turn off vacuum pump.

S

Disconnect manifold gauge center port hose from vacuum pump.

S

Attach manifold center port hose to a nitrogen cylinder with pressure
regulator set to 150 psig (1034 kPa) and purge the hose.

S

Open manifold gauge valves to break the vacuum in the line set and indoor
unit.

S

Close manifold gauge valves.

D.

Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.

E.

Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing
the manifold gauge valves.

F.

When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line
set and indoor unit.

G.

Perform the following:

S

Close manifold gauge valves.

S

Shut off HFC-410A cylinder.

S

Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure.

S

Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6) of a turn as illustrated.

OUTDOOR

UNIT

TO VAPOR

SERVICE VALVE

TO LIQUID LINE
SERVICE VALVE

MICRON

GAUGE

VACUUM PUMP

1/4 SAE TEE WITH SWIVEL
COUPLER

500

MANIFOLD

GAUGE SET

HFC-410A

RECOMMEND

MINIMUM 3/8” HOSE

A.

Connect low side of manifold gauge set with
1/4 SAE in-line tee to 

vapor 

line service valve

B.

Connect high side of manifold gauge set to

liquid 

line service valve

C.

Connect available micron gauge connector
on the 1/4 SAE in-line tee.

D.

Connect the vacuum pump (with vacuum
gauge) to the center port of the manifold
gauge set. The center port line will be used
later for both the HFC-410A and nitrogen
containers.

HIGH

LOW

1

2

3

4

5

6

7

8

9

10

11

12

1/6 TURN

NITROGEN

3

CONNECT GAUGE SET

A

B

C

D

4

EVACUATE THE SYSTEM

NOTE 

— Remove cores from service valves (if not already done).

Possible equipment damage.

Avoid deep vacuum operation. Do not use
compressors to evacuate a system.
Extremely low vacuum can cause internal
arcing and compressor failure. Damage
caused by deep vacuum operation will
void warranty.

WARNING !

NOTE - Position
canister to deliver
liquid refrigerant.

EVACUATION

FIGURE 7

Summary of Contents for Dave Lennox Signature XP25

Page 1: ...LATION INSTRUCTIONS Dave Lennox Signature Collection XP25 System HEAT PUMPS 507005 01 7 2018 PACKING LIST OUTDOOR UNIT WARRANTY CARD GROMMETS 2 BUSHING 1 RAST 6 PIN CONNECTOR 1 WARNING Improper instal...

Page 2: ...WOOD OR PLASTIC SLAB NO PLASTIC ANCHOR HOLE DRILL 1 8 INSTALL UNIT LEVEL OR IF ON A SLOPE MAINTAIN SLOPE TOLERANCE OF 2 DEGREES OR 2 INCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUN...

Page 3: ...nt or scratched While handling or stowing the panels consider any weather conditions especially wind that may cause panels to be blown around and damaged UNIT DIMENSIONS INCHES MM 4 5 8 117 BASE WITH...

Page 4: ...ressors have an internal vacuum pro tector that will unload scrolls when suction pressure goes below 20 psig A hissing sound will be heard when the compressor is running unloaded Protector will reset...

Page 5: ...Sizes for Horizontal Runs Required Vapor Riser Size 024 180 150 60 60 7 8 5 8 036 180 150 60 60 7 8 3 4 048 180 150 60 60 7 8 7 8 060 180 150 60 60 7 8 7 8 Table 3 Liquid Line Diameter Selection Table...

Page 6: ...the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LIN...

Page 7: ...rvice port nitrogen flow will have an exit point NITROGEN HIGH LOW B A C PIPING PANEL REMOVAL PREPARING LINE SET CAP AND CORE REMOVAL Remove piping panel to access service valves Cut ends of the refri...

Page 8: ...ted nitrogen at 1 to 2 psig through the refrigeration gauge set into the valve stem port connection on the liquid service valve and out of the suction vapor valve stem port See steps 3A 3B and 3C on p...

Page 9: ...ASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon...

Page 10: ...he cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 11: ...and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A positioned...

Page 12: ...e care during unit installation and service to protect the unit s electronic controls Precautions will help to avoid control exposure to electrostatic discharge by putting the unit the control and the...

Page 13: ...rminals PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMP...

Page 14: ...nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as shown in the figure below Any...

Page 15: ...play and push button operations are available on the unit access panel and in the XP25 Installation and Service Procedures Corp 1252 L11 System Component Configuration Outdoor Unit All outdoor unit se...

Page 16: ...ls to operate check the following before calling for service S Verify room thermostat settings are correct S Verify that all electrical disconnect switches are ON S Check for any blown fuses or trippe...

Reviews: