background image

Page 6

506294−01

4. Rotate drain pan 180º front-to-back and install it on the

opposite side of the coil.

5. Remove screws from top cap. Remove horizontal drip

shield screw located in the center of the back coil end
seal as illustrated in figure 4 on page 5.

6. Rotate horizontal drip shield 180º front to back.

7. Remove plastic plug from left hole on coil front end

seal and reinstall plug in back hole. Reinstall horizontal
drip shield screw in front coil end seal. Drip shield
should drain downward into horizontal drain pan inside
coil.

HORIZONTAL DRIP SHIELD (−060 MODEL)

DOWN−FLOW

RAIL

FRONT EDGE OF HORIZONTAL

DRAIN PAN

Figure 5. Left−Hand Discharge Configuration

8. Rotate top cap 180º front-to-back and align with

unused screw holes. Holes must align with front and
back coil end plates. The top cap has a 45º bend on
one side and a 90º bend on the other. 

The 90

º

 bend

must be on the same side as the horizontal drain
pan 

as illustrated in figure 4 on page 5.

NOTE − Be very careful when you reinstall the screws into
coil end plate engaging holes. Misaligned screws may
damage the coil.

9. From the up−flow position, flip cabinet 90º to the left

and set into place. Replace blower assembly. Secure
coil in place by bending down the tab on the cabinet
support rail as illustrated in figures 4 and 5.

10. Install the horizontal shield (−060 model) on the front

edge of the horizontal drain pan as illustrated in figure
5 on page 6.

NOTE − For horizontal applications in 

high humidity

areas

, remove the down−flow rail closest to the drain pan.

To remove rail, remove screw from rail at back of unit and
at cabinet support rail. Remove down−flow rail then replace
screws. Also, seal around the exiting drain pipe, liquid and
suction lines to prevent infiltration of humid air.

11. Knock out drain seal plate from access door. Secure

plate to cabinet front flange with screw provided.

12. Flip access door and replace it on the unit.

13. Set unit so that it is sloped 1/4" toward the drain pan

end of the unit. Connect return and supply air plenums
as required using sheet metal screws.

14. If suspending the unit, it must be supported along the

entire length of the cabinet. If using chain or strap, use
a piece of angle iron or sheet metal attached to the unit
(either above or below) so that the full length of the
cabinet is supported. Use securing screws no longer
than 1/2" to avoid damage to coil or filter. as illustrated
in figure 3 on page 5. Connect return and supply air
plenums as required using sheet metal screws.

DOWN−FLOW APPLICATION

NOTE − If down−flow application is required, separately
order kit number 83M57 and install per kit’s instructions.
Also use metal or class I supply and return air plenums.

Use the installation instruction provided with the downflow
kit.

IMPORTANT

If electric heat section with circuit breakers
(ECB29/ECB31) is applied to down−flow and CBX27UH
units, the circuit breakers must be rotated 180° to the UP
position. See ECB29/ECB31 installation instructions for
more details.

Brazing Connections

IMPORTANT

To prevent the build up of high levels of nitrogen when
purging, be sure it is done in a well ventilated area. Purge
low pressure nitrogen (1 to 2 psig) through the refrigerant
piping during brazing. This will help to prevent oxidation
and the introduction of moisture into a system.

All coils are equipped with a factory−installed, internally
mounted check/expansion valve.
The air handler’s coil line sizes are listed in table 2. Use
Lennox L15 (sweat) series line sets (refer to the outdoor
unit Engineering Handbook for proper size, type and
application). For field−fabricated refrigerant lines, see the
piping section of the Lennox Unit Information Service
Manual.

WARNING

Danger of explosion!

Can cause equipment damage, injury, or
death.

When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator
that can control the pressure down to 1 or
2 psig (6.9 to 13.8 kPa).

Summary of Contents for CBX27UH

Page 1: ...r reclaiming must be followed Fines and or incarceration may be levied for noncompliance INSTALLATION INSTRUCTIONS Elite Series CBX27UH Units MULTI POSITION AIR HANDLERS 506294 01 07 11 Supersedes 05...

Page 2: ...N LINE Return Air Opening SUPPLY AIR FILTER SUPPLY AIR TOP VIEW FRONT VIEW SIDE VIEW BLOWER A B C 11 1 16 281 F D E COIL 5 8 16 5 8 16 5 8 16 5 8 16 5 8 16 LOW VOLTAGE RIGHT SIDE LINE VOLTAGE LEFT SID...

Page 3: ...AND LEFT SIDE Horizontal Position Right Hand Air Discharge FILTER ACCESS FILTER ACCESS 5 3 4 146 1 1 2 38 1 3 4 44 CONDENSATE DRAINS 2 HORIZONTAL A 5 8 16 G H A 5 8 16 G 1 25 1 25 11 1 16 281 PIPING P...

Page 4: ...BLE REASSEMBLE AIR HANDLER UNITS The air handler units consists of two factory assembled sections It may be necessary to disassemble the sections when positioning the unit for installation To disassem...

Page 5: ...EW END VIEW ANGLE IRON OR SHEET METAL electrical inlet clearance 4 in 102 mm 1 2 in Screws Maximum Figure 3 Suspending Horizontal Unit IMPORTANT When removing the coil there is possible danger of equi...

Page 6: ...ccess door and replace it on the unit 13 Set unit so that it is sloped 1 4 toward the drain pan end of the unit Connect return and supply air plenums as required using sheet metal screws 14 If suspend...

Page 7: ...e both wet rags 8 Refer to instructions provided with outdoor unit for leak testing evacuating and charging procedures 9 Install access panel Table 2 Refrigerant Line Sizes Model Liquid Line Vapor Lin...

Page 8: ...TWO PART DESIGN FOR USE WHERE OBSTRUCTIONS PREVENT DIRECT THREADING SECONDARY DRAIN PAN 2 51MM TRAP DEPTH LENNOX P TRAP 49P66 REQUIRES A LARGER INSTALLATION SPACE THAN THE J TRAP 91P90 Figure 8 Typic...

Page 9: ...according to the job requirements 4 For best air performance external static pressure drop must not exceed 0 5 W C 1 2 kPa Refer to blower data tables for cfm and external static 5 Seal around the hol...

Page 10: ...213 1365 264 1485 325 30 815 101 970 136 1195 214 1310 265 1430 322 805 105 975 142 1210 219 1330 275 1445 337 40 750 106 915 148 1155 225 1275 273 1385 334 770 114 930 153 1170 231 1285 283 1405 345...

Page 11: ...to the low voltage terminal strip in the control section The speed can be increased by swapping wires as shown in figure 10 WIRING CONNECTIONS 1 Install line voltage power supply to unit from a prope...

Page 12: ...ND CONNECT YEL WIRE MOTOR SPEED TAPS 1 AND 2 Figure 10 Motor Speed Taps 208 230V Single Phase MOTOR SPEED TAPS 1 AND 2 TO INCREASE MOTOR SPEED DISCONNECT GRN WIRE AND CONNECT YEL WIRE Figure 11 Motor...

Page 13: ...Page 13 CBX27UH SERIES Figure 12 Typical System Wiring Diagram 208 230V Single and Three Phase...

Page 14: ...Page 14 506294 01 Figure 13 Typical System Wiring Diagram 460V Single and Three Phase 036 048 and 060 only...

Page 15: ...should be cut in an X pattern peeled open glued with an appropriate all purpose glue and placed back against the cabinet surface being careful to not overly compress the insulation so the insulation...

Reviews: