background image

Wattstopper

 

®

DLM - Occupancy Sensor PIR Corner Mount With Dense Lens

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24779 – 09/16  rev. 1

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPX-100

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMPX-100-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltage .............................................................................. 24VDC
Current Consumption .............................................................7mA
Power Supply ................................Wattstopper Room Controllers
Connection to the DLM Local Network ........................ RJ-45 plug
DLM Local Network characteristics when using LMRC-11x/2xx 

room controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 controllers.  

 

Free topology up to 1,000’ max.

Environment ................................................. For Indoor Use Only
 

Operating Temperature .................32° to 131°F (0° to 55°C)

 

Storage Temperature ...................23° to 176°F (-5° to 80°C)

 

Relative Humidity .......................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, adjustment is 

optional.

For full operational details, adjustment and more features of the product, see the 

DLM System Installation Guide provided with Wattstopper room controllers, and 

also available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable regulations, local and 

NEC codes. 

Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 power 

source only. Do not reclassify and install as Class 1, or Power and Lighting Wiring.

SENSOR PLACEMENT

COVERAGE PATTERN

Coverages shown are maximum and represent half-step walking motion.

Side view

10’

Top view

40

0 7’ 15’ 25’

45’

45’

Sensor

30'

30'

Sensor

Ceiling

Reviews: