DLM Enhanced Digital Single Relay Plug Load Controller
Relais numérique simple amélioré – Contrôleur de prises DLM
Controlador DLM de un solo relé para receptáculo de CA

Quick Start Guide • Guide de démarrage rapide • Guía de inicio rápido

No: 24178 – 1/19  rev. 2

Catalog Number • Numéro de Catalogue • Número de Catálogo: LMPL-201

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

LMPL-201-U is BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Input Voltage ....................................................120VAC, 50/60Hz
Load Rating:
 

Maximum Duplex Receptacle Rating ...............120VAC, 20A

Connection to the DLM Local Network .................... 4 RJ-45 ports
DLM Local Network characteristics when using

 

LMPL-201

 

room 

controllers:
 

Low voltage power provided over Cat 5e cable (LMRJ);  

 

max current 800mA. Supports up to 64 load addresses,  

 

48 communicating devices including up to 4 LMRC-10x  

 

series and/or LMPL-101 and/or LMPL-201controllers.  

 

Free topology up to 1,000’ max.

Environment ................................................. For Indoor Use Only
 

Operating Temperature .................32° to 158°F (0° to 70°C)

 

Storage Temperature ...................23° to 176°F (-5° to 80°C)

 

Relative Humidity .......................5 to 95% (non condensing)

Patent Pending

This unit is pre-set for Plug n’ Go™ operation, adjustment is 

optional.

For full operational details, adjustment and more features of the product, see 

the DLM System Installation Guide provided with Wattstopper room controllers, 

and also available at www.legrand.us/wattstopper.

Installation shall be in accordance with all applicable regulations, local and 

NEC codes. Wire connections shall be rated suitable for the wire size (lead and 

building wiring) employed. 

For Class 2 DLM devices and device wiring: To be connected to a Class 2 

power source only. Do not reclassify and install as Class 1, or Power and 

Lighting Wiring.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

PLACEMENT EXAMPLES

Switch

Ceiling Mount

Occupancy

Sensor

Plug Load

Controller

Line Voltage

(Class 1 wiring)

To Plug Load

(Class 1 wiring)

J-Box 

To Other

Electrical

Outlets

Switch

Ceiling Mount

Occupancy

Sensor

Room

Controller

J-Box 

Line Voltage

(Class 1 wiring)

To Plug Load

(Class 1 wiring)

To Lighting

Load

(Class 1 wiring)

To Other

Electrical

Outlets

Line Voltage

(Class 1 wiring)

Plug Load

Controller

J-Box 

CONNECTIVITY

The LMPL-201 communicates to all other DLM 

devices connected to the DLM Local Network. 

Connections shown are for example only. The 

low voltage LMRJ cables can connect to any 

DLM device with an open RJ45 receptacle.
All line voltage wiring is #12 AWG. 

Line

Voltage

Plug Load

Controller

Deep J-Box

Room Controller

Dimmer

Switch

Corner Mount

Sensor

Ceiling Mount

Sensor

DLM Local Network

Low Voltage

LMRJ Cables

LMPL or

LMRC series

Loads

Red wire to Switched Receptacle

Line/Hot

Black wire

Neutral

White wire

Earth Ground/Green wire

Switched

Receptacle

Black wire w/white stripe to Unswitched Receptacle

Unswitched

Receptacle

Ground

Ground

CAUTION:

 TO CONNECT A COMPUTER TO THE DLM LOCAL NETWORK USE THE LMCI-100.   

NEVER CONNECT THE DLM LOCAL NETWORK TO AN ETHERNET PORT

 –  

IT MAY DAMAGE COMPUTERS AND OTHER CONNECTED EQUIPMENT.

Summary of Contents for Wattstopper LMPL-201

Page 1: ...n accordance with all applicable regulations local and NEC codes Wire connections shall be rated suitable for the wire size lead and building wiring employed For Class 2 DLM devices and device wiring...

Page 2: ...nd to this load have their blue LED solid ON Step 2 Load selection Press and release the Config button to step through the loads connected to the DLM Local Network As each load turns ON note the devic...

Page 3: ...e guide d installation du syst me DLM fourni avec les combinateurs Wattstopper et aussi disponible au www legrand us wattstopper L installation doit tre effectu e conform ment tous les r glements ains...

Page 4: ...quement celui qui devient le contr leur principal et les nombres de charges pour chaque relais du r seau local DLM Le contr leur principal est celui qui poss de le num ro de s rie le plus lev Le LMPL...

Page 5: ...ntre le dispositif et le s combinateur s Les mauvais clairages et charges de prise sont contr l s 1 Configurez les boutons d interrupteur et les d tecteurs de mani re contr ler les charges d sir es en...

Page 6: ...je de la red local DLM Cables LMRJ Serie LMPL o LMRC Cargas Cable rojo a recept culo conmutado Cable de l nea negra vivo Cable neutro blanco Cable tierra verde Recept culo conmutado Cable negro con ra...

Page 7: ...PnL a continuaci n se ACTIVAR una carga Esta es la carga N 1 que est vinculada con todos los sensores de ocupaci n de la red local DLM seg n la configuraci n predeterminada de f brica de Plug n Go To...

Page 8: ...nsabilidades por parte de Wattstopper por da os consecuentes que se deriven o est n relacionados con el uso o el rendimiento de este producto u otros da os indirectos con respecto a la p rdida de prop...

Reviews: