05November2020/V1.0
Page 27/33
4.2.9 Examples of read-outs from the
The following examples of read-outs illustrate how data and parameters are accessed from the
. Note that details in the communication might be realised differently in a specific device.
Blue
Data to the meter,
Green
Data back from the meter.
1) Read-out from read-out table 1:
/?!<CR><LF>
/EMH5\@D4EM4TIIW001--<CR><LF>
<ACK>050<CR><LF>
<STX>1-0:1.8.0*255(000000000.0*kWh)<CR><LF>
1-0:2.8.0*255(000000000.0*kWh)<CR><LF>
1-0:3.8.0*255(000000000.0*kvarh)<CR><LF>
1-0:4.8.0*255(000000000.0*kvarh)<CR><LF>
0-0:F.F.0*255(00000000)<CR><LF>
1-0:0.0.1*255()<CR><LF>
1-0:0.2.0*255(10600000)<CR><LF>
1-0:0.9.1*255(140253)<CR><LF>
1-0:0.9.2*255(121221)<CR><LF>
0-0:C.1.0*255(03878504)<CR><LF>
0-0:C.72.1*255()<CR><LF>
0-0:C.72.2*255()<CR><LF>
1-0:0.8.4*255(5*min)<CR><LF>
1-0:0.3.0*255(6.00*Imp/kWh)<CR><LF>
1-0:0.2.1*1(121120??)<CR><LF>
1-0:0.2.1*50(121120??)<CR><LF>
0-0:C.90.2*255(9F139CC2)<CR><LF>
1-0:C.1.9*255(Point-ID)<CR><LF>
!<CR><LF>
<ETX>+
<SOH>B0<ETX>q
2) Reading of date and time with commands 0.9.2 and 0.9.1 (for ex. on 03.01.2013 at 10:14:15 h):
/?!<CR><LF>
/EMH5\@D4EM4TIIW001--<CR><LF>
<ACK>051<CR><LF>
<SOH>P0<STX>()<ETX>`
<SOH>P1<STX>(00000000)<ETX>a
<ACK>
<SOH>R5<STX>0.9.2()<ETX>\
<STX>0.9.2(130103)<ETX>9
<SOH>R5<STX>0.9.1()<ETX>_
<STX>0.9.1(101415)<ETX>:
<SOH>B0<ETX>q
3) Writing of date and time:
/?!<CR><LF>
/EMH5\@D4EM4TIIW001--<CR><LF>
<ACK>051<CR><LF>
<SOH>P0<STX>()<ETX>`
<SOH>P1<STX>(00000000)<ETX>a
<ACK>
<SOH>W5<STX>1-0:0.9.129*255(1301031605000002)(00000000)<ETX>^
<ACK>
<SOH>B0<ETX>q