DirecDoor Installation Guide
35
Safe Shutdown Procedure for the DirecDoor Board
UCSIMMPlus Board LEDs
Safe Shutdown Procedure for the DirecDoor Board
The following procedure can be performed when in normal operation mode.
1.
Press SW6 and hold SW6 for 3 seconds until D14 through D21 turn on and stay on.
2.
Wait for about 5 seconds.
At this point power to the CPU board may be removed or reset via SW5.
Note:
The halt state lasts for approximately 40 to 45 seconds, after which the system will auto-
restart.
D27
Door Contact 2
Indicates physical input state.
•
ON
- Closed
•
OFF
- Open
•
Flashing
- Fault
D28
Door REX 2
Indicates physical input state.
•
ON
- Closed
•
OFF
- Open
•
Flashing
- Fault
UCSIMMPlus Board LED Indicators
LEDs
Color
Purpose (Type 2 SIMM and Type 3 SIMM)
DS1 and DS5
Green
ON
- Link activity present.
OFF
- No link activity present.
Flashing
- Network activity detected.
DS2 and DS6
Yellow
ON
- 100 Mbps
OFF
- 10 Mbps
DS3 and DS7
Red
ON
- Full duplex
OFF
- Half duplex
DS4 and DS8
Red
ON
– Collision
Input LEDs on the DirecDoor Board (Continued)
LED Number
Name
Description
Summary of Contents for DirecDoor
Page 1: ...7 4 DirecDoor Installation Guide...
Page 4: ......
Page 8: ...Table of Contents 8 DirecDoor Installation Guide...
Page 14: ...Introduction 14 DirecDoor Installation Guide...
Page 19: ...DirecDoor Installation Guide 19 Mounting DirecDoor Mounting Template...
Page 22: ...Installation Planning and Mounting 22 DirecDoor Installation Guide...
Page 56: ...DDIO Interface 56 DirecDoor Installation Guide Resistances Detected by PXNplus...
Page 58: ...DO Interface 58 DirecDoor Installation Guide Wiring Output Device to DO Interface...
Page 76: ...Controller Firmware Tools 76 DirecDoor Installation Guide...
Page 79: ...DirecDoor Installation Guide 79 CE Regulatory Notice CE Regulatory Notice...