Lennox Hearth Products Elite RAVENNA IPI Install And Operation Instructions Download Page 15

15

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Figure 15 - Control Panel Removal

Figure 16 - Burner ON/OFF Switch On Surround

Figure 17 - Burner ON/OFF Switch On Control Panel

Operating Options

 - RDV33/40 IPI Models Only

Burner ON/OFF Switch Installation:

The burner ON/OFF switch on your gas appliance is used to turn the burner 

on and off. This switch can be installed in the hole in the right side of 

the top surround panel (see Option 1) or in the hole in the control panel 

in the control compartment (see Option 2).  

Note:

 Wire connections on 

provided switch are reversible.

Option 1 - Switch Installation On Surround Panel

 

(see 

Figure 16

)

 - 

1.  Disconnect the switch from the extension wires to which it is attached, 

then unscrew the plastic nut from the back side of the switch.

2.  Insert the switch into the hole located on the upper right side of the 

surround then reinstall the plastic nut onto switch.

3.  Install the three plastic adhesive backed wire restraints (found in the 

supplied hardware kit) to the backside of the surround panel. Route 

the switch wires through these restraints and up to the switch. Care 

should be taken to ensure the wires do not come in contact with the 

hot surfaces of the fire box. Reconnect the wires to the switch. 

Option 2 - Switch Installation On Control Panel 

(see 

Figure 17

)

 -

Note: It will aid in the ease of installation if you remove the control panel 

(see 

Figure 15

)

. The panel has keyhole slots where it mounts to the base. 

Loosen the two nuts securing the panel using 

3/8" 

 wrench. Carefully 

move out the panel far enough to access the back. Do not pull the panel 

out too far or it may pull apart some of the connections.

1.  Carefully cut out the burner switch hole in the control panel label.

2.  Disconnect the switch from the extension wires to which it is attached, 

then disconnect these wires from the green and white wires on the 

on the main harness.  The extension wires are no longer needed and 

can be removed from the appliance.

3.  Unscrew the plastic nut from the back side of the switch.  Insert the 

switch into the hole on the control panel then reinstall the plastic nut 

onto switch.

4.  Connect the green and white wires from the main wire harness to the 

switch. Care should be taken to ensure the wires are positioned so they 

will not come in contact with the hot surfaces of the fire box. Reinstall 

control panel, if necessary, and verify there are no wires coming in 

contact with the fire box.

Nut

Surround

Panel

AUTO

ON

ON

OFF

BLOWER

PILOT

FLAME HEIGHT

BURNE

R

OPTION 1

OPTION 2

AU

ON

ON

OFF

BLOWER

PILO i

FLAME HEIGHT

BURN

ER

Optional GT Remote Control Installation - 

An optional remote control 

can be used to supplement the burner ON/OFF switch (see 

Page 32

 for 

ordering information).  See instructions provided with remote control 

kit for installation and operation instructions.

Face Installation - All Models

A  number  of  different  face  finishes  and  styles  are  available  for  your 

appliance. The Arch face comes with a sight obstructor that must be 

installed prior to installing the surround panels and face.  Instructions 

for installing the sight obstructor are included with the face. The faces 

come with hooked brackets. To install the face, hang the hooked brackets 

on the surround brackets (See C in 

Figure 14

)

.

Note:

 

Plated surfaces must be cleaned with glass cleaner and a soft clean 

cloth before firing the first time or fingerprints and stains will remain 

permanently. 

NEVER use brass polish to clean plated surfaces, this 

will remove the plating!!!

Summary of Contents for Elite RAVENNA IPI

Page 1: ...rnis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installation et l entretien doivent tre assur s par un installateur ou un service d entretien qualifi ou...

Page 2: ...40 TCC models only 11 Installation 11 17 Venting Installation 11 Zero Clearance Fireplace Installation 12 Firebox Panel Kit and Log Set Installation 13 14 Surround Panels Installation 14 Operating Op...

Page 3: ...ller service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Page 4: ...connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance is only...

Page 5: ...panel de control para quitarelpolvoyaceite Peguelaetiquetaadyacente alinterruptordecontroldelquemadorquecontrola elartefacto FiguraA Seleccioneelidiomaquem s se habla en la casa 2 Identifique el tran...

Page 6: ...or factory built fireplaces Fireplace Requirements These heaters are designed to be installed into an existing masonry fireplace built to UBC 37 or ULC S628 standards or factory built solid fuel wood...

Page 7: ...zed testing and certification laboratory to ANSI American National Standard Institute gas appliance safety standards This appliance has been tested and certified by Intertek Testing Services Portland...

Page 8: ...kaging List Insert Body Packaging List 1 Insert Body with Burner Cassette 1 Log Set 1 Bag of Embers 1 Power Cord 1 Fasteners 6 slotted 1 4 truss screws 6 speed nuts 9 spring clips 3 plastic adhesive w...

Page 9: ...A 31 1 2 800mm Front Opening Width B 19 1 2 495mm Height C 19 483mm Rear Width D 16 406mm Fireplace Depth Top View Left Side View Right Side View Front View A B C D Figure 3 Minimum Fireplace Cavity F...

Page 10: ...note that the RDV33 IPI TCC mantel clearances are 4 less than the RDV40 IPI TCC mantel clearances as shown in Figure 4A RDV40 IPI TCC and Figure 4B RDV33 IPI TCC CLEARANCES TO COMBUSTIBLES RDV40 IPI T...

Page 11: ...acturer s instructions for installation and vent termination These appliances are approved for use with the following vent kits Amerivent Flex Liner 3 X 35 3AFL 35 Adaptor w Flashing 4DCAT33 Terminati...

Page 12: ...e sealed around the vent pipes Use a non combustible seal off plate i e 22 gage sheet steel or unfaced fiberglass insulation 8 lb per square foot density minimum to seal around the vent pipes Whicheve...

Page 13: ...o Optional 33 000 BTU Natural Gas Input To convert input from 40 000 BTU s to 33 000 BTU s Assuming the front door is already removed 1 Remove the log rack Use a 5 32 allen wrench by removing two scre...

Page 14: ...oundpanelsinfrontoftheholesonthesurroundbrackets Next insert two slotted 1 4 truss screws for each side surround panel and secure loosely 5 Fasten the top surround panel with the remaining two truss s...

Page 15: ...ns 1 Carefully cut out the burner switch hole in the control panel label 2 Disconnect the switch from the extension wires to which it is attached then disconnect these wires from the green and white w...

Page 16: ...n retighten if necessary If the pressure is not sufficient make sure the gas supply line is large enough the supply regulator is properly adjusted and the total gas load for the residence does not exc...

Page 17: ...r will result in bigger flames and more color To adjust the air shutter insert a regular screwdriver into the slide adjustment and slide it side to side see Figures 19a and 19b CAUTION The air shutter...

Page 18: ...mmande Figure B Choisissez la langue qui est principalement parl e dans la r sidence du propri taire En cas de doute collez l tiquette en anglais 3 Si vous ne trouvez pas les tiquettes veuillez appele...

Page 19: ...power to the appliance 8 Turn the burner ON OFF switch in the control compartment to ON After approximately 4 seconds the spark ignition system will spark for 60 seconds to light the main burner 9 If...

Page 20: ...high altitudes Figure 21A RDV33 40 IPI Models Figure 21B RDV33 40 TCC Models IMPORTANTNOTE Whenopeningthelowerdoorontheface while the insert is burning pull at the far left or far right vent openings...

Page 21: ...s to indicate that it is ready to synchronize with the Remote transmitter Install 3 AAA type batteries in the Remote transmitter battery bay located on the base of the Remote With the batteries alread...

Page 22: ...d off The Up Arrow Key will increase the flame height each time it is pressed If the Up Arrow Key is pressed while the system is on but the flame is off the flame will come on in the high position see...

Page 23: ...r proper main burner operation at both high and low flame OPERATION RDV33 40 TCC Models Only No Blue Flame Center Soot at Flame Tip Dark Orange Flame IMPROPERLY BURNING FLAME Soot above Flame Tip No S...

Page 24: ...MOTE RECEIVER BLOWER SPEED CONTROL PILOT ON AUTO SWITCH AC DC ADAPTER POWER OUTLET BOX 6 WHT 5 BLUE WHT BLK WHT BLK BLK BLK 4 GRN GRN 8 GRN 3 GRAY 14 RED 9 GRN 2 RED 1 RED 3 BLK 2 BLK 1 RED PILOT ROOM...

Page 25: ...TEMPERATURE N C NORMALLY CLOSED N O NORMALLY OPEN FEMALE DISCONNECT MALE DISCONNECT STUD CONNECTION REMOTE RECEIVER PILOT ON AUTO SWITCH FAN CONTROL MODULE POWER ADAPTOR BOX 6 WHT 5 BLUE 11 YLW 10 ORG...

Page 26: ...Never block or restrict vent openings obstruct flow of ventilation air or use vents other than those approved for use with this appliance o Check that the chimney and its outlet are open and free of...

Page 27: ...not attempt to substitute the materials used on these doors or replace cracked or broken glass Handle this glass with extreme care Glass is susceptible to damage Do not scratch or handle roughly while...

Page 28: ...e conversion Gas Conversion Kits Please see instructions provided with conversion kit Blower Removal Unplug the power supply cord from the electrical outlet prior to removing theblower Theblowercanbea...

Page 29: ...llation on Pages 13 and 14 The main Burner comes on but then goes out Gas is not reaching the appliance Loose wires to the valve or ignition module Pilot flame is not engulf ing the sensor Obstructed...

Page 30: ...f Switch Burner and Pilot Mode 24 H5655 Blower Speed Control Rheostat 25 H7274 Fan Control Module For TCC Models Only H8484 Pilot Ground Wire H8485 RDV IPI Blower Wiring Harness H8486 Wire Extension H...

Page 31: ...NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE REPLACEMENT PARTS RDV33 40 IPI RDV33 40 TCC 1 27 26 2 3 4 5 15 6 7 16 37 14 36 25 33 34 21 22 23 13 32 31 30 29 28 8 17 9 10 11 20 19 33 21 34 22 23 12 24...

Page 32: ...36 1 2 W x 23 1 2 H Orifice Kits Main Burner 33 000 BTU converts from standard 40 000 BTU input to optional 33 000 BTU input Cat No Description H5924 Orifice Main Burner 36 Natural Gas 33 000 BTU H592...

Page 33: ...RDV DBV FP2941 D 29 x 41 Black Trim Includes black trim x x x x x x x H8555 RDV DBV FP2948 D 29 x 48 Black Trim Includes black trim x x x x x x x H8556 RDV DBV FP3341 D 33 x 41 Black Trim Includes bl...

Page 34: ...CST GRL TRD3 Grill bars Traditional Box 3 of 3 Or 75091 PILCST GRL FIL3 Grill filigree Ornate Box 3 of 3 45 1 2 1156mm 44 1118mm 7 1 8 181mm 30 762mm 22 7 8 581mm uCast Surround Assembly For Pillared...

Page 35: ...E D INSTALLATION ANSI NFPA 54 DERNI RE DITION ETATS UNIS OU CAN CGA B149 1 DERNI RE DITION CANADA CET APPAREIL DOIT TRE INSTALL SELON LES DIRECTIVES D INSTALLATION DU FABRICANT POUR INSTALLATION DANS...

Page 36: ...NFPA 54 DERNI RE DITION ETATS UNIS OU CAN CGA B149 1 DERNI RE DITION CANADA CET APPAREIL DOIT TRE INSTALL SELON LES DIRECTIVES D INSTALLATION DU FABRICANT POUR INSTALLATION DANS DES FOYERS COMBUSTIBLE...

Page 37: ...plosion entra nant des dommages des blessures ou la mort A Cet appareil est muni d un dispositif d allumage qui allume automatiquement la veilleuse Ne tentez pas d allumer la veilleuse manuellement B...

Page 38: ...Page 30 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your Lennox Hearth Products distributor or dealer Parts will...

Reviews: