Lennox 15CHAX?24 Installation Instructions Manual Download Page 13

Page 13

Unit Start−Up and Operation

Each 15CHAX packaged cooling unit is factory−charged
with R−410A refrigerant. The compressor is hermetically
sealed, internally sprung and base−mounted with
rubber−insulated hold−down bolts.

Pre−Start Check List:

 1 − Make sure refrigerant lines do not rub against the cabi-

net or each other.

 2 − Inspect all electrical wiring, both factory− and field−

installed, for loose connections.

 3 − Check voltage at the disconnect switch. Voltage must

be within the range listed on the unit nameplate. If not,
consult power company and have voltage condition
corrected before starting unit.

 4 − Recheck voltage with unit running. If power is not with-

in the range listed on the unit nameplate, stop the unit
and consult the power company. Check unit amper-
age. Refer to unit nameplate for correct running amps.

 5 − Make sure filter is in place before unit start−up.

 6 − Before placing the unit into full operation, energize the

unit for three false starts. Energize the compressor
just long enough for it to make a few revolutions, wait
five to seven minutes before repeating a second and
third time.

Cooling Sequence of Operation

When the thermostat calls for cooling, the  R" to Y" circuit
is closed to energize the compressor contactor. The
contactor brings on both the compressor and outdoor fan.
The thermostat also closes the R" to G" circuit to energize
the circulating air blower. When the cooling demand is
satisfied, the thermostat opens the circuits, as well as the
compressor contactor. The compressor and outdoor fan

immediately stop. The circulating air blower continues
operating through a 90−second delay.
Unit compressors have internal protection. If there is an
abnormal rise in the compressor temperature, the
protector will open and the compressor will stop.

System Performance

For maximum performance of this cooling system, the
operating temperatures and pressure should be checked
and subcooling determined at Standard ARI test conditions
of 82

 F outdoor temperature / 80

 F indoor dry bulb / 67

 F

indoor wet bulb. If subcooling measured deviates from
values in table 6, refrigerant charge should be adjusted
accordingly for maximum performance.

Table 6

Suction Superheat Values

Unit Model No.

Suction Superheat

82

F OD / 80

F IDDB

/ 67

F IDWB

15CHAX−24
15CHAX−30

12

15CHAX−36

15

15CHAX−42
15CHAX−48
15CHAX−60

10

Verify system performance using table 7 as a general
guide. Table 7 should not be used for charging unit. Minor
variations in these pressures may be expected due to dif-
ferences in installations. Significant differences could
mean that the system is not properly charged or that a prob-
lem exists with some component in the system.

Used carefully, this table could serve as a useful service
guide. Data is based on 80

°

F dry bulb / 67

°

F wet bulb return

air. Allow unit operation to stabilize before taking pressure
readings.

Table 7

Normal Operating Pressures

80

°

F db / 67

°

F wb RETURN AIR

Air Temperature Entering Outdoor Coil (

°

F)

UNIT

PRESSURE

65

70

75

80

82

85

90

95

100

105

110

115

15CHAX−24

142

143

144

146

146

147

148

149

150

151

152

153

15CHAX−30

134

136

138

140

141

142

144

146

148

149

151

152

15CHAX−36

Suction

143

144

146

147

148

149

151

152

155

155

157

157

15CHAX−42

Suction

140

140

140

141

141

141

142

142

143

144

145

147

15CHAX−48

140

141

142

144

144

145

146

147

148

149

150

151

15CHAX−60

143

144

145

146

146

147

147

148

149

150

151

152

15CHAX−24

219

242

264

287

296

310

333

355

379

398

430

457

15CHAX−30

232

255

277

300

309

323

345

368

390

408

440

470

15CHAX−36

Liquid

244

268

292

316

326

340

363

369

410

429

461

493

15CHAX−42

Liquid

225

247

269

291

300

314

337

357

383

402

434

457

15CHAX−48

243

264

285

307

315

328

349

370

391

408

440

470

15CHAX−60

257

280

303

326

335

349

372

395

418

436

468

497

Summary of Contents for 15CHAX?24

Page 1: ...it If you find any damage im mediately contact the last carrier WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life In...

Page 2: ...HAX 24 75 94 117 94 16 29 15CHAX 30 75 94 117 94 16 29 15CHAX 36 83 97 121 104 16 30 15XHAX 42 110 138 163 129 21 33 15CHAX 48 114 139 164 134 21 33 5 15CHAX 60 119 145 171 140 21 33 5 Model No A B C...

Page 3: ...s under construction the following conditions must be met or the warranty will be void A room thermostat must control the unit The use of fixed jumpers that will provide continuous heating or cooling...

Page 4: ...of the unit Rigging Setting Unit Exercise care when moving the unit Do not remove any packaging until the unit is near the place of installation An optional lifting lug kit 92M51 may be purchased sep...

Page 5: ...hat each appliance connected to the common venting system is venting properly step 3 return all doors windows exhaust fans fireplace dampers and any other gas burning appliances to their previous mode...

Page 6: ...e job They should NOT be sized by simply matching the dimensions of the duct connections on the unit Ducting installed outdoors MUST be insulated and waterproofed CAUTION When fastening duct system to...

Page 7: ...ower supplies Failure to disconnect all power supplies could result in personal injury or death CAUTION When connecting electrical power and control wir ing to the unit waterproof type connectors MUST...

Page 8: ...Page 8 Figure 7 15CHAX Series Packaged Electric Units Typical Wiring Diagram...

Page 9: ...jumper positions gently pull the jumper off the pins and place it on the desired set of pins The following section outlines the different jumper selections available and conditions associated with ea...

Page 10: ...rformance 0 through 0 80 in w g 0 through 200 Pa External Static Pressure Range AD Jumper Speed Positions AD JUST COOL Speed HEAT Speed CONTINOUS FAN Speed JUST Jumper A B C D A B C D A B C D Jumper S...

Page 11: ...devices LSOM LED Functions Power LED green Voltage within the range of 19 28VAC is present at the system monitor power connec tion Alert LED yellow Communicates an abnormal system condition through a...

Page 12: ...ondenser fan is not running 4 Return air duct has substantial leakage 5 If low pressure switch is present see Flash Code 1 info Yellow Alert Flash Code 3 Short Cycling Compres sor is running only brie...

Page 13: ...l stop System Performance For maximum performance of this cooling system the operating temperatures and pressure should be checked and subcooling determined at Standard ARI test conditions of 82 F out...

Page 14: ...y lubricated and require no further lubrication Motors should be cleaned yearly to prevent the accumulation of dust and dirt on the windings or motor exterior Coil Dirt and debris should not be allowe...

Reviews: