E-Flex User Manual, Rev. 1.30
Controller Power Load Capability
Each E-Flex relay panel (EFRP) can provide 24 VDC power for some number of input control
devices – occupancy sensors, daylight sensors, CapT stations, etc. The charts below provide
power supply load information for the E-Flex.
Controller Load Capability
Controller
Unit Load Capacity*
Comments
E-Flex 4 or 8
13
capacity > ULC use an external PS (H4019)
Input Device Unit Loads
Control Device
Unit Load*
Comments
Occupancy Sensor
1
Daylight Sensor
.25
CapT
.25
DTM606
3
DTM612
4
*A unit load is defined as 50mA.
Note:
If the total unit loads is greater than the capacity of the EFRP, install an LPS-
20UL link power supply, P/N H4017. This is +24V with 20 unit load capacity
and 120V/277V AC input.
Switch Configuration
SW1 – Daylight Sensor Inputs
SW1 Position
Daylight Sensor
Active Low* (default)
Active High**
1
Day 1
ON
OFF
2
Day 2
ON
OFF
3
Day 3
ON
OFF
4
Day 4
ON
OFF
*0V reports max light, **10V reports max light.
SW2 – Occupancy Sensor Inputs
SW2 Position Occupancy Sensor
Active Low
Active High (default)
1
Occ 1
ON
OFF
2
Occ 2
ON
OFF
3
Occ 3
ON
OFF
4
Occ 4
ON
OFF