Page 6
505059M 0511
7. Install the coil support bracket on the opposite side of
the air handler (figure 7, detail B).
RIGHT-HAND DRAINS
KNOCKOUT
Drains
AIR FLOW
Figure 6. Right-Hand Discharge Configuration
Table 2. Blow Off Prevention Bracket
Model
Front
Rear
−018
None
None
−024
None
None
−030
Yes
Yes
−036
Yes
Yes
−037
None
None
−042
None
None
−048*
Yes
None
−060
Yes
None
* −048 model supported in TXV units only.
REMOVE DRAIN PAN FROM HERE
THEN...
DETAIL A
BRACKET SHOWN AS SHIPPED
BRACKET SHOWN FOR RIGHT HAND DISCHARGE
DETAIL B
REMOVE COIL SUPPORT BRACKET FROM HERE
THEN...
ROTATE SHIELD AND BRACKET AND REINSTALL
REMOVE 2 SCREWS, BLOW OFF PREVENTION
BRACKET(S), AND DRIP SHIELD FROM HERE
THEN...
REINSTALL PAN HERE
REINSTALL BRACKET HERE
NOTE − EXPANSION VALVE SHOWN ON
COIL IS NOT ON CB26UH−R (RFC)
EQUIPPED UNITS.
Figure 7. Field Modification for Right−Hand Discharge
OPEN END FOR CONDENSATION
DRAIN
COIL ASSEMBL
Y
PLUGGED
END
Figure 8. Right-Hand Drain Plug Location
REFRIGERANT METERING DEVICE
NOTE See the outdoor unit installation instructions and
the Lennox Engineering Handbook for approved fixed
orifice match−ups and application information.
CB26UH−R units are equipped with a factory−installed
refrigerant flow control (RFC) device (see table 1 on
Page 3).
IMPORTANT
If a unit equipped with an RFC device is used in an ap-
plication which requires conversion to an expansion
valve, the fixed orifice must be removed before the ex-
pansion valve is installed.