5.2
Calling numbers sequence
5.2.1
Standard-sequence
Alarm
Calling number 1
if first party does not acknowledge
Calling number 2
if second party does not acknowledge
Calling number 3
A called party can acknowledge the alarm by sending touch-tone
0
5.2.2
How to program new calling numbers sequence
1. Set function switch to PROG.
2. Enter
**0
.
3. If you want to modify the calling number sequence press
*
followed by the digits of the new sequence (max. 9 digits).
4. Set function switch to OFF.
Sample for programming calling number sequence:
123
Call number 1 first, then number 2, followed by number 3.
111133322
Call number 1 with four attempts, then calling number 3 with three attempts
followed by calling number 2 with two attempts.
231
In normal operation calling number 2 will be used first followed by calling number 3 and in the end
24hour calling number 1.This assures a call to the 24h number in case of power loss combined with battery failure.
Notes:
Calling number sequence is factory set to
123
, and a factory reset
9.2 will NOT RESET sequence.
In emergency operation mode (no battery, no supply) only calling number 1 will be called. Sequence not relevant!
In case a calling number that is part of the sequence is not programmed this number will automatically be skipped.
If a called number is busy and another calling attempt to the same number is set, the waiting time before re-dialling is
set to 30 seconds.
If the calling number changes within the sequence, next number will be dialled without delay.
5.3
Remote programming of calling number and calling number sequence
The calling numbers and calling number sequence can be re-programmed during any telephone connection:
1. Enter touch-tone sequence
**
<n>
(
n
: see table below).
2. If you want to change send
*
, otherwise send
#
.
3. Enter new calling number or sequence.
After entering last digit you have to wait for 10 seconds. The new value will be announced followed by the request
to send touch-tone
<n>
to confirm change.
If you do not confirm within 10 seconds or if another key is pressed you will hear and the old
programming remains active.
<n>
Info
Programming
0
Calling number sequence (9 digits at max)
1
1. Calling number (24 digits at max)
emergency operation number
2
2. Calling number (24 digits at max),
to
9
9. Calling number (24 digits at max)
routine number, alarm due to
power failure
Note:
Enable / disable remote programming
11
to modify press
*
to modify press
*
...
...
If no participant acknowledges the alarm, the hole
sequence can be repeated according to the option
(default: no alarm repetitions
Programming: Abort