background image

Page 13

 7 − After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and HCFC-22
mixture. Correct any leaks and recheck.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 10,000 microns.

 1 − Connect manifold gauge set to the service valve ports :

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open both manifold valves and start vacuum pump.

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches of mercu-

ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in 

absolute pressure

.

A rapid rise in pressure indicates a relatively large leak.
If this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the hose. Open the manifold gauge valves
to break the vacuum in the line set and indoor unit.
Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not
rise above 500 microns (29.9 inches of mercury) within
a 20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When  the  absolute  pressure  requirement  above  has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of
HCFC-22 refrigerant. Open the manifold gauge valves
to break the vacuum from 1 to 2 psig positive pressure in
the line set and indoor unit. Close manifold gauge
valves and shut off the HCFC-22 cylinder and remove
the manifold gauge set.

Start−Up

IMPORTANT

If unit is equipped with crankcase heater, it should be
energized 24 hours before unit start−up to prevent
compressor damage as a result of slugging.

 1 − Rotate the fan to check for frozen bearings or binding.

 2 − Inspect all factory− and field-installed wiring for loose

connections.

 3 − After evacuation is complete, open the liquid line and

vapor line service valves to release the refrigerant
charge (contained in outdoor unit) into the system.

 4 − Replace the stem caps and secure finger tight, then

tighten an additional one-sixth (1/6) of a turn.

 5 − Check voltage supply at the disconnect switch. The

voltage must be within the range listed on the unit’s
nameplate. If not, do not start the equipment until you

Summary of Contents for 12HPB Series

Page 1: ...4 532M 06 04 Supersedes 04 04 Table of Contents 12HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Refrigerant M...

Page 2: ...tion 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 compressor coil drain outlets around perimeter of base optional unit stand off kit 4 field installed B C A optional unit stand off kit 4 field in...

Page 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Page 4: ...G Unit must be grounded in accordance with national and local codes Electric Shock Hazard Can cause injury or death 1 Install line voltage power supply to unit from a properly sized disconnect switch...

Page 5: ...power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor Figure 5 R C W1 Y1 O G R C W1 W2 W3 G Outdoor Unit and Blower Unit Thermostat Designations with emergency heat...

Page 6: ...o the compressor Installing Refrigerant Line During the installation of any heat pump or a c system it is important to properly isolate the refrigerant lines to prevent unnecessary vibration Line set...

Page 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Page 10: ...d line at the indoor coil Refrigerant Metering Device 12HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application informat...

Page 11: ...e wrench 2 Connect gauge to the service port 3 When testing is completed replace service port cap Tighten finger tight then an additional 1 6 turn To Open Service Valve 1 Remove stem cap with an adjus...

Page 12: ...r use oxygen to pressurize a refrigera tion or air conditioning system Oxygen will explode on contact with oil and could cause personal injury WARNING Danger of explosion Can cause equipment damage in...

Page 13: ...r port hose from vacuum pump Attach the manifold center port hose to a nitrogen cylin der with pressure regulator set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break th...

Page 14: ...which charg ing method to use Proceed with the appropriate charg ing procedure Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient...

Page 15: ...erature to check liquid line tempera ture Verify the unit charge using the approach method 5 The difference between the ambient and liquid temper atures should match values given in table 6 If the val...

Page 16: ...ts An amber indicating light simultaneously comes on to remind the homeowner that he is operating in the emergency heat mode Emergency heat is usually used during an outdoor shut down but it should al...

Page 17: ...mode If the jumper is removed before an addi tional 5 second period has elapsed 7 seconds total the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed If th...

Page 18: ...lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop tabl...

Reviews: