8. A rain cap must be installed on top of the chimney. Failure to install 

a rain cap may cause corrosion problems.

9. Cut and frame square holes in all floors, ceilings, and roof that the 

chimney will go through to provide a 2” (50 mm) clearance between 

the chimney and any combustible materials.  Do not fill this 2” space 

with insulation or any other combustible material.

10. Portions of the chimney which may extend through accessible spaces 

must  be  enclosed  to  avoid  contact  with  combustible  materials  or 

damage to the chimney. 

11.When offsets are used, the pipe may not penetrate a ceiling or floor 

unless it is running vertical (no 30° offsets).

Figure 21

THE CHIMNEY SYSTEM

Chimney Installation Notes

1. If possible, install an interior chimney as it will provide better per-

formance.  In areas with continuous temperatures below 18°C (0°F), 

the use of an exterior chimney increases the likelihood of operating 

problems such as low draft, high rate of creosoting, and poor start-up 

characteristics.  Exterior chimneys are also prone to down-drafting 

and flow reversal.  Installations which are located on lower floors in 

the house, such as in a basement, in combination with an outside 

chimney, are especially prone to flow reversal.

2. The fireplace model MONTEST may be installed only with Security 

Chimneys International Ltd  7” dia. chimney systems model Secure 

Temp™

  

S2100+ / Nova Temp™

  

HT6000 / Secure Temp GX (U.S. only) 

or ACBI.

3. A chimney venting a fireplace shall not vent any other appliance.

4. The minimum chimney height is 12 feet (3.7 m) excluding the fire-

place.

5. All chimney installations must include at least one support in order to 

be able to take any lateral load.  The maximum chimney length that 

can be supported by the fireplace is nine (9) feet (2.75 m) for Secure 

Temp

 

S2100+ / Nova Temp

 

 / Secure Temp

 

GX and 26 feet 

(8m) for ACBI chimney.  In altitude, add 18” (450 mm) to the chimney 

for every 2,000 feet (600 m) above sea level.

6. The chimney must extend at least three (3) feet (915 mm) above its 

point of contact with the roof and at least two (2) feet (610 mm) higher 

than any wall, roof or building within ten (10) feet (3 m) of it (

Figure 

21

).

7. If the chimney extends higher than five (5) feet (1,500 mm) above 

its point of contact with the roof, it must be secured using a roof 

brace.

ten (10) feet

three (3) feet Min.

two (2) feet Min.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

13

Summary of Contents for 038M

Page 1: ...HESE INSTRUCTIONS FOR FUTURE REFERENCE Listed to standards ULC S610 UL 127 Report No 304 7213 EPA Cert No 609 WARNINGS Hot Do not touch The glass and surfaces of this appliance will be hot during oper...

Page 2: ...re left partly opened smoke may be drawn into the room Use optional firescreen when doors are fully opened WARNING Usecarewhenselectingwindow treatments for windows located near the fireplace Avoid us...

Page 3: ...Required Fireplace model MONTEST 7 diameterchimney Model SecureTemp S 2100 Nova Temp HT6000 Secure TempGX U S only or ACBI manufactured by Security Chimneys International only including Chimney lengt...

Page 4: ...lburnveryintenselyus ing this method and may damage the firebox Medium Combustion This is the recommended mode of operating the Montecito Estate and should be the one normally used since it will depos...

Page 5: ...g time will be between 6 8 hours and at this combustion rate the level of BTU s is at its lowest Building a Fire A To start a fire place several crumpled up ballsofnewspaperinthefirebox Placesmall dry...

Page 6: ...he chimney WARNING When cleaning the fireplace the ashes should be placed in a metal container with a tight fitting lid The closed container of ashes should be placed on a non combustible floor or on...

Page 7: ...s 1 400 F If the glass breaks or cracks it must be replaced with an identical ceramic glass Tempered glass or ordinary glass will not withstand the high temperatures of the Montecito Estate Replacemen...

Page 8: ...1 A Frame the fireplace using 2 x 3 or heavier lumber B WARNING Combustible materials cannot be used in the space directly above the fireplace except for the studs above the fa cade that support the f...

Page 9: ...3 4 705 mm J 66 3 8 1686 mm Notes Due to Lennox ongoing commitment to quality all specifications ratings and dimensions are subject to change without notice All framing dimensions calculated for 1 2 d...

Page 10: ...It is located in the bottom of the fireplace towards the back It uses 120 V and must be connected to the main electrical circuit byaqualifiedelectrician Forconnection usethe electrical box supplied wi...

Page 11: ...heat A furnace duct is only single wall and not double wall as is required for the Montecito Estate hot air exhaust 7 Use only Security Chimneys International grills and components as described in thi...

Page 12: ...above or below floor level Makea4 1 4 110mm holeintheoutsidewallofthehouseatthechosen location From outside place the outside air register in the hole open side down and fasten the register to the wal...

Page 13: ...are located on lower floors in the house such as in a basement in combination with an outside chimney are especially prone to flow reversal 2 The fireplace model MONTEST may be installed only with Se...

Page 14: ...rsal support AC10SU 4 Put the roof flashing in place and seal the joint between the roof and the flashing with roofing pitch see Figures 25 26 For sloping roofs place the flashing under the upper shin...

Page 15: ...uctions on Page 14 5 From below install a firestop See Figure 23a 6 A support XST or XSO must be used on the first 15 section 5 m 7 Continue with the regular installation ACBI Chimney 1 Install the fi...

Page 16: ...mm 45 21 32 1160 mm 54 1 8 1375 mm B 17 9 16 446 mm 20 7 16 519 mm 24 5 8 625 mm 28 7 8 733mm 37 3 8 949 mm 42 1067 mm 44 3 4 1137 mm 49 1245 mm 59 9 32 1353 mm 61 3 4 1568 mm Chimney Elbow Offset Hei...

Page 17: ...diation Shield Framing 2 x 3 Figure 29 Roof Support Note In cold areas it is recommended to protect the chimney in a insulated chase Straps Chimney ACBI ACBI Starter Section Straps Outside Wall OFFSET...

Page 18: ...t of supported chimney NOTE For the ACBI chimney a support section ACBI7SL must be used every 30 feet 9m or an universal support every 20 feet 6m instead of the universal roof support ST CHIMNEY MAXIM...

Page 19: ...ill enter the masonry chimney 2 In the middle of the oval drill a hole in the masonry chimney at 30 3 Increase the size of the hole until a 30 TUBINOX liner elbow can be easily slipped through 4 Slide...

Page 20: ...ECMC H4855 Outside Air Kit included with fireplace Outside Air Coupler To Connect Outside Air UZI To Fireplace UZIAD UZIAD Outside Air Ducting includes 4 insulated flex x 10 long UZI UZI Gravity Kit G...

Page 21: ...ashing Adjustable 30 45 includes spacer collar ACBI7FBR H3277 Misc Firestop ACBI7BF H3268 Radiation Shield ACBI7RS H3269 Attic Radiation Shield ACBI7RSA H3270 Telescopic Attic Radiation Shield ACBI7RS...

Page 22: ...PR SR2417 Right Side Refractory Bricks Front PR SR2419 Left Side Refractory Bricks Back PR SR2416 Left Side Refractory Bricks Front PR SR2418 Bottom Refractory Brick PR SR2422 Wooden Door Handle PR SR...

Page 23: ...NOTES 23...

Page 24: ...ction which were not manufactured or supplied by LHP or for the labor necessary to install repair or remove such materials parts or construction All replacement or repair components will be shipped F...

Reviews: