ARIA EC-AGU-0909-E
Page 9
Acoustic data
Sound power to an available static pressure of 40 Pa
ARIA EC –
Size 10 & 20
Spectrum per octave band (Hz)
Control
voltage
Volts
Airflow
(m
3
/h)
125 250 500 1000 2000 4000 8000 global
dBA
Lw Total
(dBA)
Supply
44 46 44 39 32 23 -
45
Return
46 40 46 40 28 21 -
45
2 100
Radiated
39 33 40 37 34 32 23
42
49
Supply
45 46 44 40 33 24 -
45
Return
47 40 47 41 29 22 -
46
4 160
Radiated
39 33 40 37 35 33 24
43
49
Supply
44 39 47 42 36 27 21
47
Return
50 44 50 39 30 25 20
48
6 265
Radiated
44 38 42 45 43 40 27
49
53
Supply
49 52 50 44 41 35 25
51
Return
55 51 55 42 40 38 34
53
8 385
Radiated
44 42 45 48 37 30 23
50
56
Supply
59 59 51 45 42 41 33
54
Return
66 59 57 44 43 46 43
58
10 445
Radiated
52 49 45 48 38 36 31
50
60
ARIA EC –
Size 30
Spectrum per octave band (Hz)
Control
voltage
Volts
Airflow
(m
3
/h)
125 250 500 1000 2000 4000 8000 Global
(dBA)
Total
(dBA)
Supply
58 53 50 42 35 22 -1
50
Return
58
55
47
39
27
18
-1
49
2 130
Radiated
53
48
42
38
31
22
-1
44
53
Supply
67 62 59 51 46 36 27
59
Return
68
65
57
49
38
32
25
59
4 250
Radiated
62
57
51
47
42
36
31
53
63
Supply
56 58 56 51 46 39 29
57
Return
58
52
58
45
40
39
32
56
6 500
Radiated
48
43
47
51
37
30
29
52
60
Supply
58 60 59 53 50 44 34
60
Return
60
56
60
47
45
43
39
58
8 680
Radiated
50
49
51
55
43
36
29
56
63
Supply
68 68 60 54 51 49 42
63
Return
70
64
61
49
48
50
48
62
10 800
Radiated
59
56
52
55
44
43
38
57
66
Summary of Contents for ARIA EC 10
Page 1: ...Providing indoor climate comfort ARIA EC Application guide ARIA EC AGU 0909 E ...
Page 2: ......
Page 34: ...ARIA EC AGU 0909 E Page 32 ARIA EC 20 with 4 row coil Left hand configuration ...
Page 35: ...ARIA EC AGU 0909 E Page 33 ARIA EC 30 with 4 row coil Left hand configuration ...
Page 36: ...ARIA EC AGU 0909 E Page 34 ARIA EC 40 with 4 row coil Left hand configuration ...