background image

506468-01

Page 19 of 24

Issue  1946

System Diagnostic Module

4HP16LT  units contain a diagnostic module for 

troubleshooting heat pump system failures. By monitoring 

and analyzing data from the compressor and thermostat 

demand, the module can accurately detect the cause of 

electrical and system related failure without any sensors. 

If  a  system  problem  occurs,  a  flashing  LED  indicator 

communicates the failure code.

LED Description

POWER LED (Green) indicates voltage is present at the 

power connection of the module.

ALERT LED (Yellow) communicates an abnormal system 

condition  through  a  unique  flash  code. The ALERT  LED 

will flash a number of times consecutively, pause, and then 

repeat  the  process.  The  number  of  consecutive  flashes 

correlates to a particular abnormal condition.

TRIP LED (Red) indicates there is a demand signal 

from the thermostat but no current to the compressor is 

detected by the module. The TRIP LED typically indicates 

the compressor protector is open or may indicate missing 

supply power to the compressor.

Interpreting the Diagnostic LEDs

When an abnormal system condition occurs, the 

diagnostic module displays the appropriate ALERT and/or 

TRIP LED. The yellow ALERT LED will flash a number of 

times consecutively, pause, and then repeat the process. 

To  identify  a  flash  code  number,  count  the  number  of 

consecutive  flashes.  Refer  to  Table  7  for  information  on 

the flash codes.

Every time the module powers up, the last ALERT LED 

flash  code  that  occurred  prior  to  shutdown  is  displayed 

for 60 seconds. The module will continue to display the 

previous  flash  code  until  the  condition  returns  to  normal 

or 24VAC is removed from the module. TRIP and ALERT 

LEDs  flashing  at  the  same  time  means  control  circuit 

voltage is too low for operation.

24VAC Power Wiring

The diagnostic module requires a constant nominal 24VAC 

power supply. The wiring to the module’s R and C terminals 

must be directly from the indoor unit or thermostat. The 

module cannot be powered by R and C terminals on the 

control board without experiencing nuisance alerts.

Thermostat Wiring

The diagnostic module requires a thermostat demand 

signal to operate properly. See Figure 6 for connections. 

The thermostat signal input is 24VAC and should not be  

less than 0.5VAC.

Mis-wired Module Codes

Depending  on  the  system  configuration,  some  ALERT 

flash  codes  may  not  be  active.  The  presence  of  safety 

switches  affects  how  the  system  alerts  are  displayed  by 

the module. Mis-wiring the diagnostic module will cause 

false LED codes. Table 8 describes LED operation when 

the module is mis-wired and what troubleshooting action is 

required to correct the problem.

LED Status

Fault Description

Troubleshooting Information

POWER

 

(Green)

Module has power

Supply voltage is present at module terminals

TRIP 

(Red)

Thermostat demand signal Y1 is 

present, but the compressor is not 

running

1.  Compressor protector is open

•  Check for high head pressure

•  Check compressor supply voltage

2.  Outdoor unit power disconnect is open

3.  Compressor circuit breaker or fuse(s) is open

4.  Broken wire or connector is not making contact

5.  Low pressure switch open if present in system

6.  Compressor contactor has failed open

ALERT

 

(Yellow) 

Flash Code 1

Long Run Time

 

Compressor is running extremely long 

run cycles 

(Not applicable on heat pump models)

--

ALERT

 

(Yellow) 

Flash Code 2

System Pressure Trip

 

Discharge or suction pressure out of 

limits or compressor overloaded

1.  High head pressure

•  Check high pressure switch if present in system

•  Check if system is overcharged with refrigerant

•  Check for non-condensable in system

2.  Condenser coil poor air circulation (dirty, blocked, damaged)

3.  Condenser fan is not running

•  Check fan capacitor

•  Check fan wiring and connectors

•  Check fan motor for failure or blockage

4.  Return air duct has substantial leakage

5.  If low pressure switch present in system, check Flash Code 1 information

ALERT

 

(Yellow) 

Flash Code 3

Short Cycling

 

Compressor is running only briefly

1.  Thermostat demand signal is intermittent

2.  Time delay relay or control board defective

3.  If high pressure switch present, go to Flash Code 2 information

4.  If low pressure switch present, go to Flash Code 1 information

Table 7. Diagnostic Module Codes

Summary of Contents for Allied Air Enterprises BHP16L

Page 1: ...l as well as the instructions supplied in separate equipment before starting the installation Observe and follow all warnings cautions instructional labels and tags Failure to comply with these instru...

Page 2: ...when lifting avoid contact with sharp edges Installation NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment Locate unit away from wi...

Page 3: ...cted by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and...

Page 4: ...Size 12 ft 25 ft 50 ft 75 ft 100 ft 24 000 3 4 7 8 3 4 7 8 7 8 36 000 7 8 7 8 7 8 7 8 1 1 8 48 000 7 8 7 8 7 8 1 1 8 1 1 8 60 000 1 1 8 1 1 8 1 1 8 1 1 8 1 1 8 For lines longer than 50 ft refer to lo...

Page 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Page 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Page 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Page 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Page 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Page 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Page 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Page 12: ...ring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a proper conduit fitting Un...

Page 13: ...e 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adju...

Page 14: ...he compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the control board will cycle off the compressor and the strike counter in the board will count one strike...

Page 15: ...rost mode Units are shipped with jumper installed on DELAY pins NOTE The 30 second compressor delay feature known as the quiet shift must be deactivated during any unit performance testing The feature...

Page 16: ...e will be initiated after 30 minutes of heating mode compressor run time The control will attempt to self calibrate after this and all other defrost cycle s Calibration success depends on stable syste...

Page 17: ...n system 3 Improper metering device installed or incorrect operation of metering device 4 Incorrect or improper sensor location or connection to system 1 Remove any blockages or restrictions from coil...

Page 18: ...Page 18 of 24 506468 01 Issue 1946 24V No 24V...

Page 19: ...he control board without experiencing nuisance alerts Thermostat Wiring The diagnostic module requires a thermostat demand signal to operate properly See Figure 6 for connections The thermostat signal...

Page 20: ...mer is overloaded 2 Low line voltage contact utility if voltage at disconnect is low Check wiring conditions Table 7 Diagnostic Module Codes Mis wired Module Troubleshooting Mis wired Module Indicatio...

Page 21: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Page 22: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Page 23: ...506468 01 Page 23 of 24 Issue 1946 Figure 9 Two Stage Wiring Diagram 24 36 48 Models Only...

Page 24: ...Page 24 of 24 506468 01 Issue 1946 Figure 10 Two Stage Wiring Diagram 60 Model Only...

Reviews: