• 8 •
10
20
30
40
50
60
70
175
225
275
325
375
825
1400
1,3
1,1
1
1
1
1
1
1300
1850
2275
2700
3150
6900
11575
70,8
71,9
70
69,9
70,1
70,4
70,3
10
20
30
40
50
60
70
75
125
150
200
225
600
1025
1,2
1
1,3
1
1,2
1,1
1
575
1050
1100
1650
1725
4900
8450
68,5
69,7
70
69,2
69,6
70,7
70,2
10
20
30
40
50
60
70
1
2
3
100
100
4
-
-
-
-
-
1
2
3
90
85
4
-
-
-
-
-
Application Guide • COMFAIR HH-AGU-1107-E
Data indicated as min., med., max. concern the 3 standard speeds set at the factory. Upon customer request other 3 speeds among the 6 speeds available can be
connected.
NOTE: The symbol (-) means that for HH30 to HH70, only 3 fan speeds are available. For HH10 and HH20, upon customer request other 3 speeds among the 4 available
speeds can be connected.
WORKING LIMITS - HH
Maximum entering water temperature: 70°C
Maximum entering air temperature: 40°C
Minimum entering water temperature: +4°C
Minimum entering air temperature: +4°C
Maximum working pressure:
8 Bar
WATER FLOW AND PRESSURE DROP LIMITS, 3R COIL (HH10 TO HH50)
AND 4R COIL (HH60 AND HH70)
WATER FLOW AND PRESSURE DROP LIMITS, 1 ROW COIL (HH10 TO
HH50) AND 2R COIL (HH60 AND HH70)
Data given for medium water temperature at 9,5°C
3 WAYS VALVE
Using of 2 or 3 ways valves is compulsory when the unit is used for cooling to avoid condensate in the external structure (bearing
structure and cabinet). As alternative install a regulating system to stop coil water entering when the fan is off.
When the units is connected with ducts fan air fl ow is reduced due to the ducting pressure drops.
With very high pressure drops fancoil air fl ow becomes too low and electric motor which is connected to the fan can be damaged. For
this reason we recommand static pressures lower than the maximum limit static pressures indicated in the schedule.
NOTE: When the fancoil is operating with the maximum operating indicated static pressure value, air fl ow is half in comparison with
the unit without ducts at the same working speed. Defi nitively the static presure limit corresponds to the back pressure ables to half
fancoil air fl ow (as a consequence the fancoil unit performances like heating & cooling capacity, will be reduced of about 50%).
MAXIMUM FAN STATIC PRESSURE
Data given for medium water temperature at 65°C
COMFAIR
HH
Minimal water fl ow
l/h
Minimal water pressure drop
kPa
Maximal water fl ow
l/h
maximal water pressure drop
kPa
COMFAIR
HH
Minimal water fl ow
l/h
Minimal water pressure drop
kPa
Maximal water fl ow
l/h
maximal water pressure drop
kPa
COMFAIR
HH
2 pipes system
Pa
90 min
80 min
115 min
105 min
135 min
220 min
220 min
Pa
95 med
95 med
130 med
130 med
180 med
240 med
240 med
Pa
135 max
135 max
205 max
260 max
260 max
Pa 105 max
105 max
4 pipes system
Pa
75 min
70 min
95 min
90 min
110 min
180 min
180 min
Pa
85 med
80 med
115 med
115 med
155 med
210 med
210 med
Pa
120 max
120 max
180 max
220 max
220 max
Pa
95 max
90 max