Lennox 3PC036 Installation Instruction Download Page 10

10

3.  Drain should be as short as possible and should 

not have any droops or kinks that would restrict 

condensate flow and shall be approved resistant pipe. 

There must be a 2-inch (51 mm)  space between the 

end of the condensate drain and the final termination 

point (ground, open drain, etc.) to ensure that the line 

will drain freely.

4.  After the system installation is complete, the 

condensate drain line must be checked for leaks and 

proper drainage. If a field-provided condensate pump 

has been installed, it must be checked to ensure proper 

operation. This check is part of the start-up process 

which must be done by the installing contractor.

IMPORTANT

Drain should have a slope of at least ¼ inch per foot and 

should be approved corrosion-resistant pipe. You must 

confirm operation of every drain and pump in the system 

as part of the commissioning procedure.

CORRECT 

Make sure there are no 

kinks or dent in drain 

hose to ensure proper 

drainage.

Figure 11. Condensate Line

Outdoor Unit Installation

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

Placement Considerations

Consider the following when positioning the unit:

•  In coastal areas or other places with salty atmosphere 

of sulfate gas, corrosion may shorten the life of the 

unit. In coastal areas, the coil should be cleaned with 

potable water several times per year to avoid corrosive 

buildup (salt).

•   Some localities are adopting sound ordinances based 

on the unit’s sound level registered from the adjacent 

property, not from the property where the unit is in-

stalled. Install the unit as far as possible from the prop-

erty line.

•  When possible, do not install the unit directly outside 

a window. Glass has a very high level of sound trans-

mission.

•  Install unit level.

Ground

Level

Building Structure

Figure 12. Install Unit Level

•  Choose a place solid enough to bear the weight and 

vibration of the unit, where the operation noise will not 

be amplified.

•  Choose a location where the hot air discharged from 

the unit or the operation noise will not be a nuisance 

to neighbors.

•  Avoid installing the outdoor unit near a bedroom or 

other places where noise may cause a problem.

• 

There must be sufficient space  to carry the unit into 

and out of the site.

• 

There must be unobstructed air flow around the air in

-

let and the air outlet.

• 

The unit must not be installed in areas where a flam

-

mable gas leak may occur.

•  Install the outdoor unit a minimum of 3 feet (1m) away 

from any antenna, power cord (line), radio, telephone, 

security  system,  or  intercom.  Electrical  interference 

and radio frequencies from any of these sources may 

affect operation.

•  Since water drains from the outdoor unit during vari-

ous stages of operation, do not place anything which 

may be damaged by moisture under the unit.

Direct Sunlight, Rain, Snow and Ice Protection

•  If the outdoor unit is subjected to prolong exposure to 

direct sunlight with temperatures over 100°F (38°C) a 

canopy is recommended as illustrated in “Figure 13. 

Outdoor Unit on Pedestal and Protective Canopy” or  

“Figure 18. Dog House-Style Shelter” on page 12.

IMPORTANT

The construction of a canopy or shade is necessary 

because of an ambient limit control set to 122°F (50°C)

to protect the electronics. If the outdoor unit is placed in 

direct sunlight it is possible that the limit may activate 

and shut down the unit. 

Summary of Contents for 3PC036

Page 1: ...7784 01 Table of Contents General 1 Included Parts 2 Model Number Identification 3 Indoor Outdoor Unit Match Ups 4 Typical System Components 4 System Dimensions 5 Outdoor Units 5 Indoor Units 6 System...

Page 2: ...er guide 1 ea Wireless control holder with 2 mounting screws 1 Mounting plate with mounting screws and anchors FROM EDGE TO HOLE CENTER 50mm FROM EDGE TO HOLE CENTER 100mm 150 100 100 100 50 50 50 2 2...

Page 3: ...ominal Cooling Capacity 036 3 tons Refrigerant Type 4 HFC 410A Minor Design Sequence 1 1st Revision 3 P C 036 S 4 S 1 P Series Type 3 3 ton outdoor unit for 3PC 3WMC Wall Mount system OUTDOOR SINGLE Z...

Page 4: ...Panel Outdoor Unit Power Cable 1 2 3 4 5 6 7 8 9 10 1 2 3 4 6 7 8 9 10 5 Humidity Boost IMPORTANT The refrigerant metering device for this system is located in the outdoor unit This makes it necessary...

Page 5: ...SIDE VIEW 37 1 4 946 26 1 2 673 40 1 2 1029 GAS VALVE LIQUID VALVE 2 3 8 60 4 1 4 108 3 5 8 92 18 1 8 460 18 457 15 7 8 403 DRAIN HOLE Bottom of Unit 31 7 8 810 15 1 4 387 16 1 8 410 2 7 8 73 1 25 Fi...

Page 6: ...O HOLE CENTER 70mm BUBBLE LEVEL 150 100 50 2 4 6 RECOMMAND mm inch 100 100 50 50 2 2 4 4 LIQUID GAS mm inch Indoor unit outline Right rear side refrigerant pipe inlet 2 1 2 64 diameter Left rear side...

Page 7: ...th no obstructions on the other three sides Figure 5 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW Wall Vertical Clearance Clearance to Floor 72 inches 1829 mm Minimum 96 inches 2438 mm Rec...

Page 8: ...local codes Allow sufficient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or interc...

Page 9: ...sed to these construction materials Installation of Indoor Unit on Wall Mounting Plate 1 A length of field provided flexible condensate piping should be connected to the drain prior to securing the un...

Page 10: ...tall the unit as far as possible from the prop erty line When possible do not install the unit directly outside a window Glass has a very high level of sound trans mission Install unit level Ground Le...

Page 11: ...et Figure 14 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Figure 15 Outdoor Unit Air Flow Obstructed by Snow Figure 16 Avoid Defrost Water Ice Hazard Prevai...

Page 12: ...low drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated d...

Page 13: ...using Table 3 Refrigerant Piping and Indoor Unit Connection Sizes on page 14 2 Confirm that you are using the correct diameter piping 3 Determine the necessary piping length required for the applicat...

Page 14: ...Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 36000 3 8 5 8 A B CANT ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 25 Making Connections Male...

Page 15: ...tested and evacuated to remove any non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas c...

Page 16: ...e to reattach all electrical box covers after con nections are complete Indoor Unit Indoor unit is powered by the outdoor unit Communication Wiring Use one stranded 3 conduc tor wire to provide power...

Page 17: ...17 T5 T5 NOTE Recommend to use two core shielded wire Figure 27 3PC036 Outdoor Unit Wiring Diagram...

Page 18: ...ed 24 hours before unit start up to prevent compressor damage as a result of slugging 1 Inspect all factory and field installed wiring for loose connections 2 Verify that the manifold gauge set is con...

Page 19: ...e detection PC 00 Error Inverter module IPM error PC 01 Error High or Low voltage protection PC 02 Error High temperature sensed at compressor top PC 03 Error Low or High pressure protection PC 04 Err...

Page 20: ...he mode button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function run for 5 minutes and perfor...

Page 21: ...e or other various factors Also the Follow Me mode does not operate in this mode NOTE In addition the indoor units do not have a humidistat installed therefore they are unable to determine humidity le...

Page 22: ...ture Figure 30 Self Clean User Information Indoor Unit Display Remote Control Remote Control Holder Louver Front Panel Air Filter pull up Display window ECO intelligent eye Humidity Boost Figure 31 In...

Page 23: ...ow out After cleaning the internal blower then keeps operating with hot air to blow dry the evaporator thus preventing the growth of mold and keeping the inside clean When this function is turned on t...

Page 24: ...r operation use the remote control to activate the unit Unit must be turned off before manual operation To operate your unit manually 1 Locate the MANUAL CONTROL button on the right hand side panel of...

Reviews: