background image

4

460989001B 

CPU status LED D45 possible module error conditions for LED Normal and 
Series 2 modes:

Mounting

The SDC can be mounted in the LNL-AL400ULX or LNL-AL600ULX-
4CB6 and the LNL-CTX or LNL-CTX6 enclosure using the Universal 
Mounting Plate (UMP) LNL-CONV-U2. The universal mounting plate can 
hold up to two (2) LNL-1300-U modules.

Mounting the SDC in the LNL-AL400ULX and LNL-CTX

Mounting the SDC in the LNL-AL600ULX-4CB6 or LNL-CTX6

Error condition

Flashing 
pattern

Description

No valid 
application 
firmware

3 Red, 
2 Green

The module is not operational. 
Firmware must be loaded using a 
console, e.g. HyperTerminal with 
Xmodem.

Boot loader waiting 
on firmware file

3 Red, 
1 Green

Console boot loader is waiting on 
start of firmware file.

Boot loader loading 
firmware file

2 Red, 
2 Green

Console boot loader is loading a 
firmware file.

Invalid EFL file

1 Red, 
2 Green

The EFL specified to be loaded 
using the console loader is not a 
valid EFL file.

Invalid Xmodem 
packet

1 Red, 
1 Green

The console loader received an 
invalid Xmodem packet and 
terminated the firmware 
download operation.

Invalid Application 
firmware for 
module CPU

3 Red, 
0 Green

The module is not operational. 
Application firmware loaded on 
the module will not run properly. 
Requires new firmware be loaded 
using the console boot loader or 
the module must be returned for 
repair.

Invalid Boot 
firmware for 
module CPU

2 Red, 
3 Green

The module is not operational. 
Boot loader firmware loaded on 
the module will not run properly. 
The module must be returned for 
repair.

Firmware update 
failed

1 Red, 
3 Green

Firmware update operation was 
unsuccessful. Retry and if it fails 
continuously, load a different 
firmware file.

No valid primary 
firmware copy

3 Green, 
2 Red

The firmware flash contains 2 
copies of the application 
firmware. The primary copy is 
not valid so the backup copy will 
be loaded into the primary copy 
and executed.

No valid backup 
firmware copy

3 Green, 
1 Red

The firmware flash contains 2 
copies of the application 
firmware. The backup copy is not 
valid so the primary copy will be 
loaded into the backup copy.

No valid 
manufacturing 
parameters

3 Green, 
0 Red

The manufacturing parameters 
which include the serial number, 
etc. are invalid. The module must 
be returned for repair.

Summary of Contents for LNL-1300-U

Page 1: ...es a 12 to 24 VDC power source SDC board Dimensions are in inches mm Package Contents LNL 1300 U board 1000 ohm resistors Installation To install the SDC perform the installation procedures described...

Page 2: ...bps off ON off ON 38400 bps ON ON ON ON SW1 Switch 5 State ON LEDs behave as the Access LNL series module off LED behavior is in Normal Mode Address SW2 switch 5 4 3 2 1 0 off off off off off 1 off o...

Page 3: ...Ds LED Table for Series 2 LNL 1300 Mode When switch 5 is in the ON position the LEDs behave like the series 2 LNL 1300 LED Table for Normal Mode When SW1 switch 5 is in the off position the LEDs opera...

Page 4: ...modem packet and terminated the firmware download operation Invalid Application firmware for module CPU 3 Red 0 Green The module is not operational Application firmware loaded on the module will not r...

Page 5: ...hms maximum Belden 9841 West Penn or equivalent The drop cables to downstream devices should be kept as short as possible no longer than 10 feet The RS 485 communication is asynchronous half duplex us...

Page 6: ...ing LCD reader display control Wiring for OSDP readers Elevator Control OnGuard hardware is capable of supporting elevator control for up to 128 floors An elevator reader has an input output module th...

Page 7: ...uires a 12 to 24 VDC 10 power source for it input power Wire the power input with 18 AWG minimum twisted pair cable Power source wiring Notes Be sure to observe polarity Do not use an AC transformer t...

Page 8: ...o 95 at 85 C 185 F non condensing storage Certifications FCC Part 15 FCC compliance This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15...