background image

Page 18

Flushing Line Set and Indoor Coil 

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor as­
sembly.

C

Using two wrenches, disconnect liquid line from liquid line orifice hous­
ing. Take care not to twist or damage distributor tubes during this pro­
cess.

D

Remove and discard fixed orifice, valve stem assembly if present and
Teflon

®

 washer as illustrated above.

E

Use a field-provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE (UNCASED
COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)

TWO PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

CHECK

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor
assembly.

C

Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.

D

Remove the vapor line sensing bulb.

E

Disconnect the liquid line from the check expansion valve at the liquid
line assembly.

F

Disconnect the check expansion valve from the liquid line orifice
housing. Take care not to twist or damage distributor tubes during this
process.

G

Remove and discard check expansion valve and the two Teflon

®

 rings.

H

Use a field-provided fitting to temporary reconnect the liquid line to the
indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

INVERTED HCFC-22
CYLINDER CONTAINS
CLEAN HCFC-22 TO BE
USED FOR FLUSHING.

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

V

APOR

LIQUID

1

A

Inverted HCFC-22 cylinder with clean refrigerant to the vapor service
valve.

B

HCFC-22 gauge set (low side) to the liquid line valve.

C

HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank to the gauge set.

D

Connect recovery tank to recovery machines per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

A

Set the recovery machine for liquid recovery and start the
recovery machine. Open the gauge set valves to allow the
recovery machine to pull a vacuum on the existing system line
set and indoor unit coil.

B

Invert the cylinder of clean HCFC-22 and open its valve to allow
liquid refrigerant to flow into the system through the vapor line
valve. Allow the refrigerant to pass from the cylinder and through
the line set and the indoor unit coil before it enters the recovery
machine.

C

After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull down to 0
the system.

D

Close the valve on the inverted HCFC-22 drum and the gauge
set valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the
same amount of clean refrigerant that previously charged the
system. Check the charge in the flushing cylinder before
proceeding.

1A

2

3

1B

Figure 9. Removing Metering Device and Flushing

Summary of Contents for 13ACX

Page 1: ...nit Dimensions 8 Typical Unit Parts Arrangement 9 Operating Gauge Set and Service Valves 9 Unit Placement 11 Removing and Installing Louvers 12 New or Replacement Line Set 13 Brazing Connections 15 Fl...

Page 2: ...4 lbs 7 oz 3 18 13ACX 018 230 02 76 3 lbs 13 oz 3 18 13ACX 018 230 03 76 5 lbs 7 oz 3 18 13ACX 018 230 10 through 15 76 3 lbs 13 oz 3 18 13ACX 018 230 17 18 76 3 lbs 15 oz 3 18 1 Tested according to...

Page 3: ...hes 13ACX 042 230 01 79 8 lbs 3 oz 4 22 13ACX 042 230 03 79 7 lbs 6 oz 4 22 13ACX 042 230 10 through 16 79 6 lbs 6 oz 4 22 13ACX 042 230 17 18 79 6 lbs 8 oz 4 22 1 Tested according to AHRI Standard 27...

Page 4: ...manual to determine wire fuse and disconnect size requirements 208 230V 60 Hz 1 Ph Model Number Label Rev Unit Compressor Condenser Fan Maximum Over current Protection amps 1 Minimum Circuity Ampacity...

Page 5: ...o National or Canadian Electrical Code manual to determine wire fuse and disconnect size requirements 208 230V 60 Hz 1 Ph Model Number Label Rev Unit Compressor Condenser Fan Maximum Over current Prot...

Page 6: ...breaker or fuse 2 Refer to National or Canadian Electrical Code manual to determine wire fuse and disconnect size requirements 208 230V 60 Hz 1 Ph Model Number Label Rev Unit Compressor Condenser Fan...

Page 7: ...5 26 2 134 0 1 4 825 1 7 3 1 2 0 50 33 0 25 1 120 0 1 4 825 1 7 3 1 3 0 60 34 6 26 3 120 0 1 4 825 1 7 3 1 13ACX 060 230 12 1 0 60 34 6 26 3 134 0 1 4 825 1 7 3 1 13ACX 060 230 13 1 0 50 33 1 25 1 120...

Page 8: ...4 718 37 1 4 946 13ACX 060 230 03 through 16 28 1 4 718 33 1 4 845 13ACX 060 230 17 28 1 4 718 29 1 4 743 WARNING This product and or the indoor unit it is matched with may contain fiberglass wool Dis...

Page 9: ...ess See the Lennox Service and Application Notes C 08 1 for further details and information TORQUE REQUIREMENTS When servicing or repairing heating ventilating and air conditioning components ensure t...

Page 10: ...ing Ball Type Service Valve 1 Remove stem cap with an appropriately sized wrench 2 Use an appropriately sized wrenched to open To open valve roate stem counterclockwise 90 To close rotate stem clockwi...

Page 11: ...ALLED IN LINE SET WILL REDUCE LINE SET VIBRATION GROUND LEVEL MOUNTING SLAB BUILDING STRUCTURE DISCHARGE AIR Figure 3 Placement and Slab Mounting Unit Placement See Unit Dimensions on page 8 for sizin...

Page 12: ...ING To prevent personal injury or damage to panels unit or structure be sure to observe the following While installing or servicing this unit carefully stow all removed panels out of the way so that t...

Page 13: ...nes will not create unnecessary vibration and subsequent sounds Also consider the following when placing and installing a high efficiency air conditioner Field refrigerant piping consists of liquid an...

Page 14: ...ER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices should be...

Page 15: ...connections to service valves WARNING Danger of fire Bleeding the refrigerant charge from only the high side may result in pressurization of the low side shell and suction tubing Application of a bra...

Page 16: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 17: ...nstructions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY D...

Page 18: ...expansion valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANI...

Page 19: ...onnected the liquid line to the indoor unit s distributor assembly B Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads...

Page 20: ...f HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the line set...

Page 21: ...and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F...

Page 22: ...local codes and the current Canadian Electrical Code CEC Refer to the furnace or air handler installation instructions for additional wiring application diagrams and refer to unit nameplate for minim...

Page 23: ...IGH VOLTAGE FLEXIBLE CONDUIT A B System Operation IMPORTANT Some scroll compressor have internal vacuum protector that will unload scrolls when suction pressure goes below 20 psig A hissing sound will...

Page 24: ...be flushed with a water hose Ensure power is off before cleaning NOTE It may be necessary to flush the outdoor coil more frequently if it is exposed to substances which are corrosive or which block ai...

Page 25: ...Maximum Fuse or Circuit Breaker Electrical Connections Tight Indoor Filter clean Supply Voltage Unit Off Indoor Blower RPM S P Drop Over Indoor Dry Outdoor Coil Entering Air Temp Discharge Pressure Su...

Page 26: ...C timed off control if used which energizes contactor K1 provided S4 high pressure switch is closed 3 K1 1 N O closes energizing compressor B1 and outdoor fan motor B4 4 Compressor B1 and outdoor fan...

Page 27: ...Page 27 13ACX SERIES Figure 15 Use for 13ACX XXX 230 11 or later...

Page 28: ...ameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the i...

Page 29: ...70 Temperature of air entering indoor coil F INDOOR COIL DRY BULB DRY BULB WET BULB B TDrop 19 A Dry bulb Wet bulb F A 72 B 64 C 53 air flow air flow All temperatures are expressed in F 1 Determine t...

Page 30: ...et g per 1 5 m adjust from 15 feet 4 6 m line set 3 8 9 5 mm 3 ounce per 5 85 g per 1 5 m Refrigerant Charge per Line Set Length NOTE The above nameplate is for illustration purposes only Go to actual...

Page 31: ...THOD Weigh in or remove refrigerant based upon line length BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coi...

Page 32: ...determine superheat SH VAP _____ SAT ______ SH ______ 11 Record the wet bulb temperature air entering indoor coil WB _______ 12 Record outdoor ambient temperature 13 Compare results with table to the...

Page 33: ...above are located at the end of this manual 13ACX 018 230 XX 01 02 10 11 12 13 14 15 17 18 13ACX 024 230 XX 01 02 10 11 12 13 15 17 18 19 20 13ACX 030 230 XX 01 02 10 11 12 13 15 17 18 19 13ACX 036 2...

Page 34: ...24 27 31 95 6 10 14 18 22 25 29 100 8 12 16 21 24 28 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 24 F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 Wet bulb temperature of air entering indoor coil...

Page 35: ...95 6 10 14 18 22 25 29 100 8 12 16 21 24 28 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 24 F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 Wet bulb temperature of air entering indoor coil Model 18 2...

Page 36: ...95 6 10 14 18 22 25 29 100 8 12 16 21 24 28 105 5 9 13 17 22 26 110 6 11 15 20 25 115 8 14 18 24 F 50 52 54 56 58 60 62 64 66 68 70 72 74 76 Wet bulb temperature of air entering indoor coil Size 18 24...

Page 37: ...21 246 126 245 123 261 134 246 126 247 125 248 124 70 21 250 124 265 129 265 126 281 136 263 128 266 128 266 126 75 24 270 128 286 132 286 129 301 138 284 131 286 131 288 130 80 27 291 131 307 135 308...

Page 38: ...23 Equalizer Line Page 19 Evacuating Line Set and Indoor Coil Page 21 Expansion Valve Indoor Page 19 F Filter Drier Page 15 Flushing Line Set and Indoor Coil Page 18 G Gauge Port Seal Cap Page 9 Gauge...

Page 39: ...ethod Page 31 Determing Charge Method Page 30 Subcooling TXV Charge Method Page 31 Superheat RFC Method Page 32 Weigh In Method Page 30 RFCI Page 13 Roof Mounting Page 12 S Sensing Blub Page 19 Sequen...

Reviews: