506550-01
Page 25 of 66
Issue 1230
Gas Piping
1.
Gas piping may be routed into the unit through either
the left or right hand side in upflow applications, and
either the top or bottom in horizontal applications. Supply
piping enters into the gas valve from the side of the valve
as shown in Figures 36 and 37.
2.
When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be
considered to avoid excessive pressure drop. Table 7
list recommended pipe sizes for typical applications.
NOTE:
Use two wrenches when connecting gas piping
to avoid transferring torque to the manifold.
3.
Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or elevator
shafts. Center gas line through piping hole. Gas line
should not touch side of unit. See Figures 36 and 37.
4.
Piping should be sloped 1/4 “ per 15 feet (6 mm per 5.6
m) upward toward the gas meter from the furnace. The
piping must be supported at proper intervals, every 8 to
10 feet (2.44 to 3.05 m), using suitable hangers or straps.
Install a drip leg in vertical pipe runs to serve as a trap
for sediment or condensate.
5.
A 1/8” N.P.T. plugged tap or pressure post is located on
the gas valve to facilitate test gauge connection. See
Figure 42.
If a flexible gas connector is required or allowed by the
authority that has jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The flexible connector can then be added
between the black iron pipe and the gas supply line.
CAUTION
Do not exceed 600 in.-lbs. (50 ft.-lbs.) torque when
attaching the gas piping to the gas valve.
WARNING
6.
In some localities, codes may require installation of a
manual main shut off valve and union (furnished by
installer) external to the unit. Union must be of the
ground joint type.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory and field installed) for gas leaks. Use
a leak detecting solution or other preferred means. Do not
test with open flame
The furnace must be isolated from the gas supply system
by closing its individual manual shut-off valve during any
pressure testing of the gas supply system at pressures more
than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquified petroleum gases.
IMPORTANT
When testing gas lines using pressures in excess of
1/2 psig (3.48kPa), gas valve must be disconnected and
isolated. See Figure 35. Gas valves can be damaged
if subjected to pressures greater than 1/2 psig (3.48
kPa).
IMPORTANT
Figure 35
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result
in serious injury, death, or property damage. Never use
an open flame to test for gas leaks. Check all
connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to certain
metals. Carefully rinse piping thoroughly after leak test
has been completed.
WARNING
Summary of Contents for Allied Air A96UHMV
Page 3: ...506550 01 Page 3 of 66 Issue 1230 A96UHMV Exploded View Figure 1...
Page 16: ...506550 01 Page 16 of 66 Issue 1230 Table 5 MAXIMUM ALLOWABLE VENT LENGTH feet...
Page 30: ...506550 01 Page 30 of 66 Issue 1230 Low Voltage Field Wiring Table 11 R required on some units...
Page 31: ...506550 01 Page 31 of 66 Issue 1230 Low Voltage Field Wiring Table 11 R required on some units...
Page 32: ...506550 01 Page 32 of 66 Issue 1230 Low Voltage Field Wiring Table 11 2 Stage Single Stage...
Page 33: ...506550 01 Page 33 of 66 Issue 1230 TYPICAL WIRING DIAGRAM Figure 40...
Page 34: ...506550 01 Page 34 of 66 Issue 1230 Integrated Control Figure 41...
Page 38: ...506550 01 Page 38 of 66 Issue 1230 BLOWER DATA...
Page 39: ...506550 01 Page 39 of 66 Issue 1230 BLOWER DATA...
Page 40: ...506550 01 Page 40 of 66 Issue 1230 BLOWER DATA...
Page 41: ...506550 01 Page 41 of 66 Issue 1230 BLOWER DATA...
Page 42: ...506550 01 Page 42 of 66 Issue 1230 BLOWER DATA...
Page 43: ...506550 01 Page 43 of 66 Issue 1230 BLOWER DATA...
Page 44: ...506550 01 Page 44 of 66 Issue 1230 BLOWER DATA...
Page 45: ...506550 01 Page 45 of 66 Issue 1230 BLOWER DATA...
Page 46: ...506550 01 Page 46 of 66 Issue 1230 BLOWER DATA...
Page 58: ...506550 01 Page 58 of 66 Issue 1230 Configuring Unit Size Codes...