background image

Page 7

CB(X)26UH SERIES

The coil has a fixed orifice in the liquid line (see figure 9).
Remove the rubber plug from the vapor line of the coil.

STRAINER

LIQUID LINE STUB

DISTRIBUTOR

O−RING

FIXED ORIFICE

Figure 9. Metering Device Installation

Condensate Drain

IMPORTANT

On units of this type, where the blower draws" rather
than blows" air through the coil, traps must be installed
in the condensate drain lines (primary and auxiliary, if
used). Traps prevent the blower from drawing air through
the drain lines into the air supply.

IMPORTANT

A field−fabricated secondary drain pan, with a drain pipe
to the outside of the building, is required in all installations
over a finished living space or in any area that may be
damaged by overflow from the main drain pan. In some
localities, local codes may require an secondary drain
pan for any horizontal installation.

The air handler is provided with ¾" NPT condensate drain
connections.

SLOPING THE DRAIN

Make sure the unit is sloped (similar to the slope shown in
figure 10) so that the drain pan will empty completely
without water standing in the pan.

THIS CORNER SHOULD BE 
5/8" (+/− 1/8") HIGHER THAN DRAIN CORNER

DRAIN CORNER

THIS CORNER SHOULD BE 
5/8" (+/− 1/8") HIGHER THAN
DRAIN CORNER

Figure 10. Sloping the Drain

INSTALL CONDENSATE DRAIN

1. Remove the appropriate drain knockouts. If

necessary, remove the indoor coil assembly from the
cabinet.

2. Connect primary drain line connection to the primary

drain pan connection. The primary drain connection is
flush with the bottom of the inside of the pan.
Secondary connection is raised above the bottom of
the inside of the pan.

NOTE  When making drain fitting connections to the
drain pan, hand tighten the fitting and use a sealant.
Over−tightening the fittings can split connections on the
drain pan.

3. If the auxiliary drain line is to be used, remove the plug

and route the drain line so that water draining from the
outlet will be easily noticed by the homeowner.

4. After removal of drain pan plugs, check the drain port

to see if holes have been drilled. If not drilled, use a
19/32" bit to drill out the primary drain hole; use a 3/8"
drill bit for the secondary drain hole. Remove all drill
shavings.

5. Make sure drain ports and drain pan are free of all

debris.

6. Plug and check any unused drain pan openings for

tightness. Torque plugs to 30 in. lb. to prevent water
leaks or seepage from the drain pan.

7. Install a 2" trap in the primary drain lines as close to the

unit as practical (see figure 11). Make sure the top of
the trap is below the connection to the drain pan to
allow complete drainage of the pan.

NOTE  Horizontal runs must have an anti−siphon air vent
(standpipe) installed ahead of the horizontal run (See
figure 11). An extremely long horizontal run may require an
oversized drain line to eliminate air trapping.

NOTE  Do not operate air handler without a drain trap.
The condensate drain is on the negative pressure side of
the blower; therefore, air being pulled through the
condensate line will prevent positive drainage without a
proper trap.

8. Route the drain line to the outside or to an appropriate

drain. Drain lines must be installed so they do not block
service access to the front of the air handler. A 24"
clearance is required for filter, coil, or blower removal
and service access.

NOTE  Check local codes before connecting the drain
line to an existing drainage system.

Insulate the drain lines where sweating could cause water
damage.

Summary of Contents for CB26UH series

Page 1: ... Unit Dimensions 2 CB X 26UH Series Units 3 Requirements 3 Installation Clearances 4 Installation 4 Condensate Drain 7 Duct System and Filters 8 Connecting Refrigerant Lines 9 Sealing the Unit 9 Electrical Connections 9 Airflow Cooling Blower Speed 12 Check Out Procedures 15 Operation 15 Maintenance 16 Accessories 16 Cabinet Insulation 16 Shipping and Packing List Package 1 of 1 contains the follo...

Page 2: ... for Upflow and LH RH Horizontal Air Discharge Applications Dimension 018 024 030 036 037 042 048 060 inches mm inches mm inches mm inches mm A 46 3 4 1187 51 1295 54 1372 60 1524 B 18 1 2 470 21 1 4 540 21 1 4 540 21 1 4 540 C 22 559 22 559 26 660 26 660 D 11 279 12 1 2 318 12 305 11 3 4 298 E 16 406 18 1 2 470 16 3 4 425 17 432 F 5 1 2 140 6 152 4 102 4 102 G 13 1 2 343 16 406 16 406 16 406 H 19...

Page 3: ...pe Warm Air Heating and Air Conditioning Systems NFPA No 90B IMPORTANT The CB X 26UH units are designed to match and must be used with outdoor units as rated The indoor sections are manufactured with a check expansion valve TXV or refrigerant flow control RFC device to provide opti mum refrigerant control and system performance with a variety of different capacities of outdoor units TXV units In s...

Page 4: ... free flow of return air Installation GENERAL INFORMATION WARNING Improper installation adjustment alteration service or maintenance can cause property damage personal inju ry or loss of life Installation and service must be per formed by a qualified installer or service agency CB X 26UH units are factory assembled and configured for installation in upflow or horizontal left hand air discharge app...

Page 5: ... cabinet integrity Ensure that there is adequate room to remove service and access panels if installing in the horizontal position 1 Determine whether left hand or right hand air discharge is required If right hand is required perform Right Hand Discharge Modification on page 6 2 Determine knockouts required for drain line connections 3 With access door removed knock out drain line opening for ins...

Page 6: ...OW OFF PREVENTION BRACKET S AND DRIP SHIELD FROM HERE THEN REINSTALL PAN HERE REINSTALL BRACKET HERE NOTE EXPANSION VALVE SHOWN ON COIL IS NOT ON CB26UH R RFC EQUIPPED UNITS Figure 7 Field Modification for Right Hand Discharge OPEN END FOR CONDENSATION DRAIN COIL ASSEMBLY PLUGGED END Figure 8 Right Hand Drain Plug Location REFRIGERANT METERING DEVICE NOTE See the outdoor unit installation instruct...

Page 7: ... making drain fitting connections to the drain pan hand tighten the fitting and use a sealant Over tightening the fittings can split connections on the drain pan 3 If the auxiliary drain line is to be used remove the plug and route the drain line so that water draining from the outlet will be easily noticed by the homeowner 4 After removal of drain pan plugs check the drain port to see if holes ha...

Page 8: ... DRAIN Test the drain pan and drain line after installation 1 Pour several quarts of water into drain pan enough to fill drain trap and line 2 Check to make sure the drain pan is draining completely no leaks are found in drain line fittings and water is draining from the end of the primary drain line 3 Correct any leaks found Duct System and Filters DUCT SYSTEM The air handler is provided with fla...

Page 9: ...s This is especially important when the unit is installed in an unconditioned area WARNING There must be an airtight seal between the bottom of the air handler and the return air plenum Use fiberglass sealing strips caulking or equivalent sealing method between the plenum and the air handler cabinet to ensure a tight seal Return air must not be drawn from a room where this air handler or any gas f...

Page 10: ... ground terminal marked GND Failure to do so can result in death or elec trical shock 4 Use UL listed wire nuts to connect the field supply conductors to the unit black and yellow leads and the ground wire to ground terminal marked GND 5 Replace the air handler access panel GND CONNECT BLACK TO BLACK CONNECT UNIT S YELLOW CONDUC TOR TO WHITE FIELD SUPPLY CONDUCTOR CONNECT GROUND WIRE TO GROUND TER...

Page 11: ...Page 11 CB X 26UH SERIES WARNING USE COPPER CONDUCTORS ONLY Figure 13 Wiring Diagram ...

Page 12: ...NGE BLOWER SPEED NOTE Refer to wiring diagram figure 13 and blower performance table 4 WARNING Electric shock hazard Disconnect all power supplies before servicing Replace all parts and panels before op erating Failure to do so can result in death or elec trical shock 1 Disconnect all power supplies 2 Remove the air handler access panel 3 Locate pin number 2 on the blower relay Two black wires are...

Page 13: ...75 365 036 LOW SPEED 10 25 1560 705 1405 635 20 50 1480 670 1340 610 30 75 1390 630 1270 575 40 100 1290 585 1185 540 50 125 1170 530 1090 495 60 150 1015 480 975 460 037 LOW SPEED 10 25 1570 740 1330 625 20 50 1520 715 1310 620 30 75 1440 680 1250 590 40 100 1300 615 1180 555 50 125 1170 550 1070 505 60 150 950 450 840 395 042 MEDIUM SPEED 10 25 1940 880 1785 810 20 50 1845 835 1705 775 30 75 174...

Page 14: ...8 0 40 100 813 384 963 454 1121 529 0 50 125 721 340 886 418 1033 487 0 60 150 036 LOW SPEED 0 10 25 1135 536 1354 639 1494 705 0 20 50 1120 529 1345 635 1469 693 0 30 75 1112 525 1317 621 1417 669 0 40 100 1079 509 1260 595 1336 630 0 50 125 995 470 1090 514 1250 590 0 60 150 042 MEDIUM SPEED 0 10 25 1202 567 1404 663 1540 727 0 20 50 1192 563 1413 667 1530 722 0 30 75 1160 547 1386 654 1507 711 ...

Page 15: ...mperature The indoor blower and auxiliary heat should come on together Allow a minimum of 3 minutes for all sequencers to cycle on S Set the thermostat so that it does not call for heat Allow up to 5 minutes for all sequencers to cycle off Operation COOLING COOLING ONLY OR HEAT PUMP When the thermostat calls for cooling 24 volts is put on the blower time delay relay coil After a delay the indoor b...

Page 16: ...y drain line a problem exists which should be investigated and corrected Contact a qualified service technician Cabinet Insulation IMPORTANT DAMAGED INSULATION MUST BE REPAIRED OR REPLACED before the unit is put back into operation In sulation loses its insulating value when wet damaged separated or torn Matt or foil faced insulation is installed in indoor equipment to provide a barrier between ou...

Reviews: