![LEGRAND Wattstopper Series Manual Download Page 3](http://html1.mh-extra.com/html/legrand/wattstopper-series/wattstopper-series_manual_1870567003.webp)
3
Mounting Plate
Ceiling
Stem
Swivel Bracket
Mounting Wedge
Mounting plate
back view
European
3.5”
Octagon
4” Octagon
4” Square
2 Gang
2 Gang
1 Gang
European
3.5”
Octagon
4” Octagon
4” Square
2 Gang
2 Gang
1 Gang
Mounting plate accommodates
different size J-boxes
Sensor Params
LMPX-600
LMPC-600
Mode Auto On
Blink On
Load Type Dim
LMBR-650
For networking
and managing
rooms, floors,
and building
(optional)
LMRC-611MCC
Wireless
Dimmer and/or
Scene Switch
LMPX-600
Wireless
Sensor
IPv6 Mesh for
secure
networking
of DLM
rooms and devices
over 6LoWPAN
Secure Bluetooth
low energy
communication for
mobile App support
DLM Configuration App
on a mobile device
WIRELESS ROOM CONNECTION
Stem
Swivel
Bracket
Snug
Ring
Unlocked
Locked
Mounting
Wedge
Mounting
Bracket
Ball Mount to J-Box
1. Attach the mounting plate to the J-Box with the two included screws.
2. Attach the stem to the back of the swivel bracket by rotating the stem
until secure.
3. Attach the swivel bracket by rotating the stem into the center hole of the
mounting plate until secure.
4. Attach the mounting wedge to the mount end of the swivel bracket,
using the included 10mm screw.
5. Align the slots of the bracket to the ribs on the back of the LMPX-600.
Then slide the LMPX-600 onto the mounting plate.
6. Push snug ring towards plate to adjust sensor angle, then pull snug ring
back towards sensor to lock in place.
Ball Mount to Ceiling
This method is ideal for mounting to a
drop ceiling with ceiling tile.
1. Cut a hole in the ceiling tile the
same diameter as the stem.
2. Attach the stem to the back of the
swivel bracket by rotating the stem
until secure.
3. Line up the center hole in the
mounting plate with the hole in
the ceiling. Then attach the swivel
bracket by rotating the stem into
the center hole of the mounting
plate until secure.
4. Attach the mounting wedge to the
mount end of the swivel bracket,
using the included 10mm screw.
5. Align the slots of the bracket to the
ribs on the back of the LMPX-600.
Then slide the LMPX-600 onto the
mounting plate.
6. Push snug ring towards plate to
adjust sensor angle, then pull snug
ring back towards sensor to lock
in place.
Switch
LMBC-650
Wireless
Network Bridge
LMBR-650
Border Router
LMPX-600
Wireless
Occupancy
Sensor
Line
Voltage
Room
Controller
(LMRC-112)
B
Line Voltage
Switched with
0-10 Volt control
Dimming Ballast
LED Driver, etc.
Load
Examples
(any relay)
A
Switched
etc.
B
Class 1 Dimming
(Class 2 also available)
Sensor Params
LMPX-600
LMPC-600
Mode Auto On
Blink On
Load Type Dim
DLM Configuration App
on a mobile device
Note:
the DLM config app
can only connect with the
LMBC-650 to update firwmare.
You need an LMBR-650 and
LMCS to commision a Hybrid
room.
Distance Recommendations:
30’ max between LMPX-600 and mobile device
60’ max. between LMPX-600 and room controller
or bridge
10’ minimum and 100’ maxmimum between