+19º C STANDARD UNIT
0ºC WITH OPTIONAL CPC ON/OFF
-10ºC (*)
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
COOLING CYCLE
OPERATION
MAXIMUM TEMPERATURES
MINIMUM TEMPERATURES
MAXIMUM TEMPERATURES
MINIMUM TEMPERATURES
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
INDOOR
TEMPERATURE
OUTDOOR
TEMPERATURE
COOLING CYCLE
OPERATION
HEATING CYCLE
OPERATION
32ºC DB / 23ºC WB
DEPENDING ON MODEL
(TABLE 1)
+19ºC STANDARD UNIT
0ºC WITH OPTIONAL CPC ON/OFF
-10ºC (*)
21ºC DB / 15ºC WB
32ºC DB / 23ºC WB
21ºC DB / 15ºC WB
27ºC DB
15ºC DB
24ºC DB / 18ºC WB
-10ºC DB / -11ºC WB
DEPENDING ON MODEL
(TABLE 1)
11
22E
45
43
24E
45
43
28E
43
41
32E
43
40
38E
42
39
44D
45
43
48D
45
43
56D
43
41
64D
43
40
76D
42
39
22E
48
46
24E
48
45
28E
46
44
32E
46
44
38E
45
42
44D
48
46
48D
48
45
56D
46
44
64D
46
44
76D
45
42
(*) With kit hot gas by pass or proportional winter control (options).
(*) With kit hot gas by pass or proportional winter control (options).
1.- GENERAL CHARACTERISTICS
OPERATING LIMITS FOR (HEATING PUMP) UNITS
OPERATING LIMITS FOR (COOLING ONLY) UNITS
1.4.- OPERATING LIMITS
DB.- Dry Bulb Temperature
WB.- Wet Bulb Temperature
TABLE 1-COOLING CYCLE MAXIMUM OUTDOOR OPERATING TEMPERATURES
MODELS
With rated outdoor flow
With minimum outdoor flow
MODELS WITH
Refrigerant R-407C
MODELS
With rated outdoor flow
MODELS WITH
Refrigerant R-22
With minimum outdoor flow
Summary of Contents for Compactair LVCK 22E