background image

Page 7

CBX27UH SERIES

AIR HANDLER UNIT

SUCTION LINE

LIQUID LINE

Figure 6. Brazing Connections

NOTE − CBX27UH series air handlers use nitrogen or
dry air as a holding charge. If there is no pressure when
the rubber plugs are removed, check the coil for leaks
before installing. After installation, pull a vacuum on the
line set and coil before releasing the unit charge into the
system.

NOTE − See outdoor unit instructions on how to flow
nitrogen through line sets.

1. Remove access panel.

2. Remove the refrigerant line caps from the refrigerant

lines.

3. Use a wet rag to protect TXV sensing bulb (or remove

it) when brazing suction line connections.

4. Place a wet rag against piping plate and around the

suction line connection. The wet rag must be in place
to guard against damage to the paint.

5. With the wet rag in place, position a field provided

elbow fitting to the air handler’s suction line and line
set. Start nitrogen flow before brazing.

6. After the procedure is completed then remove the wet

rag.

7. Place wet rag against piping plate and around the

liquid line connection. Position liquid line elbow to air
handler’s suction line and to line set. Start nitrogen flow
and begin brazing both connections and after
procedure is completed then remove both wet rags.

8. Refer to instructions provided with outdoor unit for leak

testing, evacuating and charging procedures.

9. Install access panel.

Table 2. Refrigerant Line Sizes

Model

Liquid

Line

Vapor

Line

Line Sets

−018
−024
−030

036

3/8"

(10mm)

3/4"

(19mm)

L15 line set sizes are depen-
dent on unit match−up. See
Engineering Handbook for
outdoor unit to determine cor-
rect line set sizes.

−042
−048

3/8"

(10mm)

7/8"

(22mm)

−060

3/8"

(10mm)

7/8"

(22mm)

Field-fabricated

Installing the Condensate Drain

IMPORTANT

After removal of drain pan plug(s), check drain hole(s) to
verify that drain opening is fully open and free of any
debris. Also check to make sure that no debris has fallen
into the drain pan during installation that may plug up the
drain opening.

MAIN DRAIN

Connect the main drain and route downward to drain line or
sump. Do not connect drain to a closed waste system. See
Figure 8 for typical drain trap configuration.

OVERFLOW DRAIN

It is recommended that the overflow drain is connected to a
overflow drain line for all units. If overflow drain is not
connected, it must be plugged with provided cap.
For downflow orientation, the overflow drain 

MUST 

be

connected and routed to a overflow drain line.

 

See Figure 8

for main and overflow drain locations based on coil
orientation.

LEFT−HAND AIR

DISCHARGE

MAIN DRAIN ON

RIGHT

OVERFLOW

DRAIN ON LEFT

UPFLOW OR
DOWNFLOW

RIGHT−HAND AIR

DISCHARGE

Figure 7. Main and Overflow Drain Locations based

on Coil Orientation

Summary of Contents for CBX27UH

Page 1: ...r reclaiming must be followed Fines and or incarceration may be levied for noncompliance INSTALLATION INSTRUCTIONS Elite Series CBX27UH Units MULTI POSITION AIR HANDLERS 506294 01 07 11 Supersedes 05...

Page 2: ...N LINE Return Air Opening SUPPLY AIR FILTER SUPPLY AIR TOP VIEW FRONT VIEW SIDE VIEW BLOWER A B C 11 1 16 281 F D E COIL 5 8 16 5 8 16 5 8 16 5 8 16 5 8 16 LOW VOLTAGE RIGHT SIDE LINE VOLTAGE LEFT SID...

Page 3: ...AND LEFT SIDE Horizontal Position Right Hand Air Discharge FILTER ACCESS FILTER ACCESS 5 3 4 146 1 1 2 38 1 3 4 44 CONDENSATE DRAINS 2 HORIZONTAL A 5 8 16 G H A 5 8 16 G 1 25 1 25 11 1 16 281 PIPING P...

Page 4: ...BLE REASSEMBLE AIR HANDLER UNITS The air handler units consists of two factory assembled sections It may be necessary to disassemble the sections when positioning the unit for installation To disassem...

Page 5: ...EW END VIEW ANGLE IRON OR SHEET METAL electrical inlet clearance 4 in 102 mm 1 2 in Screws Maximum Figure 3 Suspending Horizontal Unit IMPORTANT When removing the coil there is possible danger of equi...

Page 6: ...ccess door and replace it on the unit 13 Set unit so that it is sloped 1 4 toward the drain pan end of the unit Connect return and supply air plenums as required using sheet metal screws 14 If suspend...

Page 7: ...e both wet rags 8 Refer to instructions provided with outdoor unit for leak testing evacuating and charging procedures 9 Install access panel Table 2 Refrigerant Line Sizes Model Liquid Line Vapor Lin...

Page 8: ...TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING SECONDARY DRAIN PAN 2 51MM TRAP DEPTH LENNOX P TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 8 Typic...

Page 9: ...according to the job requirements 4 For best air performance external static pressure drop must not exceed 0 5 W C 1 2 kPa Refer to blower data tables for cfm and external static 5 Seal around the hol...

Page 10: ...213 1365 264 1485 325 30 815 101 970 136 1195 214 1310 265 1430 322 805 105 975 142 1210 219 1330 275 1445 337 40 750 106 915 148 1155 225 1275 273 1385 334 770 114 930 153 1170 231 1285 283 1405 345...

Page 11: ...to the low voltage terminal strip in the control section The speed can be increased by swapping wires as shown in figure 10 WIRING CONNECTIONS 1 Install line voltage power supply to unit from a prope...

Page 12: ...ND CONNECT YEL WIRE MOTOR SPEED TAPS 1 AND 2 Figure 10 Motor Speed Taps 208 230V Single Phase MOTOR SPEED TAPS 1 AND 2 TO INCREASE MOTOR SPEED DISCONNECT GRN WIRE AND CONNECT YEL WIRE Figure 11 Motor...

Page 13: ...Page 13 CBX27UH SERIES Figure 12 Typical System Wiring Diagram 208 230V Single and Three Phase...

Page 14: ...Page 14 506294 01 Figure 13 Typical System Wiring Diagram 460V Single and Three Phase 036 048 and 060 only...

Page 15: ...should be cut in an X pattern peeled open glued with an appropriate all purpose glue and placed back against the cabinet surface being careful to not overly compress the insulation so the insulation...

Reviews: