Lennox B050A3B Installation/Servicing Instructions And Users Information Manual Download Page 16

Page  16  of  36

506307-01

Issue 1207

THEORY OF OPERATION

Here’s How Your System Works:

Call For Heat

The thermostat calls for heat by energizing the “W”

terminal.  The control checks to see the limit switch is closed
and pressure switch is open.  If the limit switch is open, the
control responds per the Open Limit section following.  If
the pressure switch is closed, the control will flash “3” on
the LED and wait indefinitely for the pressure switch to open.
If the pressure switch is open, the control proceeds to pre-
purge.

Pre-Purge

The control energizes the induced draft motor and waits

for the pressure switch to close.  The control flashes “3” on
the LED while the pressure switch is open.  If the pressure
switch does not close within 60 seconds of the inducer
energizing, the control will de-energize the inducer for 300
seconds, and then re-energized the inducer.  This cycle shall
continue as long as a call for heat exists until the pressure
switch is proven.

When the pressure switch is proven closed, the control

begins the pre-purge time.  If flame is present any time while
in pre-purge, the control will flash “5” on the LED and go into
soft lockout.  The control runs the inducer for a 15 second
pre-purge time, then proceeds to the ignition trial period.

Ignition Trial Period

The control energizes the spark and main gas valve.

The inducer remains energized.  If flame has not been
sensed within the 7 second ignition trial, the control de-
energizes the gas and spark outputs and proceeds with
ignition retires.  If flame is not established after three (3)
trials for ignition, the control will flash “2” on the LED and
goes into lockout.

Blower On Delay

The control waits for 30 seconds from the time the gas

valve opened and then energizes the indoor blower heat
speed.  The gas valve and inducer remain energized.  The
control proceeds to steady heat mode.

Steady Heat

Control inputs are continuously monitored to ensure limit

and pressure switches are closed, flame is established, and
the thermostat call for heat remains.  When the thermostat
call for heat is removed, the control de-energizes the gas
valve and begins post-purge and blower off delay time.

Open Limit

Any time the limit switch is open, the control de-energizes

the gas valve and runs the indoor blower motor on heat
speed, and runs the induced draft motor.  While the limit
switch is open, the control flashes “4” on the LED.  Check
for a restriction in the duct system (i.e. dirty filters, blocked
ductwork, closed registers . . . . . . ).

When the switch re-closes, the control runs the induced

draft motor through post-purge and runs the indoor blower
through the selected fan off delay.  If the call for heat is still
present when the limit switch closes, the control will begin
an ignition sequence while the blower off delay continues.

NOTE:

  An open limit switch breaks the power (“R”) to the

thermostat.  Cycling on the limit is an abnormal condition
and a corrective action must be taken.  Failure to correct
this condition could damage the heat exchangers and void
the warranty.

Post Purge

The inducer output remains on for a 15 second post-

purge period after the thermostat is satisfied.

Blower Off Delay

The indoor blower motor is de-energized after a 90

second blower off delay.  Blower timing begins when the
thermostat is satisfied.  If the thermostat calls for heat while
in the blower off delay, the control immediately restarts the
ignition sequence while the blower off delay continues.

Should overheating occur, or the gas supply fail to shut
OFF, turn OFF the manual gas valve to the appliance
BEFORE turning OFF the electrical supply.  A failure to
adhere to this warning can result in a fire or explosion
and bodily harm.

  

WARNING

For cooling operation, when the inside temperature

exceeds the thermostat setting, the thermostat will turn ON
the cooling system.

When the thermostat calls for cooling, power from the

transformer energizes the fan control board (for blower
operation) and the outdoor condensing unit (for air
conditioning).

The fan control board will automatically turn on the

blower and condensing unit.  The air moving over the indoor
coil by the blower is cooled (and dehumidified) and passes
through the ducts to the room registers.

When the thermostat is satisfied, the fan control board

is de-energized and the condensing unit is shut-off.  The
blower will continue to operate for an additional 30 seconds
for added cooling efficiency.

Summary of Contents for B050A3B

Page 1: ...est Columbia SC 29170 SECTION 1 INSTALLATION AND SERVICING INSTRUCTIONS 1 28 Important Safety Information 2 Specification and Installation 3 Start up and Operation 17 Maintenance 21 Sequence of Operat...

Page 2: ...e instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system whichhasanexternalstaticpressurewithintheallowable range as specified in Temp...

Page 3: ...506307 01 Page 3 of 36 Issue 1207...

Page 4: ...al injury due to electrical shock or uncontrolled gas leakage WARNING When operating the furnace in the heating mode the static pressure and the temperature rise supply air temperature minus return ai...

Page 5: ...506307 01 Page 5 of 36 Issue 1207 FURNACE WIRING SPECIFICATIONS...

Page 6: ...ult the U S National Fuel Gas Code obtainable from the National Fire Protection Association Inc Batterymarch Park Quincy MA 02269 or the American Gas Association 1515 Wilson Boulevard Arlington VA 222...

Page 7: ...e straps around each end of the furnace These straps should be attached to the furnace with sheet metal screws and to the rafters with bolts The furnace may also be suspended by using an angle iron fr...

Page 8: ...o air needed for combustion ventilation in the form of process air must be provided as required for cooling of eqipment or material controlling dew point heating drying oxidation or dilution safety ex...

Page 9: ...ons should be followed when installing the ductwork 1 Install locking type dampers in all branches of the individual ducts to balance out the system Dampers should be adjusted to impose the proper sta...

Page 10: ...ction BTU INPUT FILTER SIZE 50 000 75 000 100 000 125 000 13 X 23 13 X 23 16 1 2 X 26 20 X 23 Table 2 VENTING Venting for the furnace must be to the outside and in accordance with local codes or requi...

Page 11: ...ace must not be vented into a chimney serving a separate appliance designed to burn solid fuel Type II B vent connectors must be used on all installations and it must be sized per the applicable secti...

Page 12: ...t ANSI Z223 1 NFPA 54 National Fuel Gas Code A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwellings and serves both dwellings Permit...

Page 13: ...ing system being placed into operation while all other appliances connected to the common venting system are not in operation 1 Seal any unused openings in the venting system 2 Inspect the venting sys...

Page 14: ...223 1 NFPA54 and or CSA B149 1 Natural Gas and Propane Installation Codes If local codes allow the use of a flexible gas appliance connector always use a new listed connector Do not use a connector wh...

Page 15: ...tap in order to test incoming gas pressure and outgoing manifold pressure See Figure 9 FIELD SUPPLIED MAIN MANUAL SHUT OFF VALVE GAS SUPPLY DRIP LEG F0000317 Many soaps used for leak testing are corr...

Page 16: ...valve and begins post purge and blower off delay time Open Limit Any time the limit switch is open the control de energizes the gas valve and runs the indoor blower motor on heat speed and runs the i...

Page 17: ...position 5 Set the thermostat above room temperaturae 6 The ignitior will spark and the main burners will ignite Do not attempt to manually light the burners Failure to follow this warning can lead to...

Page 18: ...If the heating value of the natural gas is 1015 Btu cu and it takes 60 seconds to burn 2 cu ft of gas then Input 1015 Btu cu ft x 1 rev x 2 cu ft rev x 3600 60 sec Input 121 8000 btu hr Burner Orific...

Page 19: ...Prior to any blower adjustment electrical service must be turned OFF This furnace is equipped with a 3 speed direct drive motor to deliver a temperature rise within the range specificed on the rating...

Page 20: ...vent from the combustion blower Place the furnace into operation Gradually cover up the blower outlet the main burners should shut OFF Remvoe the restriction and the unit should relight Replace the v...

Page 21: ...be necessary to use a soft bristly brush to remove dirt and then vacuum 3 Remove the burner opening inlet plate This will expose the burner openings of the primary heat exchangers 4 Vacuum the length...

Page 22: ...nd continue sliding the blower forward until it is out of the unit Replacement 1 Place the blower in the blower opening of the unit and slide the blower back into the unit taking care to clear the top...

Page 23: ...506307 01 Page 23 of 36 Issue 1207 SEQUENCE OF OPERATION DIRECT IGNITION SYSTEM CONTROL...

Page 24: ...till present Combustion blower energized The heat speed circulation air fan will be energized after the selected heat fan on delay System waits for flame signal to disappear then goes to Soft Lockout...

Page 25: ...506307 01 Page 25 of 36 Issue 1207 WIRING DIAGRAM f0000321...

Page 26: ...sion can not be met at the time of completion of installaiton the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day peri...

Page 27: ...ollowing requirements shall be satisfied by the manufacturer 1 The identification of each special venting system shall include the listing of either the website phone number or manufacturer s address...

Page 28: ...Page 28 of 36 506307 01 Issue 1207 NOTES...

Page 29: ...eep you warm and comfortable during the winter months It will deliver superb performance with only minimal help from you To keep your operating costs low and to eliminate unnecessary service calls we...

Page 30: ...e to the furnace before shutting off the electrical supply 6 Do not use the furnace if any part has been under water A flood damaged furnace is extremely dangerous Attempts to use the furnace can resu...

Page 31: ...fan switch on the thermostat permits you to do this see Figure M 2 on page 32 With the switch in the ON position the fan will operate continuously AUTO position gives fan operation only when the unit...

Page 32: ...ashlight will be useful for these inspections Make one inspection prior to the beginning of the heating season and another during the middle Should you observe unusual amounts of any of the following...

Page 33: ...r washing Cleanable filters may be replaced with disposable filters Refer to Table 1 on page 33 when selecting the proper size and quantity of disposable filter If your air distribution system has a c...

Page 34: ...urnace still does not operate call your dealer for service Lubrication Lubrication of the bearings in the circulating air blower motor and the combustion blower motor is not recommended Burner Flame W...

Page 35: ..._______________ Serial _________________________ Installation Date ____________ Equipment Type ______________________________________ Model _________________________________ Serial ___________________...

Page 36: ...AFFIX THIS INSTRUCTION PACKET ADJACENT TO THE FURNACE HOMEOWNER RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE INSTRUCTIONS D ENTRETIEN ET INSTALLATION ET MANUAL DE L USAGER INSTALLATEUR PLACEZ LA POC...

Reviews: