16
2
3
1
2%
50
WARNING
Electric shock hazard can cause
injury or death. Before attempting
to perform any service or
maintenance on the unit, turn OFF
the electrical power, and check that
the fan has stopped.
Cover plate for
electrical box
Terminal
plate
cover
MODEL 600x1200
MODEL 600x600
Cover plate for
electrical box
Cover plate
for auxiliary
electrical box
Terminal
plate
cover
1
2
3
Electrical inlets, power supply and remote controller.
Terminal plate.
Electrical connections (it depends on versions).
DRAIN PIPEWORK
ELECTRICAL CONNECTIONS
Drain tube
Condensate
pump flexible
hose
Drain tube
Condensate
pump flexible
hose
2%
Max.200mm
ACCESS TO THE ELECTRICAL COMPONENTS OF THE UNIT
Removing the corresponding plate cover screws gives access to the electrical board and terminal plate, as indicated on the
drawing.
ELECTRICAL WIRING DIAGRAM
For electrical connection refer to wiring diagram in the unit.
DRAIN TUBE
The drain tube is connected to drip tray.
This drain tube is supplied with a cap; the cap can be removed when it is necessary to remove any water that accumulates
in the drip tray.
CONDENSATE PUMP FLEXIBLE HOSE
The unit is fitted with a condensate pump to ensure condensate removal.
To ensure that there is condensate flow, the drain tube must be installed with a fall of 2% without obstructions, or without
rising sections.
To avoid any unpleasant odours from the drainage system a trap must be fitted with a trap depth of no less than 50 mm.
The condensate pump has a maximum lift of 200 mm. The rising tube must be always vertical.
On completion the drain line must be insulated.
MODELS 600 x 1200
MODELS 600 x 600