Lennox Compact Pro Installation Operating & Maintenance Manual Download Page 11

 

 

2.3.2 

When the machine is heating, it produces condensate 

Provision for 

that has to be eliminated through a specific drain line, 

 draining con-  

otherwise the machine will not work. Drainage occurs by 

         densate for 

gravity. For this reason, it is essential for the drain line to 

    machines with 

have a minimum inclination of at least 3% throughout its 

heat pump. 

length. The pipe can be rigid or not, with a minimum 
internal diameter of 16 mm. If the line drains into a sewer 
system, it should be provided with a trap ahead of the main 
outlet. The trap should be at least 300 mm lower than the inlet 
opening on the air conditioner (fig. 7). 

If the drainpipe drains into a vessel (tank or other container), 
this container should not be sealed and the drainpipe should 
not remain immersed in the water (see fig. 8). 
The correct position for the pipe inlet on the machine is shown on 
the template for drilling and positioning the machine (see 
also fig. 6). 
The air conditioner is equipped with a pipe with an external 
diameter of 14 mm for drainage of condensate. This pipe 
protrudes from the machine for a length of about 400 mm. 
The pipe should be fitted inside the one provided by you  for a 
distance of at least 200 mm, without any sharp bends  that could 
obstruct it. 
When draining toward the outside, the pipe can be  inserted 
through the wall (always making sure to give it a  suitable 
inclination) (see fig. 5). 

 

 

Caution: make sure, in this case, that the water expelled 
outward does not damage or disturb persons or 
property. During the winter this type of drainage may 
cause sheets of ice to form. 

2.3.3 

After drilling the holes, the plastic pipes supplied with the 

      Installation of air 

air conditioner have to be fitted through them. The pipe 

   pipes and 

with insulation on the inside has to be fitted in the right 

 external 

hand hole with the insulated part toward the inside as 

  gratings 

indicated on the label applied to it. The length of the pipes 
should be 55 mm less than that of the wall. To cut the pipe, 
a normal handsaw can be used. After cutting the  pipes, fit 
the ends into the two internal anchoring flanges (fig. 10). 

The tube diameter is 152mm and should fit comfortably into 
the hole formed by the 158mm diameter core drill.  When 
introducing the tubes they may need to be forced slightly using, in 
the most difficult cases a normal rubber  hammer (fig. 10/1). 
Having the hole internal diameter extremely similar to the 
tube external diameter avoids dangerous slacks which may 
generate humidity infiltrations or air noises. Should the insertion 
prove to be too difficult, we suggest you drill using the core bit 
inside the hole so as to widen the internal diameter slightly.  If 
there is excessive play and air gap around the tubes then we 
recommend a sealant be used to ensure a tighter fit. 

 

Next, fit the pipes into the holes in the wall and fasten the flanges 
with 4 anchor bolts with diameter 6, taking care to keep the two 
fastening holes in a horizontal position. 

Fig. 9 

 

Fig 10/11 

Summary of Contents for Compact Pro

Page 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Compact Pro...

Page 2: ...ning unit You have bought one of the best air conditioners available today Follow the instructions given in this booklet to obtain the very best performance from your air conditioner and to enjoy a fr...

Page 3: ...nstallation of Wall Mounted Controller page 17 Chap 3 USE AND MAINTENANCE for the user 3 1 Important Recommendations page 26 3 2 Names of parts page 26 3 2 1 List of Units page 26 3 2 2 Description of...

Page 4: ...conditioner is installed by personnel lacking the necessary qualifications and specialization this invalidates the warranty CHAP 3 USE AND MAINTENANCE by user Contains all information and instructions...

Page 5: ...its as well as all the precautions suggested by good sense and by the safety regulations in effect in your country CHAP 1 2 SYMBOLS The pictograms in the next chapter provide the necessary information...

Page 6: ...t at 35 C b s in heating mode Air entering the inside unit at 21 C b s and 19 C b u with air entering the outside unit at 7 C b s and 6 C b u 1 3 4 The air conditioner should be used for the exclusive...

Page 7: ...UPSIDE DOWN 1 4 2 The packing is made of suitable material and is done by expert personnel Receipt and The units are delivered complete and in perfect condition however we suggest that you perform the...

Page 8: ...ce that wouldinterferewithcorrectoperation of the unit It must be possible to leave room around the unit for any maintenance operations that may be necessary The air conditioner must be installed on a...

Page 9: ...es in walls are special drills called core borers with very high twisting torque and adjustable rotation speed depending on the diameter of the hole to be drilled To prevent the creation of large amou...

Page 10: ...wall should be inspected carefully to determine the best possibleanchorageand typeofboltssuitableforparticular situations Warning The manufacturer is not liable in case of underestimation of the stru...

Page 11: ...g 5 Caution make sure in this case that the water expelled outward does not damage or disturb persons or property During the winter this type of drainage may cause sheets of ice to form 2 3 3 After dr...

Page 12: ...l with 4 anchor bolts with a diameter of 6 mm 2 3 4 The air conditioner is equipped with a power supply cable Power supply and plug Connection Ifitisinstallednearanoutlet youneedonlyplugitin In this c...

Page 13: ...it into position especially at high level CHAP 2 4 PREPARATION FOR ASSEMBLY INSTALLATION WALL TOP PART AT HIGH LEVEL 2 4 1 The air conditioner is assembled in the factory ready to Introduction be inst...

Page 14: ...ep step motor of the grating Fit the casing back on the air conditioner carefully taking care to hold the wires for the step step motor to one side so that they do not interfere with the inner part of...

Page 15: ...he LEDs lighting up at once and blinking ten times as well as by an acoustic signal At this time you can adjust the temperature reading on the room temperature sensor This correction is important if t...

Page 16: ...After eliminating the malfunction the service personnel will take care of closing the evacuation tube CHAP 2 6 PERIODICAL MAINTENANCE Air conditioners of this type do not require any particular routi...

Page 17: ...fectly horizontal or at the most having a slight inclination toward outside Put the 130 mm pipe into the hole after you cut it according to the wall thickness ATTENTION the pipe supplied with the kit...

Page 18: ...E INSTRUCTIONS IN THIS MANUAL Themanufacturerhastherightofmodifyingtheunit atanytime whilstmaintainingthe mainfeatures described in this manual During installation or maintenance it is necessary to fo...

Page 19: ......

Page 20: ...ructions may cause malfunction of the device and warranty won t be valid anymore B1000 can work in stand alone or in a network by changing the set of switches Positioning of B1000 The card must be pla...

Page 21: ...box by taking the screw on the right side out B To fix the box to the wall use the screws that are given in the pack C Attention Be very careful in order not to damage the card and its components dur...

Page 22: ...control box push the trigger on the left side and lift rotating towards the other side Positioning If you put the control farer than 2m from the conditioner you have to take a loner wire In this case...

Page 23: ...75 230v 50Hz given K2 CAN BUS mains 1 CAN L 2 CAN H 3 GND 4 Screening Screened cable 3x0 34 K3 Serial for the air conditioner 1 TX 2 GND 3 RX Given Not extendible K4 Contact occupied room 1 Contact r...

Page 24: ...s specified in the instructions if you use the mains connection DIP SWITCH CONFIGURATION On the board there are 12 microswitches dip switch that are subdivided in two groups of 4 S1 and 8 S2 selectors...

Page 25: ...model In mails Stand alone 1 The address of the board on CAN bus has to be unique and unequivocal the coding is expressed on the basis 2 2 The function of this selector is active only for the configu...

Page 26: ...2 C and t set C Temp pilot light it lights up when it is fixed a temperature 2 C lower than the set one D Temp pilot light it lights up when it is fixed a temperature 2 C higher than the set one When...

Page 27: ...h the remote control Once the machine is started through the remote control in compliance with the above data you have to press the button placed on the power board see picture to store on the Eprom t...

Page 28: ......

Page 29: ...f airflow 3 Motor operated air baffles for upward airflow 4 Alarm display console 5 Air intake grating 6 Grips for removal of air filter 7 Rubber hose with cap on end for evacuation of 8 condensation...

Page 30: ...collection points provided by the local authorities for this type of waste REPLACE BOTH BATTERIES AT THE SAME TIME To insert the batteries remove the spring latch cover on the back of the remote contr...

Page 31: ...witch off or unplugging the machine from the mains 3 4 4 By means of this button the machine is automatically Wellbeingmode regulated in order to create an optimal comfort tempera Automatic ture in th...

Page 32: ...ing pump HP heatpump To select this mode press button T4 operating mode selection switch until the sun symbol appears on the display First set the desired temperature and fan speed see the specific pa...

Page 33: ...o the effective room temperature As the room temperature nears the setting fan speed is reduced automatically When the unit is operating in dehumidification mode fan speed adjustment is not possible a...

Page 34: ...ed Night comfort mode operation is not available for dehumidifying only Night comfort mode operation can be halted at any time ideally when you wake up in the morning by pressing button T3 again At th...

Page 35: ...ime when you want program 2 to start Every time you press one end of the toggle button the time setting increases or decreases by 30 minutes g Press button T6 Time and Program Setting as many times as...

Page 36: ...3 5 MAINTENANCE Your air conditioner has been designed to reduce operations of routine maintenance to a minimum and ensure that they can be performed easily by any user The only operations required a...

Page 37: ...nctions This is to safeguard the compressor When heating on versions with the heating pump the machine does not start emitting heat until a few minutes after the compressor starts If the fan should go...

Page 38: ...re has been an increase in the heating or cooling load for example a door or window has been left open or a device that dissipates a large amount of heat has been installed in the room what to do make...

Page 39: ...999A MICRO SWITCH TRIGGER 12 05M0194 DRAIN PUMP 13 281692B72 CONDENSATE DISTRIBUTOR 14 23M0114 CENTRIFUGAL FAN 15 275971A CAPACITOR 4mF 16 591908A85F ELECTRONIC BOARD UNIT SIZE 21 cooling only 17 5919...

Page 40: ......

Page 41: ...www lennoxuk com Lennox UK Cornwell Business Park Salthouse Road Brackmills Northampton NN4 7EX Tel 01604 669100 Fax 01604 669150 info uk lennoxeurope com 07 2005...

Reviews: