Lennox COMFAIR HH 10 Application Manual Download Page 10

• 8 •

10

20

30

40

50

60

70

175

225

275

325

375

825

1400

1,3

1,1

1

1

1

1

1

1300

1850

2275

2700

3150

6900

11575

70,8

71,9

70

69,9

70,1

70,4

70,3

10

20

30

40

50

60

70

75

125

150

200

225

600

1025

1,2

1

1,3

1

1,2

1,1

1

575

1050

1100

1650

1725

4900

8450

68,5

69,7

70

69,2

69,6

70,7

70,2

10

20

30

40

50

60

70

1

2

3

100

100

4

-

-

-

-

-

1

2

3

90

85

4

-

-

-

-

-

Application Guide  COMFAIR HH-AGU-1107-E

Data indicated as min., med., max. concern the 3 standard speeds set at the factory. Upon customer request other 3 speeds among the 6 speeds available can be 
connected.
NOTE: The symbol (-) means that for HH30 to HH70, only 3 fan speeds are available. For HH10 and HH20, upon customer request other 3 speeds among the 4 available 
speeds can be connected.

WORKING LIMITS - HH

Maximum entering water temperature:  70°C 

Maximum entering air temperature:  40°C

Minimum entering water temperature:   +4°C 

Minimum entering air temperature:  +4°C

Maximum working pressure: 

8 Bar

WATER FLOW AND PRESSURE DROP LIMITS, 3R COIL (HH10 TO HH50) 
AND 4R COIL (HH60 AND HH70)

WATER FLOW AND PRESSURE DROP LIMITS, 1 ROW COIL (HH10 TO 
HH50) AND 2R COIL (HH60 AND HH70)

Data given for medium water temperature at 9,5°C

3 WAYS VALVE

Using of 2 or 3 ways valves is compulsory when the unit is used for cooling to avoid condensate in the external structure (bearing 
structure and cabinet). As alternative install a regulating system to stop coil water entering when the fan is off.

When the units is connected with ducts fan air fl ow is reduced due to the ducting pressure drops.
With very high pressure drops fancoil air fl ow becomes too low and electric motor which is connected to the fan can be damaged. For 
this reason we recommand static pressures lower than the maximum limit static pressures indicated in the schedule.
NOTE: When the fancoil is operating with the maximum operating indicated static pressure value, air fl ow is half in comparison with 
the unit without ducts at the same working speed. Defi nitively the static presure limit corresponds to the back pressure ables to half 
fancoil air fl ow (as a consequence the fancoil unit performances like heating & cooling capacity, will be reduced of about 50%).

MAXIMUM FAN STATIC PRESSURE

Data given for medium water temperature at 65°C

COMFAIR

HH

Minimal water fl ow

l/h

Minimal water pressure drop

kPa

Maximal water fl ow

l/h

maximal water pressure drop

kPa

COMFAIR

HH

Minimal water fl ow

l/h

Minimal water pressure drop

kPa

Maximal water fl ow

l/h

maximal water pressure drop

kPa

COMFAIR

HH

2 pipes system

Pa

90 min

80 min

115 min

105 min

135 min

220 min

220 min

Pa

95 med

95 med

130 med

130 med

180 med

240 med

240 med

Pa

135 max

135 max

205 max

260 max

260 max

Pa 105 max

105 max

4 pipes system

Pa

75 min

70 min

95 min

90 min

110 min

180 min

180 min

Pa

85 med

80 med

115 med

115 med

155 med

210 med

210 med

Pa

120 max

120 max

180 max

220 max

220 max

Pa

95 max

90 max

Summary of Contents for COMFAIR HH 10

Page 1: ...lennoxemeia com COMFAIR HH APPLICATION GUIDE High pressure fan coil unit 840 8000 m3 h COMFAIR HH AGU 1107 E...

Page 2: ......

Page 3: ...ure fan coil units Product designed and manufactured under a quality management system certified ISO 9001 Our products comply with the European standards Our company is a member of the Eurovent Certif...

Page 4: ...is constructed to comply with all relevant International standards with a capacitor permanently in circuit Motors are connected directly to the fan shafts and are located on anti vibration mounts to e...

Page 5: ...y standards and are fitted as standard with a safety cut out thermostat and automatic reset Heater elements are factory fitted with all electrical wiring and are connected to the control panel via a c...

Page 6: ...30 8 20 11 9 25 3 13 3 15 24 3 18 4 33 8 19 3 24 9 26 8 22 9 37 21 7 33 8 0 11 0 14 0 3 0 31 0 28 0 12 0 17 0 32 0 34 0 41 0 16 0 22 0 32 0 34 0 58 230 1 50 63 53 61 59 61 67 62 68 66 68 69 66 70 70...

Page 7: ...al h Water flow 1 3 l h l s Water pressure drops in cooling 1 kPa mWG Water pressure drops in heating 3 kPa mWG Heating capacity 2 W kcal h Water flow 2 l h l s Water pressure drops in heating 2 kPa m...

Page 8: ...00 max 1 00 max 1 00 max 1 00 max 4 1 00 max 1 00 max Heating capacity 1 0 86 min 0 72 min 0 77 min 0 72 min 0 67 min 0 75 min 0 77 min 2 0 95 med 0 90 med 0 94 med 0 92 med 0 86 med 0 88 med 0 89 med...

Page 9: ...ng ISO 23741 6 Electrical data referred to the maximum available speed Data indicated as min med max concern the 3 standard speeds set at the factory Upon customer request other 3 speeds among the 6 s...

Page 10: ...nstall a regulating system to stop coil water entering when the fan is off When the units is connected with ducts fan air flow is reduced due to the ducting pressure drops With very high pressure drop...

Page 11: ...limit Air flow m3 h Available static pressure Pa Working limit Air flow m3 h Available static pressure Pa Working limit Data indicated as min med max concern the 3 standard speeds set at the factory...

Page 12: ...Pa Working limit Data indicated as min med max concern the 3 standard speeds set at the factory Upon customer request other 3 speeds among the 6 speeds available can be connected Air flow m3 h Availa...

Page 13: ...mit Air flow m3 h Available static pressure Pa Working limit Air flow m3 h Available static pressure Pa Working limit Data indicated as min med max concern the 3 standard speeds set at the factory Upo...

Page 14: ...Air flow m3 h Available static pressure Pa Working limit Air flow m3 h Available static pressure Pa Working limit Data indicated as min med max concern the 3 standard speeds set at the factory Upon cu...

Page 15: ...9 54 1 51 3 45 3 62 3 66 9 61 7 60 1 58 9 56 1 53 8 48 6 64 4 68 4 63 9 61 8 60 9 58 2 56 2 51 4 66 1 61 9 57 6 58 7 55 9 53 49 6 42 7 61 2 67 6 64 2 64 8 64 60 4 52 54 68 3 68 3 65 6 63 8 66 2 62 1...

Page 16: ...0 1 7 9 6 8 0 9 2 3 12 7 25 5 27 8 55 6 6 2 5 4 0 7 1 8 10 20 2 22 43 9 4 8 4 1 0 5 1 4 7 7 15 4 16 8 33 6 3 5 3 0 4 1 5 6 11 3 12 4 24 7 2 4 2 1 0 3 0 7 3 9 7 9 8 6 17 2 1 6 1 4 0 5 2 5 5 5 5 11 1 0...

Page 17: ...HH AGU 1107 E STANDARD COIL Ref water medium temperature 9 5 C Water flow l h Water pressure drops kPa Water flow l h Water pressure drops kPa AUXILIARY COIL Ref water medium temperature 65 C WATER C...

Page 18: ...65 75 533 852 96 107 133 235 100 200 35 43 65 28 36 41 46 57 117 192 Application Guide COMFAIR HH AGU 1107 E DIMENSIONAL DATA HH GENERAL DIMENSIONS 2 PIPES SYSTEM Models HH10 to HH50 Models HH60 and...

Page 19: ...13 140 240 35 42 95 114 35 32 43 40 65 30 38 44 49 61 130 210 Application Guide COMFAIR HH AGU 1107 E DIMENSIONAL DATA HH GENERAL DIMENSIONS 4 PIPES SYSTEM Models HH10 to HH50 Models HH60 and HH70 COM...

Page 20: ...258 1290 1985 546 898 998 1238 1238 1230 1924 195 195 222 222 272 568 568 215 215 242 242 292 625 625 67 67 67 67 67 118 118 10 10 10 10 10 31 31 Application Guide COMFAIR HH AGU 1107 E ACCESSORIES HH...

Page 21: ...900 1000 1240 1240 1240 1929 365 600 665 825 825 825 642 185 300 335 415 415 415 1286 70 70 70 70 70 100 100 330 330 330 330 330 625 625 136 136 136 136 136 288 288 200 200 225 225 275 575 575 170 170...

Page 22: ...8 1238 1242 1926 10 20 30 40 50 60 70 648 998 1098 1338 1338 1342 2026 219 219 244 244 294 416 416 197 197 222 222 272 394 394 548 898 998 1238 1238 1242 1926 A C 204 25 25 11 11 D 50 50 B 204 25 25 A...

Page 23: ...98 1098 1338 1338 1342 2029 84 159 109 128 128 131 380 580 780 980 980 980 1929 197 197 222 222 272 394 394 204 204 204 204 204 404 404 15 15 15 15 15 115 115 548 898 998 1238 1238 1242 1929 Applicati...

Page 24: ...242 1242 1932 315 315 340 340 390 650 650 200 200 225 225 275 395 395 360 360 360 360 360 490 670 340 340 340 340 340 470 650 115 115 115 115 115 255 255 265 265 265 265 265 395 575 Application Guide...

Page 25: ...1242 1245 1932 315 315 340 340 390 650 650 200 200 225 225 275 575 575 360 360 360 360 360 670 670 340 340 340 340 340 650 650 115 115 115 115 115 75 75 265 265 265 265 265 575 575 Application Guide C...

Page 26: ...0 2x 400 4x 400 E B C C D D A E A F 69 30 10 20 30 40 50 60 70 550 900 1000 1240 1245 1245 1935 200 200 226 226 276 576 576 135 181 227 170 135 320 242 280 270 272 300 325 600 482 100 100 113 113 138...

Page 27: ...0 50 60 70 600 952 1052 1292 1292 1290 1985 249 249 276 276 326 625 625 570 922 1022 1262 1262 1260 1260 219 219 246 246 296 595 595 539 891 991 1231 1231 1230 1926 188 188 215 215 265 565 565 10 20 3...

Page 28: ...PAM PAM AM PAM RAM PAM RAM RA BAM PAM SRE PAM B PAM SRE PAM BAM SRE SRE SRE FAM GAM FAM 130 251 12 251 12 200 373 12 373 12 Application Guide COMFAIR HH AGU 1107 E ACCESSORIES HH EXAMPLE OF ACCESSORI...

Page 29: ...ir conditioning system compressor or valve thermal protection 90 on the pump coil electrical connection by plug delivered with 1 m cable rubber mounting bracket included AVANTAGES Small size low noise...

Page 30: ...f Heating Cooling 3 speeds Ambiant temperature knob adjustment Wall mounted CD2X6 RCE10E Characteritics On Off Manual speed control Automatic fan control Manual Heating Cooling control Automatic Heati...

Page 31: ......

Page 32: ...ELGIUM AND LUXEMBOURG FRANCE GERMANY ITALY NETHERLANDS POLAND PORTUGAL Due to Lennox s ongoing commitment to quality the specifications ratings and dimensions are subject to change without notice and...

Reviews: