LEM reserves the right to carry out modifications on its transducers, 

 

in order to improve them.

LEM International SA 

Route du Nant-d’Avril, 152

1217 Meyrin 

 www.lem.com

ITZ 2000-SBPR FLEX ULTRASTAB

Safety

This transducer must be used in limited-energy secondary circuits according to IEC 61010-1.

 

Caution

This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in 

accordance with the manufacturer’s operating instructions. 

If the device is used in a way that is not specified by the manufacturer, the protection provided by the device may be 

compromised. Always inspect the electronics unit and connecting cable before using this product and do not use it if damaged. 

Mounting assembly shall guarantee the maximum primary conductor temperature, fulfill clearance and creepage distance,  

minimize electric and magnetic coupling.

  

Caution, risk of electrical shock

Use caution during installation and use of this product; certain parts of the module can carry hazardous voltages and high currents 

(e.g. primary conductor). 

Ignoring this warning can lead to injury and or/or cause serious damage.

De-energize all circuits and hazardous live parts before installing the product.

All installations, servicing operations and use must be carried out by trained and qualified personnel practicing applicable safety 

precautions.

This transducer is a built-in device, no maintenance required; cleaning by dry compressed air is authorized.

This transducer is a build-in device, whose hazardous live parts must be inaccessible after installation.

This transducer must be mounted in a suitable end-enclosure.

Besides make sure to have a distance of minimum 30 mm between the primary conductor (return bar) and the transducer and 

other neighboring components.

Main supply must be able to be disconnected.

Always inspect the current transducer for damage before using this product.

Never connect or disconnect the power while the primary circuit is connected to live parts.

Never connect the output to any equipment with a common mode voltage to earth greater than 30 V.

Always wear protective clothing and gloves if hazardous live parts are present in the installation where the measurement is carried 

out.

Safe and trouble-free operation of this transducer can only be guaranteed if transport, storage and installation are carried out 

correctly and are carried out with care.

The current transducer shall not be opened or modified.

If not working, the current transducer shall be replaced by an equivalent device.

In case of main supply cable replacement, make sure to use similar cable to guaranty the safety; please refer to the user 

manual for more information.

ESD susceptibility

The product is susceptible to ESD damage if secondary connectors pins are touched without being properly grounded.

Remark

Installation of the transducer must be done unless otherwise specified on the datasheet, according to LEM Transducer Generic 

Mounting Rules. Please refer to LEM document N°ANE120504 available on our Web site: 

https://www.lem.com/en/file/3137/download/

.

Summary of Contents for ITZ 2000-SBPR FLEX ULTRASTAB

Page 1: ...lock port on 9 pin D sub male output connector Secondary current monitoring on BNC connector 4 mm banana sockets for secondary current output Full featured indicator panel Advantages Very high accurac...

Page 2: ...ce required cleaning by dry compressed air is authorized This transducer is a build in device whose hazardous live parts must be inaccessible after installation This transducer must be mounted in a su...

Page 3: ...degree 2 Rated insulation RMS voltage reinforced insulation UNm V 1250 IEC 61010 1 conditions over voltage cat III pollution degree 2 RMS voltage for AC insulation test 50 60 Hz 1 min Ud kV 10 8 Impu...

Page 4: ...230 V RMS PC W VA 48 104 Average Peak RMS noise current 0 10 Hz 4 Ino ppm 0 1 RMS noise current 0 10 kHz 4 2 RMS noise current 0 100 kHz 4 60 Re injected RMS noise on primary bus bar 0 100 kHz V 10 Te...

Page 5: ...o improve them LEM International SA Route du Nant d Avril 152 1217 Meyrin www lem com ITZ 2000 SBPR FLEX ULTRASTAB Typical power consumption 0 10 20 30 40 50 60 2500 2000 1500 1000 500 0 500 1000 1500...

Page 6: ...lit when the transducer head saturates due to excessive primary current 600 A 24000 A yellow LED These LEDs are lit when a transducer head with the corresponding full scale range is connected to the r...

Page 7: ...Status Interlock signal outputs 9 pin D Sub male UNC 4 40 screw lock 8 Option A B These positions are for future expansion or customization not used 2 8 3 1 7 6 5 4 LEM International SA Route du Nant...

Page 8: ...esent on the port each having two dedicated floating pins in the SUBD9 Male connector Collector C and Emitter E Status Interlock port wiring Depending on how each signal is wired it can be Active Low...

Page 9: ...sducer head is not saturated High IP UC The primary current is higher than 105 of nominal full scale output 0 2 V The primary current is lower than 105 of nominal full scale output ACTIVE UC The prima...

Page 10: ...ed off When the rack electronics temperature cools to approximately 60 C the measuring circuit is automatically re enabled and the status LED is again lit Over current protection Electrical specificat...

Page 11: ...ansducer head description Connect the transducer head to the electronics rack using the supplied transducer head cable and mount the programming plug in the 25 pin D Sub connector on the transducer he...

Page 12: ...gh Out 6 Ground 7 US Low Sense 8 US Low Out 9 Current out 10 Current out 11 Current out 12 US High Sense 13 US High Out 14 US Low Sense 15 US Low Out Connect both pins 1 and 9 pins 2 and 10 pins 3 and...

Page 13: ...mount ITZ FLEX ULTRASTAB electronics Transducer head European Schuko CEE 7 7 and US Japanese mains cables 2 m each with three pole IEC C13 female connector Short plug for 4 mm banana terminals and 15...

Page 14: ...nt d Avril 152 1217 Meyrin www lem com ITZ 2000 SBPR FLEX ULTRASTAB Optional Calibration can be separately ordered as per the table hereafter Calibration with certificate in ISO 17025 certificated lab...

Page 15: ...odifications on its transducers in order to improve them LEM International SA Route du Nant d Avril 152 1217 Meyrin www lem com ITZ 2000 SBPR FLEX ULTRASTAB Dimensions Rack electronics in mm general t...

Reviews: