PLANNING YOUR INSTALLATION
PAGE 7
ALCOVE CLEARANCES
NOTE:" = inches, mm = millimeter, cm = centimeter
Alcoves must have minimum dimensions of 84" (214 cm)
height, 56" (142 cm) width and 24" (610 mm) maximum
depth.
Require pipe: Type L Vent pipe to the top of the stove.
Manufactured (mobile) home installations must be
equipped with a rain cap and spark arrestor and must
use a pipe shield extending a minimum of 24" (610 mm)
above the stove (resting on stove) is mandatory for the
installation of this appliance into a combustible alcove.
Alcove Dimension Requirements
Alcove Top View / Stove Clearances
ALCOVE CLEARANCES:
Back wall to pipe O.D.
11" / 280 mm
Side wall to pipe O.D.
25.5" / 648 mm
Back wall to stove
5.5" / 140 mm
Side wall to stove
16" / 407 mm
Alcove - Top View
* NOTE:
Alcove dimensions cannot be reduced by the
use of non-combustible materials such as brick, stone,
etc. Alcove dimensions listed are minimum dimensions
and are not measurements for building an Alcove. You
will need to consider these clearances, as well as
other dimensional requirements before you build the
alcove and install this appliance.
REDUCED MASONRY STRUCTURE CLEARANCE
(ALCOVE)
Your stove can be installed in a masonry structure with
reduced clearances if the structure was built to National
Building Code for fireplaces and chimneys (UBC 37).
The firebox of the masonry structure must be of ade-
quate size to allow a minimum of 6” (152.4 mm) clear-
ance to the sides and top of the stove and 2” (50.8 mm)
clearance to the rear. All stove models must be installed
on their original listed legs or base unless otherwise
specified by OMNI Testing Laboratory.
The minimum venting requirement is a listed chimney
liner that extends from the flue collar of the stove to the
first tile liner of the chimney where it is sealed. All joints
and connections must be made airtight to prevent leak-
ing and
downdrafts.
PROTECTED WALL CLEARANCE
Some local codes will allow reduced clearances when
the stove is installed adjacent to a protected wall system.
Your local building official must approve the variance.
Normally, the protected wall system is defined as a non-
combustible material with a minimum of 1” (25.4 mm) air
space behind. Check your local building codes or with a
qualified installer (Ref. NFPA 211).
56” (143 cm)
Minimum
24” (610 mm)
Depth
Maximum
84”
(214 cm)
Min.
16”
(407 mm)
25.5”
(648 mm)
5.5” (140 mm)
11” (280 mm)
Summary of Contents for 1003C
Page 29: ...SAFETY LISTING LABEL PAGE 29 ...
Page 30: ...EPA LABEL PAGE 30 ...