17
Measuring sequence:
approx. 2 measurements/s
Measuring time:
typ. 4 sec. incl. reversal of polarity (2 pole or 4 pole)
Max. interference voltage:
≤
3 V AC or DC, with higher voltages measurement will
not be started
Max inductivity:
2 Henry
Max. overload:
Urms = 250 V
Compensation of lead resistance (RK)
Compensation of lead resistance (RK) can be
switched on in functions RE 3pole , RE 4pole
,
R~ , and R
...
2pole
Formation of measured value:
Rdisplay = Rmeasured - Rcompensated*
* Value of setpoint entry RK = 0.000 W, variable
from 0.000…29.99 W by means of measuring
adjustment