CBX32M SERIES

Table 10.

 

CBX32M−048 Air Handler Performance (460V − 1 ph)

External Static Pressure

Air Volume and Motor Watts at Specific Blower Taps

Low

High

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

.00

0

1775

835

530

1870

885

610

.05

10

1775

835

530

1875

885

610

.10

25

1765

835

515

1870

880

590

.15

35

1750

825

510

1850

875

585

.20

50

1720

815

500

1825

860

575

.25

60

1685

795

490

1790

845

560

.30

75

1645

775

480

1745

825

545

.40

100

1530

720

450

1625

765

505

.50

125

1380

650

420

1465

690

470

.60

150

1195

565

385

1270

600

425

.70

175

975

460

350

1030

485

385

.80

200

720

340

320

755

355

340

NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Table 11. CBX32M-060 Air Handler Performance (208/230V)

External Static

Pressure

Air Volume and Motor Watts at Specific Blower Taps

Low

Medium

High

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

cfm

L/s

Watts

.00

0

1775

835

585

2025

955

670

2115

995

780

.05

10

1775

835

590

2010

950

665

2100

990

770

.10

25

1770

835

580

1995

940

655

2085

985

765

.15

35

1760

830

570

1975

930

645

2060

970

750

.20

50

1745

825

560

1950

920

635

2030

960

740

.25

60

1725

815

550

1915

905

625

2000

945

730

.30

75

1695

800

535

1880

885

610

1960

925

715

.40

100

1630

770

505

1795

845

580

1870

880

685

.50

125

1540

725

475

1690

795

545

1755

830

655

.60

150

1425

675

440

1560

735

515

1620

765

625

.70

175

1295

610

410

1415

670

480

1465

690

590

.80

200

1140

535

375

1250

590

445

1290

610

560

.85

210

1050

495

360

1160

550

425

1195

565

545

NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Table 12.

 

CBX32M−60

 

Air Handler Performance (460V − 1 ph)

External Static Pressure

Air Volume and Motor Watts at Specific Blower Taps

Low

High

in. w.g.

Pa

cfm

L/s

Watts

cfm

L/s

Watts

.00

0

1965

930

710

2140

1010

795

.05

10

1950

920

700

2110

995

780

.10

25

1930

910

685

2080

980

765

.15

35

1910

900

675

2045

965

755

.20

50

1880

890

660

2005

945

740

.25

60

1850

875

645

1965

925

725

.30

75

1815

855

630

1920

905

710

.40

100

1735

820

600

1820

860

680

.50

125

1635

770

570

1710

805

650

.60

150

1520

720

540

1585

750

615

.70

175

1390

655

505

1450

685

585

.80

200

1245

590

475

1305

615

550

.85

210

1165

550

460

1225

580

535

NOTE − All air data is measured external to unit with air filter in place. Electric heaters have no appreciable air resistance.

Summary of Contents for CBX32M Elite Series

Page 1: ...be levied for noncompliance INSTALLATION INSTRUCTIONS Elite Series CBX32M Units AIR HANDLER 506150 01 05 09 Supersedes 12 08 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Table of Contents CBX32M Up...

Page 2: ...ow LIQUID LINE SUCTION LINE SUPPLY AIR OPENING Return Air FILTER LOW VOLTAGE INLETS TOP AND RIGHT SIDE Return Air Top View Front View Side View Blower PIPING PLATE DETAIL FOR UPFLOW AND DOWNFLOW POSIT...

Page 3: ...G PLATE DETAIL LIQUID LINE SUCTION LINE 2 51 1 1 8 29 5 3 8 137 4 3 8 111 PIPING PLATE DETAIL Horizontal Position Left Hand Air Discharge Top View Front View 3 4 19 End View FOR DIMENSIONS A THROUGH H...

Page 4: ...air handler unit consists of two sections which are shipped assembled from the factory If necessary the unit may be disassembled to facilitate setting the unit Follow the steps below To disassemble 1...

Page 5: ...opening is fully open and free of any debris Also check to make sure that no debris has fallen into the drain pan during installa tion that may plug up the drain opening 3 Rotate the drain pan 180 fro...

Page 6: ...to downflow CBX32M unit circuit breakers must be rotated 180_ to the UP position See ECB29 installation instructions for more details NOTE If downflow application is required separately order kit num...

Page 7: ...n purging be sure it is done in a well ventilated area Purge low pressure nitrogen 1 to 2 psig through the refrigerant piping during brazing This will help to prevent oxidation and the introduction of...

Page 8: ...rd against damage to the paint 5 With the wet rag in place position a field provided elbow fitting to the air handler s suction line and line set Start nitrogen flow before brazing 6 After the procedu...

Page 9: ...ss panel Air leakage will occur if access panel is placed over filter door Filters should be inspected monthly and must be cleaned or replaced when dirty to assure proper furnace operation Reusable fi...

Page 10: ...igure 11 Typical Field Wiring Cooling Application with Electric Heat C W1 O Y1 R L T E C W1 G O Y1 R L T SERVICE LIGHT THERMISTOR Y2 Y2 2ND STAGE COMPRESSOR 1 2 3 4 5 6 COMMON ELECTRIC HEAT REVERSING...

Page 11: ...PUMP UNIT COMMON USED ONLY ON SOME THERMOSTATS Y2 USED ONLY WHEN TWO SPEED COMPRESSOR IS USED HP21 AMBIENT COMPENSATING THERMISTOR CONNECTION USED ONLY ON SOME THERMOSTATS LINE VOLTAGE FIELD INSTALLE...

Page 12: ...Page 12 506150 01 05 09 Figure 15 Typical Wiring Diagram Single Phase...

Page 13: ...Page 13 CBX32M SERIES Figure 16 Typical Wiring Diagram Three Phase...

Page 14: ...ies units with electric heat refer to the ECB29 installation instructions AIR VOLUME ADJUSTMENT Blower speed selection is accomplished by changing the taps at the harness connector at the Blower motor...

Page 15: ...20 50 1055 495 230 1190 560 280 1475 695 455 25 60 1060 500 220 1185 560 275 1450 685 440 30 75 1050 495 215 1175 555 375 1415 670 430 40 100 1005 475 290 1135 535 325 1335 630 400 50 125 915 430 255...

Page 16: ...data is measured external to unit with air filter in place Electric heaters have no appreciable air resistance Table 9 CBX32M 048 Air Handler Performance 208 230V External Static Pressure Air Volume a...

Page 17: ...2060 970 750 20 50 1745 825 560 1950 920 635 2030 960 740 25 60 1725 815 550 1915 905 625 2000 945 730 30 75 1695 800 535 1880 885 610 1960 925 715 40 100 1630 770 505 1795 845 580 1870 880 685 50 12...

Page 18: ...e cut in an X pattern peeled open glued with an appropriate all purpose glue and placed back against the cabinet surface being careful to not overly compress the insulation so the insulation can retai...

Reviews: