LEGRAND Wattstopper Series Manual Download Page 1

Wattstopper

 

®

DLM Wireless PIR Corner Mount Occupancy Sensor with IPv6/

Bluetooth

®

 Low Energy Technology

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 27366 – 5/19  rev. 3a

Catalog Numbers • Numéros de Catalogue • Números de Catálogo: LMPX-600, LMPX-600-1, LMPX-600-4

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

SPECIFICATIONS

Power Supply .......................... Battery powered, CR123A Lithium Ion, 3 VDC
Connection to DLM Network ... Wireless via LMRC-611MCC room controllers 
Lens Types
 LMPX-600 .........................................................................Wide Angle 

 LMPX-600-1 .................................................................... Long Range
 LMPX-600-4 ............................................................ Extra Wide Angle
Wireless Hardware
 Radios: 

 ................................................................ Two IEEE 802.15.4

 Frequency: 

 ............................................................................. 2.4Ghz

 Antennas: 

 ................................ IPv6 Mesh and Bluetooth low energy

Wireless Standards
 

Radio 1:  .........................................................IPv6 Mesh (6LoWPAN)

   Range: 

 .......................................................................up to 60 ft.

 

Radio 2:  ............................................................ Bluetooth low energy

   Range: 

 .......................................................................up to 30 ft.

Wireless Encryption
 

AES-128 bit symmetric key, randomly generated per PAN

 

Shared via secured DTLS only

Environment ............................................................... For Indoor Use Only
 

Operating Temperature ...............................32° to 104°F (0° to 40°C)

 

Storage Temperature .................................23° to 140°F (-5° to 60°C)

 

Relative Humidity .....................................5 to 95% (non condensing)

Compliance/Regulatory
 

FCC, RoHS, 

 

Bluetooth certified

 

UL and cUL listed (E101196)

Patent Pending

Once paired to an LMRC-611 wireless room 

controller or LMBC-650 wireless bridge, 

this unit is set for Plug n’ Go operation, 

adjustment via the DLM Configuration App 

is recommended to meet the local energy 

code where installed.

The DLM Wireless corner mount sensor is a wireless 

battery powered PIR occupancy sensor intended for 

operation with wireless room controllers or bridges. 

Once paired to a wireless room controller or bridge, 

it detects and monitors the presence of motion to 

determine if lights should be on or off.

COVERAGE PATTERNS

Coverages shown are maximum and represent half-step walking 

motion.

Side view

8’

Top view

60

0 7’ 12’ 25’

60’

100°

LMPX-600, wide angle lens

8ft

0

8ft

8ft

16ft

16ft

0

6’ 10ft

27ft

60ft

Top View

Side View

16ft

LMPX-600-1, long range lens

8ft

0

8ft

8ft

16ft

16ft

0

6’ 10ft

27ft

60ft

Top View

Side View

16ft

0

10ft

20ft

30ft

40ft 45ft

8ft

Side View

0

10ft

10ft

20ft

20ft

Top View:

LMPX-600-4, extra wide angle lens

Summary of Contents for Wattstopper Series

Page 1: ...r Use Only Operating Temperature 32 to 104 F 0 to 40 C Storage Temperature 23 to 140 F 5 to 60 C Relative Humidity 5 to 95 non condensing Compliance Regulatory FCC RoHS Bluetooth certified UL and cUL listed E101196 Patent Pending Once paired to an LMRC 611 wireless room controller or LMBC 650 wireless bridge this unit is set for Plug n Go operation adjustment via the DLM Configuration App is recom...

Page 2: ...Attach the mounting wedge to the ceiling with the two included 1 mounting screws 2 Align the slots of the bracket to the ribs on the back of the LMPX 600 Then slide the LMPX 600 downward onto the mounting wedge Threaded Rod Mount The threaded rod adapter can mount to a 3 8 16 1 4 20 or 1 2 13 hanging threaded rod 1 Screw the adapter onto the rod 2 Attach the mounting wedge to the adapter using the...

Page 3: ...back towards sensor to lock in place Ball Mount to Ceiling This method is ideal for mounting to a drop ceiling with ceiling tile 1 Cut a hole in the ceiling tile the same diameter as the stem 2 Attach the stem to the back of the swivel bracket by rotating the stem until secure 3 Line up the center hole in the mounting plate with the hole in the ceiling Then attach the swivel bracket by rotating th...

Page 4: ...ll flash on all room controllers The first room controller placed into PtP will become the master 2 Pair the room controllers together Press the Config button once on each room controller This indicates to the rooms controllers that they will be paired with each other The master room controller s LED blink rate will double once the first device is paired to it This faster blink rate is convenient ...

Page 5: ...ND UNIT ADJUSTMENT USING THE DLM CONFIG APP The DLM Config App is available for both iOS and Android devices Search DLM Config on your device to download The app provides the ability to pair various devices in a room Additionally you can modify load binding and edit various DLM parameters for each device For details on the features and operation download the DLM Config App User Guide from the watt...

Page 6: ...NFORMACIÓN DE LA GARANTÍA FCC REGULATORY STATEMENTS This device complies with part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 this device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Cla...

Reviews: