ARIA EC-AGU-0909-E
Page 10
ARIA EC –
Size 40
Spectrum per octave band (Hz)
Control
voltage
Volts
Airflow
(m3/h)
125 250 500 1000 2000 4000 8000 Global
(dBA)
Total
(dBA)
Supply
44 45 43 36 31 23 10
43
Return
45 39 45 38 30 22 19
44
2 180
Radiated
39 32 40 36 34 31 25
41
48
Supply
46 38 46 42 35 26 20
46
Return
48 42 48 37 28 28 24
46
4 400
Radiated
43 38 41 45 42 35 28
48
52
Supply
52 54 52 46 42 35 24
52
Return
55 49 55 42 37 36 29
53
6 620
Radiated
46 41 45 48 35 28 31
50
57
Supply
53 55 54 47 44 38 28
54
Return
57 52 57 44 41 40 35
55
8 850
Radiated
48 46 49 52 41 34 27
54
59
Supply
62 62 55 48 46 44 37
58
Return
67 61 58 45 44 47 44
59
10 910
Radiated
55 53 49 52 41 40 35
54
62